background image

1

n

English

Safety Precautions

• The precautions described herein are classified as WARNING and CAUTION. They both contain important informa-

tion regarding safety. Be sure to observe all precautions without fail.

• Meaning of WARNING and CAUTION notices

WARNING..............Failure to follow these instructions properly may result in personal injury or loss of life.

CAUTION...............Failure to observe these instructions properly may result in property damage or personal injury, 

which may be serious depending on the circumstances.

• The safety marks shown in this manual have the following meanings:

After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate 
the air conditioner and take care of it with the aid of the operation manual.

Be sure to follow the instructions.

Be sure to establish an earth connection.

Never attempt.

WARNING

• Ask your dealer or qualified personnel to carry out installation work.

Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.

• Install the air conditioner in accordance with the instructions in this installation manual.

Improper installation may result in water leakage, electric shocks or fire.

• Be sure to use only the specified accessories and parts for installation work.

Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit.

A foundation of insufficient strength may result in the equipment falling and causing injury.

• Electrical work must be performed in accordance with relevant local and national regulations and with instructions 

in this installation manual. Be sure to use a dedicated power supply circuit only.

Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire.

• Use a cable of suitable length.

Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal connections or wires.

Improper connections or securing of wires may result in abnormal heat build-up or fire.

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires 

so that the control box lid can be securely fastened.

Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals.

• If refrigerant gas leaks during installation, ventilate the area immediately.

Toxic gas may be produced if the refrigerant comes into contact with fire.

• After completing installation, check for refrigerant gas leakage.

Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, and 

use only the specified refrigerant (R410A).

The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage and even injury.

• During installation, attach the refrigerant piping securely before running the compressor.

If the refrigerant pipes are not attached and the stop valve is open when the compressor is run, air will be sucked in, causing abnormal 
pressure in the refrigeration cycle, which may result in equipment damage and even injury.

• During pump-down, stop the compressor before removing the refrigerant piping.

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, 
causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in electric shocks or fire.

CAUTION

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage. 

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and 

insulate piping to prevent condensation.

Improper drain piping may result in indoor water leakage and property damage.

• Tighten the flare nut according to the specified method such as with a torque wrench.

If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.

• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

• The temperature of refrigerant circuit will be high, please keep the inter-unit wire away from copper pipes that are not thermally insulated.
• Sound pressure level is less than 70dB(A).

Summary of Contents for 3MXS68G3V1B2

Page 1: ...INSTALLATION MANUAL R410A Split Series Models 3MXS68G3V1B2 4MXS68F3V1B2 ...

Page 2: ...Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enlig...

Page 3: ......

Page 4: ...ting terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leakage Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker When installing or r...

Page 5: ...other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient tem perature be sure to follow the instructions des...

Page 6: ... in the insulation pipe s cut line Wrap the insulation pipe with the finishing tape from bottom to top 250mm from wall Allow space for piping and electrical servicing If there is the danger of the unit falling or overturning fix the unit with foundation bolts or with wire or other means If the location does not have good drainage place the unit on a level mounting base or a plastic pedestal Instal...

Page 7: ...ons on Installation Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolt...

Page 8: ...piping is as short as possible Shortest allow able length per room is 3m Outdoor unit capacity class 4MXS68 3MXS68 Piping to each indoor unit 25m max 25m max Total length of piping between all units 60m max 50m max If the outdoor unit is positioned higher than the indoor units If the outdoor unit is positioned otherwise If lower than one or more indoor units Wall facing one side Side view More tha...

Page 9: ...ation oil for R410A Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Drain water hole Bottom frame Drain plug While pressing Hose available commercially inner dia 16mm Flare nut tightening torque Flare nut for φ6 4 1...

Page 10: ... Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1MPa 76cmHg Evacuation for at least 1 hour is recommended 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Leave as is for 4 5 minutes and make sure the coupling meter needle does not go back If it does g...

Page 11: ...o not leave the flare nut removed for a long period of time Outdoor capacity class 4MXS68 3MXS68 Total length of piping for all rooms 30m Filling a cylinder with an attached siphon Stand the cylinder upright when filling There is a siphon pipe inside so the cylinder need not be upside down to fill with liquid Filling other cylinders Turn the cylinder upside down when filling 3 5 6 2 1 4 Please fil...

Page 12: ...tem as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never install a dryer to this R410A unit in order to guarantee its lifetime The drying material may dissolve and damage the system Incomplete flaring may cause refrigerant gas leakage Gas pipe O D 9 5mm 12 7mm Thickness 0 8mm C1220T O O...

Page 13: ...d connection port of the outdoor unit where the flare nut comes in Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut Flare nut tightening torque Flare nut for φ9 5 32 7 39 9N m 333 407kgf cm Flare nut for φ12 7 49 5 60 3N m 505 615kgf cm Flare nut for φ15 9 61 8 75 4N m 630 769kgf cm No 1 φ15 9 φ12 7 No 2 φ12 7 φ9 5 No 3 φ15 9 φ12 7 No 4 φ12 7 φ9 5 N...

Page 14: ... the liquid stop valve with a hexagonal wrench 4 After two to three minutes close the gas stop valve and stop forced cooling operation 1 Forced operation 1 Turn the Operation Mode switch SW2 to COOL 2 Press the Forced Operation switch SW1 to begin forced cooling Press the Forced Operation switch SW1 again to stop forced cooling Gas stop valve Close Hexagonal wrench Liquid stop valve Valve caps Ser...

Page 15: ...ioner must be earthed For earthing follow the applicable local standard for electrical installations Safety breaker Earth leakage circuit breaker Outdoor unit 50Hz 220 240V Be sure to use the dedicated circuits To room B To room C To room D Room A Room A Room C Room D Room B Indoor unit Power supply wire 3 core 2 5mm or more H05RN Inter unit wire 4 core 1 5mm or more H05RN L N Shape the wires so t...

Page 16: ...operating all other indoor units do not operate and enter standby mode according to the operation mode of the set indoor unit 1 2 Priority during high power operation If the indoor unit which is set for priority room setting is operating at high power the capabilities of other indoor units will be somewhat reduced Power supply gives priority to the indoor unit which is set for priority room settin...

Page 17: ...saved Setting procedure Remove the SW5 jumper switch Once the settings are complete reset the power NOTE Install the removed jumper switch as described below This switch will be needed to later disable this setting COOL HEAT Mode Lock S15 Use the S15 connector to set the unit to only cool or heat Setting to only heat H short circuit pins 1 and 3 of the connector S15 Setting to only cool C short ci...

Page 18: ...ing in the usual manner NOTE 1 For three rooms LED 4 is not displayed 2 If the outside air temperature is 5 C or less the wiring error check function will not operate 3 After wiring error check operation is completed LED indication will continue until ordinary operation starts This is normal 4 Follow the product diagnosis procedures Check the nameplate on the underside of the stop valve Wiring err...

Page 19: ...ures and temperature adjustment Even when the air conditioner is not operating it consumes some electric power If the customer is not going to use the unit soon after it is installed turn off the breaker to avoid wasting electricity If additional refrigerant has been charged because of long piping list the amount added on the nameplate on the reverse side of the stop valve cover Cooling Heating Te...

Page 20: ...3P401524 3 2015 02 Copyright 2015 Daikin ...

Reviews: