Refrigerant Piping Work

6.

Refrigerant piping work

Cautions on pipe handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for 

bending. 

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)

Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimen-

sions as below.  

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
4) Piping and other pressure containing parts shall comply with the applicable legislation and shall be suitable for refrigerant. 

Use phosphoric acid deoxidised seamless copper for refrigerant.

7.

Flaring the pipe end

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing down-

ward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a dryer to this R32 unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

Gas pipe

O.D.: 9.5mm, 12.7mm / Thickness: 0.8mm (C1220T-O)
O.D.: 15.9mm / Thickness: 1.0mm (C1220T-O)

Liquid pipe

O.D.: 6.4mm / Thickness: 0.8mm (C1220T-O)

Gas pipe insulation

I.D.: 12-15mm, I.D.: 16-20mm / Thickness: 13mm min.

Liquid pipe insulation

I.D.: 8-10mm / Thickness: 10mm min.

Minimum bend radius

O.D.: 6.4mm, 9.5mm / 30mm or more
O.D.: 12.7mm / 40mm or more
O.D.: 15.9mm / 50mm or more

Wall

If no flare cap is 
available, cover 
the flare mouth 
with tape to keep 
dirt or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wires

(Cut exactly at 

right angles.)

 Remove burrs

Set exactly at the position shown below.

A

Flaring

Die

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

A

0-0.5mm

Clutch-type

Flare tool for R32

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

3PEN417620-1D.book  Page 10  Thursday, February 4, 2016  8:24 AM

Summary of Contents for 3MXM52M2V1B

Page 1: ...plit Series Models 3MXM40M2V1B 3MXM52M2V1B 3AMXM52M2V1B 3MXM68M2V1B 4MXM68M2V1B 4MXM80M2V1B 5MXM90M2V1B Deutsch Fran ais Nederlands Espa ol Italiano Portugues T rk e 3PEN417620 1D book Page 1 Thursday...

Page 2: ......

Page 3: ...v E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekn...

Page 4: ...emperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS...

Page 5: ...stsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske K...

Page 6: ...emperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS...

Page 7: ...tions or wires Improper connections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units positi...

Page 8: ...trical parts can cause malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wir...

Page 9: ...ore than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since water will flo...

Page 10: ...ion bolts or with wire or other means If the location does not have good drainage place the unit on a level mounting base or a plastic pedestal Install the outdoor unit in a level position Failure to...

Page 11: ...nit will not cause any operating vibration or noise after installed In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foun...

Page 12: ...t capacity class 3MXM40M 3MXM52M 3AMXM52M 3MXM68M 4MXM68M 4MXM80M 5MXM90M Piping to each indoor unit 25m max 25m max 25m max 25m max 25m max 25m max Total length of piping between all units 50m max 50...

Page 13: ...mply with the applicable legislation In Europe the EN378 is the applicable standard that shall be used Ensure that the field piping and connections are not subjected to stress Align the centres of bot...

Page 14: ...with a torque wrench to the specified tightening torque 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pr...

Page 15: ...6 2 1 4 Please fill in with indelible ink 1 the factory refrigerant charge of the product 2 the additional refrigerant amount charged in the field and 1 2 the total refrigerant charge on the refriger...

Page 16: ...al oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts whi...

Page 17: ...outdoor unit where the flare nut comes in Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut Flare nut tightening torque Flare nut for 9 5 32 7 39 9N m 3...

Page 18: ...the service PC board switch cover 1 screw 4 Switch SW5 and SW6 to off 5 Turn the operation mode switch SW2 to COOL 6 Screw the service PC board switch cover back on 1 screw 7 Switch the power on 8 Pu...

Page 19: ...indoor and outdoor units so that the terminal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used to tighten the screws 3 Be sure to match the symbols for w...

Page 20: ...ective connector for standby electricity saving is required if an indoor unit other than the above applicable one is connected Good Round crimp style terminal Flat washer Screw Wrong Flat washer Round...

Page 21: ...the operation mode of the set indoor unit 1 2 Priority during high power operation If the indoor unit which is set for priority room setting is operating at high power the capabilities of other indoor...

Page 22: ...running cooling capacity will be saved Setting procedure Turn the Night Quiet Mode switch SW6 1 to on HEAT Mode Lock SW5 1 Use the HEAT Mode Lock switch SW5 1 in the ON position COOL Mode Lock S15 Us...

Page 23: ...d and for four rooms LED 5 is not displayed 2 If the outside air temperature is 5 C or less the wiring error check function will not operate 3 After wiring error check operation is completed LED indic...

Page 24: ...ly cleaning of the air filters operation procedures and temperature adjustment Even when the air conditioner is not operating it consumes some electric power If the customer is not going to use the un...

Page 25: ...able models 3MXM52M2V1B 3MXM40M2V1B 3AMXM52M2V1B S1PH S2PH High pressure switch Manual reset Automatic reset Outdoor Unit Heat exchanger thermistor Outdoor air temperature thermistor 7 9CuT 7 9CuT 7 9...

Page 26: ...uT 7 9CuT MVD 6 4CuT RoomD 6 4CuT D 12 7CuT 12 7CuT Room Outdoor Unit Heat exchanger thermistor Outdoor air temperature thermistor 15 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 12 7CuT M 12 7CuT A B C 12 7CuT 9...

Page 27: ...e 6 4CuT 6 4CuT 6 4CuT Filter Room Room Room Field piping Liquid Gas A B C 6 4CuT 6 4CuT 6 4CuT Room Room Room 9 5CuT Liquid stop valve 9 5CuT 9 5CuT Muffler with filter Capillary tube Distributor Ref...

Page 28: ...3PEN417620 1D book Page 1 Thursday February 4 2016 8 24 AM...

Page 29: ...3PEN417620 1D book Page 2 Thursday February 4 2016 8 24 AM...

Page 30: ...3PEN417620 1D book Page 3 Thursday February 4 2016 8 24 AM...

Page 31: ...3PEN417620 1D book Page 1 Thursday February 4 2016 8 24 AM...

Page 32: ...3P417620 1D 2016 01 Copyright 2015 Daikin 3PEN417620 1D book Page 2 Thursday February 4 2016 8 24 AM...

Reviews: