Installation
EDUS30-900-N
42
Installation of Outdoor Units
9-4 Connecting the refrigerant piping
Connect piping to outside unit by using accessory pipes
(Refer to figure 20)
1.
Gas side piping
2.
(field supply)
3.
Gas side accessory pipe (for suction gas (1))
4.
Liquid side pipe (field supply)
5.
Flare nut (Included in the unit)
6.
Accessory pipes (for discharge gas and suction gas (2))
is not used.
7.
Piping on discharge gas side (field supply)
8.
Piping on suction gas side (field supply)
9.
Cut off the hatched area and use it as a cover for the
drilled.
10.
Hatched area
11.
Accessory pipe (for discharge gas)
12.
Accessory pipe (for suction gas)
13.
Guideline for pipe machining
14.
Accessory pipe (for suction gas (2))
15.
Brazing
16.
Accessory pipe (for suction gas (1))
17.
Before fitting to the product, apply brazing.
NOTE
•
Be sure to use the attached pipe when carrying out piping work
in the field.
•
Be sure that the local piping does not touch other pipes, the bottom
panel or side panel. Especially for the bottom and side connection,
be sure to protect the local piping with the provided insulation, to
prevent it from coming into contact with the casing.
Precautions for installation of units
NOTE
•
The outside unit multi connection piping kit that is sold separately
as an option (BHFP2 84U, BHFP2 84U) is
necessary for the multi installation of outside units.
• See the installation manual attached to the kit with attention to
installation restrictions described in “connecting the refrigerant
piping” when installing.
Cautions for installation of multiple outdoor units
1.
The piping between the outdoor units must be routed level or
slightly upward to avoid the risk of oil detention to the piping side.
2.
The gas piping (both discharge and suction gas pipings in case of
the heat recovery system) after branched, install without fail a trap
of 8 in. or more using the piping included in the piping kit for con-
necting the outside unit. Otherwise, the refrigerant may stay within
the piping, causing any damage to the outside unit.
3.
If the piping length between the outside unit connecting pipe kit or
between the outside units exceeds 80 in., create a rise of 8 in. or
more in the gas line within a length of 80 in. from the kit.
Pattern 1
Pattern 2
Prohibited pattern
to indoor
unit
to indoor
unit
to indoor
unit
Downward
inclination
Downward
inclination
Change to pattern 1 or pattern 2
Oil remains in piping
Piping between outside units
8 in. or more
No trap has been installed in the gas piping.
★
Oil may remain in the farthest outside unit.
Change to pattern 1 or pattern 2
to indoor unit
Prohibited pattern
to indoor
unit
to indoor
unit
If 80 in. or less
If 80 in. or more
80 in. or less
80 in. or less
Rising height:
8 in. or more
Piping between outside unit
Summary of Contents for 80PTJU
Page 1: ...EDUS 30 900 N AMERICAS AMERICAS Installation ...
Page 17: ...REFNET Pipe System EDUS30 900 N 16 Installation of Outdoor Units 3P161697D ...
Page 21: ...REFNET Pipe System EDUS30 900 N 20 Installation of Outdoor Units C 3P113151C 7 8 1 1 1 8 ...
Page 23: ...REFNET Pipe System EDUS30 900 N 22 Installation of Outdoor Units C 3P113623C 7 8 1 1 1 8 ...
Page 25: ...REFNET Pipe System EDUS30 900 N 24 Installation of Outdoor Units 3P185500 ...
Page 27: ...REFNET Pipe System EDUS30 900 N 26 Installation of Outdoor Units 1P185542 ...