background image

9

English

Outdoor Unit Installation

4. 

Refrigerant piping

CAUTION

•  Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)
•  To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
•  Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

•  Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a 

torque wrench.

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration 
oil only to the inner 

surface of the flare.

Do not apply refrigeration oil to 

the flare nut to avoid tightening 
with excessive torque.

Apply oil

T

orque wrench

Piping union

Flare nut

Spanner

Tighten

 

Tightening torque

Flare nut

Piping connection

3/8 inch (9.5mm)

24-1/8 –

29-1/2lbf • ft

(32.7-39.9N • m)

36-1/2–

44-1/2lbf • ft

(49.5-60.3N • m)

Gas side

1/2 inch (12.7mm)

45-5/8–

55-5/8lbf • ft

(61.8-75.4N • m)

5/8 inch (15.9mm)

10-1/2 –

12-3/4lbf • ft

(14.2-17.2N • m)

Liquid side

1/4 inch (6.4mm)

Width across flats

Valve cap

3/4 inch (19mm)

12-5/8 –

15-3/8lbf • ft

(17.0-20.9N • m)

16–

20-1/4lbf • ft

(21.6-27.4N • m)

8 –

10-7/8lbf • ft

(10.7-14.7N • m)

7/8 inch (22mm)

Service port cap

Cautions on pipe handling

• 

Protect the open end of the pipe from dust and moisture.

• 

All pipe bends should be as gentle as possible. Use a pipe bender for bending.

Wall

If no flare cap is 

available, cover 

the flare mouth 

with tape to keep 

dirt and water out.

Be sure to 

place a cap.

Rain

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:

• 

Insulation material:  Polyethylene foam
Heat transfer rate:  0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F)  
(0.035 to 0.045kcal/mh°C)
Be sure to use insulation that is designed for use with HVAC Systems.

• 

ACR Copper only.

• 

Be sure to insulate both the gas and liquid piping and observe the insulation 
dimensions as below.

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Gas side

Piping size

O.D. 3/8 inch

(9.5mm)

O.D. 1/2 inch

(12.7mm)

O.D. 5/8 inch

(15.9mm)

O.D. 1/4 inch

(6.4mm)

1-3/16 inch (30mm)

or more

1-9/16 inch (40mm)

or more

1-15/16 inch (50mm)

or more

1-3/16 inch (30mm)

or more

0.031 inch (0.8mm)

(C1220T-O)

0.039 inch (1.0mm)

(C1220T-O)

0.031 inch (0.8mm)

(C1220T-O)

I.D. 15/32-19/32 inch

(12-15mm)

I.D. 9/16-5/8 inch

(14-16mm)

I.D. 5/8-13/16 inch

(16-20mm)

I.D. 5/16-13/32 inch

(8-10mm)

13/32 inch

(10mm) Min.

Minimum bend radius

Piping thickness

Thermal insulation size Thermal insulation

thickness

Liquid side

• 

Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

•  Using finishing tape, bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below 

the other piping.

01_EN_3P675080-1.indd   9

3/24/2022   16:01:44

Summary of Contents for 2MXS18WMVJU9

Page 1: ...LATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n MODELS 2MXS18WMVJU9 3MXS24WMVJU9 4MXS36WMVJU9 2MXL18WMVJU9 3MXL24WMVJU9 2MXLH18WVJU9 3MXLH24WVJU9 Manuel...

Page 2: ...Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Additionally grounding to ga...

Page 3: ...or moisture should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultra...

Page 4: ...ill flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6 5 8ft 2m from...

Page 5: ...bottom to top 9 13 16 250 from wall Allow space for piping and electrical servicing Level mounting base available separately If there is a danger of the unit falling or overturning x the unit with fo...

Page 6: ...to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Selecting a Location for Installation of the Indoor Units The maximum allowa...

Page 7: ...e is determined by the size of the indoor unit fittings Reducers are used at the outdoor unit to accommodate the correct gas line pipe size 3MXS 3MXL 4MXS Port 2MXS 2MXL B 07 09 12 15 18 07 09 12 15 0...

Page 8: ...he gasket 2 Connecting a pipe of 3 8 inch 9 5mm to a gas pipe connection port for 1 2 inch 12 7mm Connection port of outdoor unit No 4 No 2 Flare nut for 1 2 inch 12 7mm Be sure to attach the gasket F...

Page 9: ...which are delivered with this unit Never install a dryer to this R410A unit in order to guarantee its service life The drying material may dissolve and damage the system Improper flaring may result i...

Page 10: ...he pipe from dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no are cap is available cover the are mouth with tape to keep dirt and water out Be...

Page 11: ...MPa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hoses to the service po...

Page 12: ...be upside down to ll with liquid Filling other cylinders Turn the cylinder upside down when lling Be sure to use the R410A tools to ensure pressure and to prevent foreign objects from entering 7 Char...

Page 13: ...ake care not to pull at the conduit Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire Do not turn on the circuit breaker until all work is completed CAUTION Pr...

Page 14: ...not disconnect 5 Pass the wiring through the cutout on the bottom of the protection plate and attach the protection plate 6 After completing the work reattach the service lid to its original position...

Page 15: ...mode of the set indoor unit 2 Priority during powerful operation If the indoor unit which is set for priority room setting is operating at powerful the capabilities of other indoor units will be some...

Page 16: ...ing in night quiet mode Setting procedure Turn the night quiet mode switch SW6 1 to on COOL HEAT mode lock S15 Use the S15 connector to set the unit to only cool or heat Setting to only heat H short c...

Page 17: ...ling operation 5 Attach the valve caps once procedures are complete Gas stop valve Close Hexagonal wrench Liquid stop valve Valve caps Forced cooling operation WARNING Do not remove the switch cover u...

Page 18: ...rrection is possible as shown in the table below For details on how to read the LED display refer to the collective indications label on the reverse side of the top plate or the service manual If self...

Page 19: ...Temperature difference between inlet and outlet About 14 F 8 C About 36 F 20 C When running in one room 2 5 After trial operation is complete set the temperature to a normal level 78 F to 82 F 26 C to...

Page 20: ...Two dimensional bar code is a manufacturing code 3P675080 1 M21B361 2203 HT 00_CV_3P675080 1 indd 2 2022 03 01 11 25 45...

Reviews: