10
910193093 Output Chart
1st Cool
2nd Cool
1st Heat
2nd Heat
Water Source Heat Pump (w/ Low Speed Fan)
Y1, G
Y1, Y2, G
W1, G
W1, W2, G
Water Source Heat Pump (w/High Speed Fan)
Y1, G2
Y1, Y2, G2
W1, G2
W1, W2, G2
Electric
Y1, G
Y1, Y2, G
W1, G
W1, W2, G
Electric (w/ High Speed Fan)
Y1, G2
Y1, Y2, G2
W1, G2
W1,W2, G2
Heat Pump (One Compressor)
Y1, G, O
Y1, G, O
Y1, G, B
Y1, W2, G, B
Heat Pump (One Compressor w/ High Speed Fan)
Y1, G2, O
Y1, G2, O
Y1, G2, B
Y1, W2, G2, B
Heat Pump (Two Compressors)
Y1, G, O
Y1, Y2, G, O
Y1, G, B
Y1, Y2, G, B
Heat Pump (Two Compressors w/ High Speed Fan)
Y1, G2, O
Y1, Y2, G2, O
Y1, G2, B
Y1, Y2, G2, B
910193126 Output Chart
1st Cool
2nd Cool
1st Heat
2nd Heat
Water Source Heat Pump
Y1, G
Y1, Y2, G
W1
W1, W2
Electric
Y1, G
Y1, Y2, G
W1, G
W1, W2, G
Heat Pump (One Compressor)
Y1, G, O
Y1, G, O
Y1, G, B
Y1, W2, G, B
Heat Pump (Two Compressors)
Y1, G, O
Y1, Y2, G, O
Y1, G, B
Y1, Y2, G, B
910193127 Output Chart
1st Cool
2nd Cool
3rd Cool
1st Heat
2nd Heat
Water Source Heat Pump
Y1, G
Y1, Y2, G
Y1, Y2, Y3
W1
W1, W2
Electric
Y1, G
Y1, Y2, G
Y1, Y2, Y3, G
W1, G
W1, W2, G
Heat Pump (One Compressor)
Y1, G, O
Y1, G, O
Y1, G, O
Y1, G, B
Y1, W2, G, B
Heat Pump (Two Compressors)
Y1, G, O
Y1, Y2, G, O
Y1, Y2, Y3, G, O
Y1, G, B
Y1, Y2, G, B