8

Pump down operation

In order to protect the environment, be sure to pump down when
relocating or disposing of the unit.

1

Remove the valve lid from liquid stop valve and gas stop valve.

2

Carry out forced cooling operation.

3

After 5 to 10 minutes, close the liquid stop valve with a
hexagonal wrench.

4

After 2-3 minutes, close the gas stop valve and stop forced
cooling operation.

Forced operation

1

Turn the operation mode switch SW2 to "COOL".

2

Press the forced operation switch SW1 to begin forced cooling.
(See 

figure 5

)

Wiring

Equipment complying with EN/IEC 61000-3-12

(1)

Do not turn ON the safety breaker until all work is completed.

1

Strip the insulation from the wire (20 mm).

2

See caution 2.
Connect the connection wires between the indoor and outdoor
units so that the terminal numbers match. Tighten the terminal
screws securely. We recommend a flathead screwdriver to
tighten the screws. 

(See figure 4)

1

Gas stop valve

2

Close

3

Hexagonal wrench

4

Valve lid

5

Liquid stop valve

1

Service PCB

2

Operation mode switch SW2

3

Forced operation switch SW1

NOTE

Forced operation automatically stops
approximately 15 minutes after starting.

To continue forced operation after elapse of the 15
minutes, press the forced operation switch SW1
again.

To stop forced operation immediately, press the
forced operation switch SW1.

1

3

2

4

4

5

All wiring must be performed by an authorized electrician.

WARNING

Do not use tapped wires, stranded conductor wires
(see caution 1), extension cords or connections from
a star system, as they may cause overheating,
electrical shock or fire.

Do not use locally purchased electrical parts inside
the product and do not branch the power for the drain
pump, etc., from the terminal block. Doing this may
cause electrical shock or fire.

Be sure to install an earth leakage breaker. This unit
uses an inverter, which means that an earth leakage
breaker capable of handling high harmonics needs to
be used in order to prevent malfunctioning of the earth
leakage breaker itself.

Use an all-pole disconnection type breaker with a
contact separation of at least 3 mm in between all poles.

(1) European/International Technical Standard setting the limits for harmonic 

currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

1

Safety breaker

2

Earth leakage circuit breaker

3

Power supply
Be sure to use a dedicated power supply circuit.

NOTE

If the length of a connection wire is:

10 m, use 2.5 mm

2

 wires

<10 m, use 1.5 mm

2

 wires.

Make sure that wiring connections of each
individual indoor unit (room A, B, ...) match
the corresponding piping connections on the
outdoor unit refrigeration ports (A, B, ...).

CAUTION
1.

In case the use of stranded conductor wires is
unavoidable for one reason or another, make sure
to install round crimp-style terminals on the tip.
Place the round crimp-style terminal on the wire up
to the covered part and fasten the terminal with the
appropriate tool.

2.

When connecting the connection wires to the
terminal board using a single core wire, be sure to
perform curling.

Not executing the connections properly may
cause heat and fire.

1

Stranded conductor wire

2

Round crimp-style terminal

Summary of Contents for 4MXS80E3V3B2

Page 1: ...INSTALLATION MANUAL 4MXS80E3V3B2 5MXS90E3V3B2 R410A Split series ...

Page 2: ...Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enlig...

Page 3: ...8 6 15 m 2 15 m 2 7 5 m 1 7 5 m 1 1 2 3 A 1 2 3 4 5 L N 5 50 Hz 230 V A B 3 C D E 1 E D C B A 2 S102 S2 S52 A BC D E ON SERVICE MONITOR S15 S10 S23 S24 S22 S21 S20 A A H05RN A B C D E 3 1 4 4 P 2 5 A A A A A B B B B B B B B 1 2 3 4 5 6 7 ...

Page 4: ...r leakage electrical shock or fire Install the air conditioner on a solid base that can support the weight of the unit An inadequate base or incomplete installation may cause injury in the event the unit falls off the base Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete...

Page 5: ... air temperature remains below or around the freezing point for a few days the outdoor unit s drain may freeze If so it is recommended to install an electric heater in order to protect drain from freezing Tighten the flare nut according to the specified method such as with a torque wrench If the flare nut is tightened too hard the flare nut may crack after a long time and cause refrigerant leakage...

Page 6: ...nstall the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind install a baffle plate on the air discharge side of the outdoor unit In heavy snowfall areas select an installation site where the snow will not affect the unit Construct a large canopy Construct a pedestal Install...

Page 7: ...gth per room is 3 m If the outdoor unit is positioned higher than the indoor units See figure 2 If the outdoor unit is positioned otherwise i e lower than one or more indoor units See figure 3 Refrigerant piping work Installing the outdoor unit When installing the outdoor unit refer to Precautions for selecting the location on page 2 and Indoor outdoor unit installation drawings on page 3 If drain...

Page 8: ...oupling meter needle does not go back If it does go back this may indicate presence of moisture or leaking from connecting parts Repeat steps 2 4 after checking all connecting parts and slightly loosening and retightening the nuts 5 Remove covers from liquid stop valve and gas stop valve 6 Turn the liquid stop valve s rod 90 degrees counterclockwise with a hexagonal wrench to open the valve Close ...

Page 9: ...ipe bends should be as gentle as possible Use a pipe bender for bending Bending radius should be 30 to 40 mm or larger Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following Insulation material polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C ma...

Page 10: ...are tool Clutch type Clutch type Ridgid Wing nut type Imperial A 0 0 5 mm 1 0 1 5 mm 1 5 2 0 mm 1 Flare s inner surface must be flaw free 2 The pipe end must be evenly flared in a perfect circle 3 Make sure that the flare nut is fitted WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which...

Page 11: ...rds or connections from a star system as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product and do not branch the power for the drain pump etc from the terminal block Doing this may cause electrical shock or fire Be sure to install an earth leakage breaker This unit uses an inverter which means that an earth leakage breaker capable ...

Page 12: ...f the indoor unit which is set for priority room is operating at Powerful operation distribution of capacity to other indoor units will be reduced This means that the room of which the indoor unit is set for priority room will be cooled or heated much quicker than other rooms Indoor or outdoor unit quiet operation priority Pressing the Quiet operation button on the remote controller of the indoor ...

Page 13: ...cannot be directly checked Wiring error check This product is capable of automatic correction of wiring errors Press the wiring error check switch SW3 on the outdoor unit service PCB Approximately 15 20 minutes after the switch is pressed the errors in the connection wiring will be corrected However the wiring error check switch will not function the first 3 minutes after the safety breaker was tu...

Page 14: ...p For 4 rooms LED 5 does not light up 2 If the outside air temperature is 5 C the wiring error check function will not operate 3 After wiring error check operation is completed LED indication will continue until ordinary operation starts This is normal 4 Follow procedures as mentioned on the service sticker on the rear side of the service cover Cooling Heating Temperature difference between inlet ...

Page 15: ......

Page 16: ...3P401524 4 2015 02 Copyright 2015 Daikin ...

Reviews: