![background image](http://html.mh-extra.com/html/daikin/4mxl-t-series/4mxl-t-series_service-manual_501130271.webp)
SiUS121827E
Field Settings
Part 7 Trial Operation and Field Settings
265
Note(s)
5.2.2 Overview of Field Settings for FFQ Series
Factory Setting
Any function that is not available on the indoor unit us not displayed.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
05
06
10
(20)
0
Filter cleaning
sign interval
Longlife filter
Li
g
ht
Approx.
2,500 hrs.
He
avy
Approx.
1,250 hrs.
—
—
—
—
2
Remote controller thermistor
Enabled
Disabled
—
—
—
—
3
Filter cleaning sign
Display
No display
—
—
—
—
12
(22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Compressor
—
Operation
output
Error
output
Outdoor
air
intake
Presence
sensor
13
(23)
0
High air outlet velocity (for
high ceiling applications)
≤ 2.7 m
(≤ 8-7/8 ft)
2.7 ~ 3.0 m
(8-7/8~9-13/16 ft)
3.0 ~ 3.5 m
(9-13/16~11-1/2 ft)
—
—
—
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow
3-way flow
2-way flow
—
—
—
4
Airflow direction range setting
Upper
Normal
Lower
—
—
—
15
(25)
3
Drain pump operation with
humidifying
Not equipped
Equipped
—
—
—
—