5
|
Application guidelines
Installer reference guide
31
EPRA14~W1 + ETBH/9W
Daikin Altherma 3 H HT W
4P587501-1B – 2020.10
▪
The heat pump convectors are connected as follows:
-
Warm water → Indoor unit
-
Cold water → Outdoor unit
▪
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
-
The installation manual of the heat pump convectors
-
The installation manual of the heat pump convector options
-
The addendum book for optional equipment
▪
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
▪
The space operation mode is sent to the heat pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
1 (
External room thermostat
):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
0 (
Single zone
): Main
External room thermostat for the
main
zone:
▪
#: [2.A]
▪
Code: [C-05]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Benefits
▪
Cooling.
The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
▪
Efficiency.
Optimal energy efficiency because of the interlink function.
▪
Stylish.
Combination: Underfloor h Heat pump convectors
▪
Space heating is provided by:
-
The underfloor heating
-
The heat pump convectors
▪
Space cooling is provided by the heat pump convectors only. The underfloor
heating is shut off by the shut-off valve.