9
|
Configuration
Installer reference guide
191
EPRA14~W1 + ETBH/9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
#
Code
Description
[9.9.9]
[5-09]
Limit 1
: 0 kW~20 kW
[9.9.A]
[5-0A]
Limit 2
: 0 kW~20 kW
[9.9.B]
[5-0B]
Limit 3
: 0 kW~20 kW
[9.9.C]
[5-0C]
Limit 4
: 0 kW~20 kW
Priority heater
#
Code
Description
[9.9.D]
[4-01]
Power consumption control DISABLED
[4‑08]=0
▪
0
None
: Backup heater and booster heater
can operate simultaneously.
▪
1
Booster heater
: The booster heater is
prioritised.
▪
2
Backup heater
: The backup heater is
prioritised.
Power consumption control ENABLED
[4‑08]=1/2
▪
0
None
: Depending on the power limitation
level, the booster heater will be limited first,
before the backup heater is limited.
▪
1
Booster heater
: Depending on the
power limitation level, the backup heater will
be limited first, before the booster heater is
limited.
▪
2
Backup heater
: Depending on the power
limitation level, the booster heater will be
limited first, before the backup heater is
limited.
Note:
In case power consumption control is DISABLED (for all models) the setting
[4‑01] defines whether backup heater and booster heater can operate
simultaneously, or if the booster heater/backup heater has priority over the
backup heater/booster heater.
In case power consumption control is ENABLED, the setting [4‑01] defines the
priority of the electrical heaters depending on applicable limitation.
BBR16
See
"5.6.4 BBR16 power limitation"
57] for detailed information about this
functionality.
INFORMATION
Restriction:
BBR16 settings are only visible when the language of the user interface is
set to Swedish.