This section describes program features . For each feature, there is a list of related user settings, actual signals, and
fault and alarm messages .
Programmable Analog Inputs
The drive has two programmable analog voltage/current
inputs. The inputs can be inverted, filtered and the maximum
and minimum values can be adjusted . The update cycle for
the analog input is 8 ms (12 ms cycle once per second) . The
cycle time is shorter when information is transferred to the
application program (8 ms -> 2 ms) .
Table 2: Programmable Analog Input Settings
Table 3: Programmable Analog Input Diagnostics
Programmable Analog Output
One programmable current output (0…20 mA) is available .
Analog output signal can be inverted, filtered and the maximum
and minimum values can be adjusted . The analog output
signals can be proportional to motor speed, output frequency,
output current, motor torque, motor power, etc . The update
cycle for the analog output is 2 ms .
It is also possible to write a value to an analog output through a
serial communication link .
Table 4: Programmable Analog Output Settings
Table 5: Programmable Analog Output Diagnostics
Parameter
Additional Information
Group 11:Reference
Select AI as reference source
Group 13: Analog Inputs
Analog input processing
3001, 3021, 3022, 3107
AI loss supervision
Group 35: Motor Temp Meas
AI in motor temperature measurement
Group 40: Process PID Set 1 …
Group 42: External PID
AI as PID process control reference
or actual value source
Group 44: Pump Protection
AI as pump protection measurement
source
Actual Signal
Additional Information
0120, 0121
Analog input values
1401 AI1/A2
signal loss
Alarm
AI1 LOSS / AI2 LOSS
AI1/AI2 signal below AI1/AI2 FAULT
LIMIT (3021/3022)
Fault
AI1 LOSS / AI2 LOSS
AI1/AI2 signal below limit AI1/AI2
FAULT LIMIT (3021/3022)
PAR AI SCALE
Incorrect AI signal scaling (1302 <
1301 or 1305 < 1304)
Parameter
Additional Information
Group 15: Analog Outputs
AO value selection and processing
Group 35: Motor Temp Meas
AO in motor temperature
measurement
Actual Signal
Additional Information
0124
AO value
Fault
PAR AO SCALE
Incorrect AO signal scaling (1503 <
1502)
OM 1190-1 • MD4 VFD 24 www .DaikinApplied .com