Drain holes
E
Knockout hole for snow
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface,
raise the unit to provide a free space of more than 150 mm under the outdoor unit.
≥150 mm
7.3.6 To fix the fluorinated greenhouse gases label
1
Fill in the label as follows:
RXXX
d
Contains fluorinated greenhouse gases
kg
tCO
2
eq
GWP × kg
1000
=
GWP: XXX
a
b
c
a
If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of
a
.
b
Total refrigerant charge
c Quantity of fluorinated greenhouse gases
of the total refrigerant charge
expressed as tonnes CO
2
equivalent.
d
GWP = Global warming potential
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label. That GWP is based on
the current legislation on fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.
2
Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.
7.3.7 To prevent the outdoor unit from falling over
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1
Prepare 2 cables as indicated in the following illustration (field supply).
2
Place the 2 cables over the outdoor unit.
3
Insert a rubber sheet between the cables and the outdoor unit to prevent the
cables from scratching the paint (field supply).
4
Attach the ends of the cables.
5
Tighten the cables.