Daikin Altherma 3 GEO EGSAH06UD Series Installation Manual Download Page 2

Table of contents

Installation manual

2

EGSAH/X06+10UD

Daikin Altherma 3 GEO

4P598591-1C – 2023.02

Table of contents

1 About the documentation

2

1.1

About this document..................................................................

2

2 Specific installer safety instructions

3

3 About the box

4

3.1

Indoor unit .................................................................................

5

3.1.1

To remove the accessories from the indoor unit.........

5

3.1.2

To handle the indoor unit ............................................

5

3.2

Domestic hot water tank kit .......................................................

5

3.2.1

To remove the accessories from the domestic hot
water tank kit...............................................................

5

3.3

Checklist for the required DHW accessories .............................

5

4 Unit installation

6

4.1

Preparing the installation site ....................................................

6

4.1.1

Installation site requirements of the indoor unit ..........

6

4.2

Opening and closing the unit.....................................................

6

4.2.1

To open the indoor unit ...............................................

6

4.2.2

To remove the hydro module from the unit .................

7

4.2.3

To close the indoor unit...............................................

9

4.3

Mounting the indoor unit............................................................

9

4.3.1

To install the indoor unit..............................................

9

4.3.2

To connect the drain hose to the drain ....................... 10

5 Piping installation

10

5.1

Preparing piping ........................................................................

10

5.1.1

To check the water volume and flow rate of the
space heating circuit and brine circuit......................... 10

5.2

Connecting the brine piping.......................................................

10

5.2.1

To connect the brine piping......................................... 10

5.2.2

To connect the brine level vessel................................ 11

5.2.3

To connect the brine filling kit ..................................... 11

5.2.4

To fill the brine circuit .................................................. 11

5.2.5

To insulate the brine piping......................................... 12

5.3

Connecting water piping ............................................................

12

5.3.1

To connect the water piping........................................ 12

5.3.2

To connect the water piping for domestic hot water ... 13

5.3.3

To connect the recirculation piping ............................. 14

5.3.4

To fill the space heating circuit.................................... 14

5.3.5

To fill the domestic hot water tank .............................. 14

5.3.6

To check for water leaks ............................................. 14

5.3.7

To insulate the water piping ........................................ 14

6 Electrical installation

15

6.1

About electrical compliance.......................................................

15

6.2

Safety device requirements .......................................................

15

6.3

Overview of electrical connections for external and internal
actuators....................................................................................

15

6.4

To connect the main power supply............................................

16

6.5

To connect the remote outdoor sensor .....................................

19

6.6

To connect the shut-off valve ....................................................

19

6.7

To connect the electricity meters...............................................

20

6.8

To connect the domestic hot water pump .................................

20

6.9

To connect the alarm output......................................................

20

6.10

To connect the space cooling/heating ON/OFF output .............

21

6.11

To connect the changeover to external heat source .................

22

6.12

To connect the power consumption digital inputs .....................

22

6.13

To connect the safety thermostat (normally closed contact) .....

23

6.14

To connect the brine low pressure switch .................................

23

6.15

To connect the thermostat for passive cooling..........................

24

6.16

LAN adapter ..............................................................................

24

6.16.1

About the LAN adapter ............................................... 24

6.16.2

Overview of electrical connections.............................. 25

6.16.3

Router ......................................................................... 26

6.16.4

Electricity meter .......................................................... 26

6.16.5

Solar inverter/energy management system ................ 27

7 Configuration

28

7.1

Overview: Configuration ............................................................. 28

7.1.1

To access the most used commands .......................... 28

7.2

Configuration wizard................................................................... 29

7.2.1

Configuration wizard: Language .................................. 29

7.2.2

Configuration wizard: Time and date ........................... 29

7.2.3

Configuration wizard: System ...................................... 29

7.2.4

Configuration wizard: Backup heater ........................... 30

7.2.5

Configuration wizard: Main zone.................................. 31

7.2.6

Configuration wizard: Additional zone.......................... 31

7.2.7

Configuration wizard: Tank .......................................... 32

7.3

Weather-dependent curve .......................................................... 32

7.3.1

What is a weather-dependent curve? .......................... 32

7.3.2

2-points curve .............................................................. 33

7.3.3

Slope-offset curve ........................................................ 33

7.3.4

Using weather-dependent curves ................................ 34

7.4

Settings menu ............................................................................ 35

7.4.1

Main zone .................................................................... 35

7.4.2

Additional zone ............................................................ 35

7.4.3

Information ................................................................... 35

7.4.4

Brine freezing temperature .......................................... 35

7.5

Menu structure: Overview installer settings................................ 36

8 Commissioning

37

8.1

Checklist before commissioning ................................................. 37

8.2

Checklist during commissioning ................................................. 37

8.2.1

To perform an air purge on the water circuit ................ 37

8.2.2

To perform an air purge on the brine circuit................. 38

8.2.3

To perform an operation test run ................................. 38

8.2.4

To perform an actuator test run ................................... 38

8.2.5

To perform an underfloor heating screed dryout.......... 38

8.2.6

To start or stop 10-day brine pump operation.............. 39

9 Hand-over to the user

39

10 Maintenance and service

40

10.1

Maintenance safety precautions................................................. 40

10.2

Yearly maintenance.................................................................... 40

10.2.1

Yearly maintenance: overview ..................................... 40

10.2.2

Yearly maintenance: instructions ................................. 40

10.3

To drain the domestic hot water tank ......................................... 41

10.4

To inspect the inside of the domestic hot water tank ................. 42

11 Technical data

43

11.1

Piping diagram: Indoor unit ........................................................ 43

11.2

Wiring diagram: Indoor unit ........................................................ 44

11.3

Technical specifications: Domestic hot water tank ..................... 48

11.3.1

Test results in accordance with EN12897 (2016) ........ 48

11.3.2

Warning label ............................................................... 48

1

About the documentation

1.1

About this document

INFORMATION

Make sure that the user has the printed documentation and
ask him/her to keep it for future reference.

Target audience

Authorised installers

Documentation set

This  document  is  part  of  a  documentation  set.  The  complete  set
consists of:

General safety precautions:

▪ Safety instructions that you must read before installing

▪ Format: Paper (in the box of the unit)

Summary of Contents for Altherma 3 GEO EGSAH06UD Series

Page 1: ...Installation manual Daikin Altherma 3 GEO English Installation manual Daikin Altherma 3 GEO EGSAH06UD 9W EGSAH10UD 9W EGSAX06UD 9W EGSAX10UD 9W 1 2 3 9 A B C Z 1 2 3 9...

Page 2: ...normally closed contact 23 6 14 To connect the brine low pressure switch 23 6 15 To connect the thermostat for passive cooling 24 6 16 LAN adapter 24 6 16 1 About the LAN adapter 24 6 16 2 Overview of...

Page 3: ...an be downloaded for iOS and Android devices using the QR codes below Registration to the Stand By Me platform is required to access the app App Store Google Play 2 Specific installer safety instructi...

Page 4: ...y cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Do NOT push or place redundant cable length into the unit...

Page 5: ...the unit Remove the hydro module before you carry the unit up or down staircases See 4 2 2 To remove the hydro module from the unit 47 It is recommended to use lifting straps to carry the unit up or...

Page 6: ...nd the following requirements and precautions WARNING Do NOT pierce or burn refrigerant cycle parts Be aware that the refrigerant inside the system is odourless WARNING The appliance shall be stored s...

Page 7: ...ain power supply 416 3 T25 5 Open the installer switch box as follows 2 T25 6 In case you have to install additional options that require access to the main switch box remove the main switch box cover...

Page 8: ...module to the main switch box or other locations Route the wires through the grommets of the upper hydro module cover X22Y X11YB X803YA X1YA 7 Remove the upper hydro module cover You can lift up the...

Page 9: ...the remaining steps as described in 4 2 2 To remove the hydro module from the unit 47 4 2 3 To close the indoor unit 1 If applicable reinstall the left side panel 2 If applicable reinsert the hydro m...

Page 10: ...uate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded see 5 3 2 To connect the water piping for domestic hot water 413 The minimum fluid pressure to operate is 1 bar...

Page 11: ...low the vessel 5 Remove the safety valve on top of the vessel 6 Top up the vessel with brine until it is approximately 2 3 filled 7 Reconnect the safety valve 8 Open the shut off valve below the vesse...

Page 12: ...f the valve NOTICE Expansion vessel An expansion vessel field supply MUST be installed on the entering piping before the water pump within 10 m of the unit NOTICE A pressure relief valve field supply...

Page 13: ...ief valve combination to the water mains inlet 7 Install the tundish part of the kit in a vertical position within a maximum of 600 mm away from the pressure reducing valve pressure relief valve combi...

Page 14: ...grommet on top of the unit and remove the stop The recirculation connector is located below the space heating cooling water outlet pipe 3 Route the recirculation piping through the grommet and connect...

Page 15: ...gislation Selection and sizing of the wiring should be done in accordance with the applicable legislation based on the information mentioned in the table below Make sure that a separate power supply c...

Page 16: ...manual of the remote indoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 2 External sensor Room 1 7 Room sensor offset Current sensors See the installation manual of the current...

Page 17: ...Open the unit a 6 Dual cable power supply split power supply Preferential kWh rate power supply with separate normal kWh rate power supply b C1 C2 C3 X5M Z1F X2M C5 C1 Normal kWh rate power supply for...

Page 18: ...m Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB The voltage free contact shall ensure the minimum applicable load of 15 V DC 10 mA Connect the preferential kWh...

Page 19: ...ing 1 0A 1 Connect the external temperature sensor cable to the indoor unit a c d b a Factory mounted cable b Splicing connectors field supply c Remote outdoor sensor cable 40 m delivered as accessory...

Page 20: ...A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open the following see 4 2 1 To open the indoor unit 46 1 Top panel 1 3 2 2 User interface panel 3 Installer switch box cover 2 Connect the domest...

Page 21: ...1 Top panel 3 2 5 1 4 2 User interface panel 3 Front panel 4 Installer switch box cover 5 Main switch box cover 2 Connect the alarm output cable to the appropriate terminals as shown in the illustrat...

Page 22: ...1 2 4 2 User interface panel 3 Front panel 4 Main switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below 1 2 X2X1 L N X...

Page 23: ...commend the following The safety thermostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There is a minimum distance of 2 m between the safety...

Page 24: ...onnectors field supply c Wires from the brine low pressure switch cable field supply 3 Fix the cable with cable ties to the cable tie mountings 6 15 To connect the thermostat for passive cooling INFOR...

Page 25: ...method On the user interface make sure to set 2 9 2 Control Room thermostat Smart Grid application Item Requirement LAN adapter software It is recommended to ALWAYS keep the LAN adapter software up to...

Page 26: ...directly Depending on the wireless bridge or power line adapter model the system might not function properly NOTICE To prevent communication problems due to cable breakdown do NOT exceed the minimum b...

Page 27: ...he domestic hot water tank and or the room WITH power limitation Closed Open Forced OFF Deactivation of unit and electrical heater operation in case of high energy tariffs Open Closed Forced ON Energy...

Page 28: ...u structure or the overview settings INFORMATION When the configuration wizard is finished the user interface will show an overview screen and request to confirm When confirmed the system will restart...

Page 29: ...ing installation or service this behaviour is undesired Therefore the protective functions can be disabled For more information see the Installer reference guide chapter Configuration 7 2 1 Configurat...

Page 30: ...e zone Only one leaving water temperature zone a a Main LWT zone Code Description 4 4 7 02 1 Dual zone Two leaving water temperature zones The main leaving water temperature zone consists of the highe...

Page 31: ...floor heating Maximum 55 C 1 Fancoil unit Maximum 65 C 2 Radiator Maximum 65 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is decide...

Page 32: ...make use of the comfort setpoint as a preset value When you later want to change the storage setpoint you only have to do it in one place The tank will heat up until the storage comfort temperature ha...

Page 33: ...X2 Y1 Example Y1 Y2 X1 X2 a Item Description a Selected weather dependent zone Main zone or additional zone heating Main zone or additional zone cooling Domestic hot water X1 X2 Examples of outdoor am...

Page 34: ...o to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent...

Page 35: ...f problems 7 4 4 Brine freezing temperature Brine freezing temperature Depending on the type and concentration of the anti freeze in the brine system the freezing temperature will differ The following...

Page 36: ...l Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater Current sensor offset BBR16 activation BBR16 power limit 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External s...

Page 37: ...ed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connec...

Page 38: ...temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor t...

Page 39: ...is ON The unit operates as normal except that the brine pump operates continuously for 10 days independent of compressor status OFF Brine pump operation is linked to compressor status Conditions All o...

Page 40: ...See 4 2 1 To open the indoor unit 46 Temperature and pressure relief valve Check for correct operation of the temperature and pressure relief valve Manually operate the temperature and pressure relie...

Page 41: ...complete tank including the piping between the relief valve and cold water inlet To make sure this water originates from the tank check after a tank heat up cycle INFORMATION It is recommended to perf...

Page 42: ...Prerequisite Stop the unit operation via the user interface Prerequisite Turn OFF the respective circuit breaker Prerequisite Close the cold water supply Prerequisite Open all the hot water tapping po...

Page 43: ...side B Refrigerant side C Water side D Field supplied E Field installed delivered with the unit F DHW tank a1 Space heating water IN 22 mm a2 Space heating water OUT 22 mm b1 Domestic hot water cold...

Page 44: ...400 V 6 9 kW User installed options User installed options Remote user interface Remote user interface Human Comfort Interface Ext indoor thermistor External indoor thermistor Digital I O PCB Digital...

Page 45: ...er supply 6 9 kW Only for dual cable power supply Only for dual cable power supply Only for single cable power supply Only for single cable power supply English Translation Only for split 1F BUH 1F co...

Page 46: ...Only for wireless On OFF thermostat Only for wireless On OFF thermostat 9 Current sensors 9 Current sensors SWB Switch box 10 Brine pressure loss detection 10 Brine pressure loss detection SWB Switch...

Page 47: ...ntial kWh rate unit power supply installation Only with EKGSPOWCAB Compressor power supply 230 V earth Only with EKGSPOWCAB POWER SUPPLY FIELD SUPPLY OPTIONAL PART Only for EKCSENS INDOOR UNIT STANDAR...

Page 48: ...arts Contact your local Daikin dealer Installed by name address tel No completion date TECHNICAL SPECIFICATIONS EN12897 2016 Maximum water supply pressure to pressure reducing valve 16 bar Operating p...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...4P598591 1C 2023 02 Copyright 2019 Daikin 4P598591 1 C 00000009 Verantwortung f r Energie und Umwelt...

Reviews: