background image

1

English

Safety Precautions

• Read these Safety Precautions carefully to ensure correct installation.

• This manual classifies the precautions into WARNING and CAUTION.

Be sure to follow all the precautions below: they are all important for ensuring safety.

WARNING...............Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.

CAUTION...............Failure to follow any of CAUTION may in some cases result in grave consequences.

• The following safety symbols are used throughout this manual:

• After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use 

and cleaning of the unit according to the Operation Manual.

Be sure to observe this instruction.

Be sure to establish an earth connection.

Never attempt.

WARNING

• Installation should be left to the dealer or another professional.

Improper installation may cause water leakage, electrical shock, or fire.

• Install the air conditioner according to the instructions given in this manual.

Incomplete installation may cause water leakage, electrical shock, or fire.

• Be sure to use the supplied or specified installation parts.

Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.

• Install the air conditioner on a solid base that can support the unit’s weight.

An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.

• Electrical work should be carried out in accordance with the installation manual and the national electrical wiring

rules or code of practice. 

 Insufficient capacity or incomplete electrical work may cause electrical shock or fire.

• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
• For wiring, use a cable long enough to cover the entire distance with no connection. 

Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.

(Failure to do so may cause abnormal heat, electric shock or fire.)

• Use the specified types of wires for electrical connections between the indoor and outdoor units. 

Firmly clamp the inter-

connecting wires so their terminals receive no external stresses.  Incomplete connections or clamping may cause terminal overheating or fire.

• After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the 

electrical covers or panels. 

Install covers over the wires.  Incomplete cover installation may cause terminal overheating, electrical shock, or fire.

• If any refrigerant has leaked out during the installation work, ventilate the room.

(The refrigerant produces a toxic gas if exposed to flames.)

• After all installation is complete, check to make sure that no refrigerant is leaking out.

(The refrigerant produces a toxic gas if exposed to flames.)

• When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the 

specified  refrigerant (R410A), such as air.

(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)

• During pump-down, stop the compressor before removing the refrigerant piping.

If the compressor is still running and the shut-off valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, 
causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

• During installation, attach the refrigerant piping securely before running the compressor.

If the compressor is not attached and the shut-off valve is open during pump-down, air will be sucked in when the compressor is run, causing 
abnormal pressure in the freezer cycle which will lead to breakage and even injury.

• Be sure to establish an earth.  Do not earth the unit to a utility pipe, arrester, or telephone earth.

Incomplete earth may cause electrical shock, or fire.  A high surge current from lightning or other sources may cause damage to the air conditioner.

• Be sure to install an earth leakage breaker. 

Failure to install an earth leakage breaker may result in electric shocks, or fire.

CAUTION

• Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage. 

If the gas leaks and builds up around the unit, it may catch fire.

• Establish drain piping according to the instructions of this manual. 

Inadequate piping may cause flooding.

• Note for installing the outdoor unit. (For heat pump model only.)

In cold area where the outside air temperature keep below or around freezing-point for a few days, the outdoor unit’s drain may freeze. 
If so, it is recommended to install an electric heater in order to protect drain from freezing.

• Tighten the flare nut according to the specified method such as with a torque wrench.

If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.

• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around 
the unit clean.

01_EN_3P164392-2E.fm  Page 1  Wednesday, May 24, 2006  2:47 PM

Summary of Contents for 2MXS52E2V1B

Page 1: ...ссêий English Türkçe Installation manual R410A Split series Montaj kýlavuzlarý R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation Série split R410A Montagehandleiding R410A Split systeem Manual de instalación Serie Split R410A Manuale d installazione Serie Multiambienti R410A Εγχειρßδιο εγκατÜστασηò διαιροýìενηò σειρÜò R410A Manual de Instalação Série split R410A ...

Page 2: ... KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ...

Page 3: ... cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames After all installation is complete check to make sure that no refrigerant is leaking out The refrigerant produces a toxic gas if exposed to flames When installing or relocating the system be sure to keep the...

Page 4: ... depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor a...

Page 5: ...ng sure that no gap is left in the insulation pipe s cut line Wrap the insulation pipe with the finishing tape from bottom to top Caulk pipe hole gap with putty Foot bolt hole centres 58cm Foot bolt hole centres 33cm 25cm from wall Allow space for piping and electrical servicing Allow 30cm of work space below the ceiling surface If there is the danger of the unit falling or overturning fix the uni...

Page 6: ...autions on Installation Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts Prepare four sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundati...

Page 7: ...t as possible Shortest allow able length per room is 3m Outdoor unit capacity class 2MXS52 2AMX52 3MXS52 3AMX52 3MKS50 4MKS58 Piping to each indoor unit 25m max Total length of piping between all units 50m max If the outdoor unit is positioned higher than the indoor units If the outdoor unit is positioned otherwise If lower than one or more indoor units More than 100 More than 350 Side view 1200 o...

Page 8: ...urns by hand Then tighten them fully with the torque wrenches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare Use refrigeration oil for R410A Drain water hole Bottom frame Drain plug While pressing Hose available commercially inner dia 16mm ...

Page 9: ...sure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1MPa 76cmHg Evacuation for at least 1 hour is recommended 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Leave as is for 4 5 minutes and make sure the coupling meter needle does not go back If...

Page 10: ... a pipe bender for bending Bending radius should be 30 to 40mm or larger Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will w...

Page 11: ...s been used for previous installations Only use parts which are delivered with the unit 4 Do never install a drier to this R410A unit in order to guarantee its lifetime 5 The drying material may dissolve and damage the system 6 Incomplete flaring may cause refrigerant gas leakage Cut exactly at right angles Remove burrs Set exactly at the position shown below A Flaring Die Check Flare s inner surf...

Page 12: ...d connection port of the outdoor unit where the flare nut comes in Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut Flare nut tightening torque Flare nut for φ9 5 32 7 39 9N m 333 407kgf cm Flare nut for φ12 7 49 5 60 3N m 505 615kgf cm Flare nut for φ15 9 61 8 75 4N m 630 769kgf cm No 1 φ15 9 φ12 7 No 2 φ12 7 φ9 5 No 3 φ15 9 φ12 7 No 4 φ12 7 φ9 5 N...

Page 13: ...shut off valve with a hexagonal wrench 4 After two to three minutes close the gas shut off valve and stop forced cooling operation 1 Forced operation 1 Turn the Operation Mode switch SW2 to COOL Heat pump only 2 Press the Forced Operation switch SW1 to begin forced cooling Press the Forced Operation switch SW1 again to stop forced cooling Gas shut off valve Close Hexagonal wrench Liquid shut off v...

Page 14: ...ews The screws are packed with the terminal board 3 Pull the wire and make sure that it does not disconnect Then fix the wire in place with a wire stop Earth This air conditioner must be earthed For earthing follow the applicable local standard for electrical installations Safety breaker Earth leakage circuit breaker Outdoor unit 50Hz 220 240V Be sure to use the dedicated circuits To room B To roo...

Page 15: ...perating all other indoor units do not operate and enter standby mode according to the operation mode of the set indoor unit 1 2 Priority during high power operation If the indoor unit which is set for priority room setting is operating at high power the capabilities of other indoor units will be somewhat reduced Power supply gives priority to the indoor unit which is set for priority room setting...

Page 16: ... procedure Remove the SW5 jumper switch Once the settings are complete reset the power NOTE Install the removed jumper switch as described below This switch will be needed to later disable this setting COOL HEAT Mode Lock S15 Heat Pump Units Only Use the S15 connector to set the unit to only cool or heat Setting to only heat H short circuit pins 1 and 3 of the connector S15 Setting to only cool C ...

Page 17: ...TE 1 For two rooms LED 3 and 4 are not displayed and for three rooms LED 4 is not displayed 2 If the outside air temperature is 5 C or less the wiring error check function will not operate 3 After wiring error check operation is completed LED indication will continue until ordinary operation starts This is normal 4 Follow the product diagnosis procedures Check the nameplate on the underside of the...

Page 18: ... procedures and temperature adjustment 2 Even when the air conditioner is not operating it consumes some electric power If the customer is not going to use the unit soon after it is installed turn OFF the breaker to avoid wasting electricity 3 If additional refrigerant has been charged because of long piping list the amount added on the nameplate on the reverse side of the shut off valve cover Coo...

Page 19: ... 0606 HT 3P164392 2E M05B110A ...

Reviews: