6 Electrical installation
Installation manual
15
EGSAH/X06+10UD
Daikin Altherma 3 GEO
4P598591-1C – 2023.02
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
CAUTION
Do NOT push or place redundant cable length into the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
For the models EGSAH/X06+10(U)D▲9W▼(G), the following
statement…
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
…is valid in the following cases:
#
Power supply
(a)
Operation
(b)
1
Combined power supply
(1N~, 50 Hz, 230 V AC)
C1
1N~, 50 Hz,
230 V AC
Normal or emergency
2
Split power supply
(2×(1N~, 50 Hz, 230 V AC))
C1
C5
1N~, 50 Hz,
230 V AC
1N~, 50 Hz,
230 V AC
Emergency
(a)
For details of C1 and C5, see
"6.4 To connect the main power
(b)
Normal operation:
backup heater = maximum 3 kW
Emergency operation:
backup heater = maximum 6 kW
6.2
Safety device requirements
Power supply
The power supply must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.
Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below.
Make sure that a separate power supply circuit is provided for this
unit and that all electrical work is carried out by qualified personnel
according to local laws and regulations and this manual. An
insufficient power supply capacity or improper electrical construction
may lead to electric shocks or fire.
For EGSAH/X06+10(U)D▲9W▼(G):
Power supply
Minimum circuit
ampacity
Recommended
fuses
1N~ 50 Hz
230 V
29 A
32 A
3N~ 50 Hz
380-415 V
15.5 A
16 A
6.3
Overview of electrical connections
for external and internal actuators
Item
Description
Power supply
"6.4 To connect the main power
Remote outdoor
sensor
"6.5 To connect the remote outdoor
19].
Shut-off valve
19].
Electricity meter
"6.7 To connect the electricity
Domestic hot water
pump
"6.8 To connect the domestic hot water
20].
Alarm output
20].
Space cooling/heating
operation control
"6.10 To connect the space cooling/
Changeover to
external heat source
control
"6.11 To connect the changeover to
Power consumption
digital inputs
22].
Safety thermostat
"6.13 To connect the safety thermostat
23].
Brine low pressure
switch
"6.14 To connect the brine low
23].
Thermostat for passive
cooling
"6.15 To connect the thermostat for
24].
LAN adapter
connections
24].