background image

16

English

Trial Operation and Testing

• Before starting the test run, measure the voltage at the primary side of the safety breaker. 
• Check that all liquid and gas stop valves are fully open.
• Check that piping and wiring all match. 

1.

Trial operation and testing

1) To test cooling, set for the lowest temperature. To test heating, set for the highest temperature. (Depending on the room 

temperature, only heating or cooling (but not both) may be possible.)

2) After the unit is stopped, it will not start again (heating or cooling) for approximately 3 minutes.
3) During the test run, first check the operation of each unit individually. Then also check the simultaneous operation of 

all indoor units.
Check both heating and cooling operation.

4) After running the unit for approximately 20 minutes, measure the temperatures at the indoor unit inlet and outlet. If the 

measurements are above the values shown in the table below, then they are normal.

(When running in one room)

5) During cooling operation, frost may form on the gas stop valve or other parts. This is normal.
6) Operate the indoor units in accordance with the included operation manual. Check that they operate normally.

2.

Items to check 

ATTENTION

• Have the customer actually operate the unit while looking at the manual included with the indoor unit. Instruct the customer 

how to operate the unit correctly (particularly cleaning of the air filters, operation procedures, and temperature adjustment).

• Even when the air conditioner is not operating, it consumes some electric power. If the customer is not going to use the unit 

soon after it is installed, turn off the breaker to avoid wasting electricity.

• If additional refrigerant has been charged because of long piping, list the amount added on the nameplate on the reverse side 

of the stop valve cover.

Cooling

Heating

Temperature difference 
between inlet and outlet

Approx. 8

°

C

Approx. 15

°

C

Check item

Consequences of trouble

Check

Are the indoor units installed securely?

Falling, vibration, noise

Has an inspection been made to check for gas leakage?

No cooling, no heating

Has complete thermal insulation been done (gas pipes, liquid 
pipes, indoor portions of the drain hose extension)?

Water leakage

Is the drainage secure?

Water leakage

Are the ground wire connections secure?

Danger in the event of a ground fault

Are the electric wires connected correctly?

No cooling, no heating

Is the wiring in accordance with the specifications?

Operation failure, burning

Are the inlets/outlets of the indoor and outdoor units free of any 
obstructions?

No cooling, no heating

Are the stop valves open?

No cooling, no heating

Do the marks match (room A, room B) on the wiring and piping 
for each indoor unit?

No cooling, no heating

Summary of Contents for 2MXM50M2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models 2MXM40M2V1B 2MXM50M2V1B 2AMXM40M2V1B 2AMXM50M2V1B Deutsch Fran ais Nederlands Espa ol Italiano Portugues T rk e...

Page 2: ...blece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A...

Page 3: ...ionsfilen D som positivt intygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifi...

Page 4: ...survele PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22...

Page 5: ...es may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be secure...

Page 6: ...malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wire away from copper pip...

Page 7: ...y be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air condi...

Page 8: ...prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is installed above Cut thermal insulation pipe to an appropriate length and wrap it...

Page 9: ...ion bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation...

Page 10: ...ormance Connect so that the piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor...

Page 11: ...joints which have been used once already Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislation In Europe the EN378 is the ap...

Page 12: ...high pressure valve Hi 3 Apply vacuum pumping for 20 minutes or longer Check that the compound pressure gauge reads 0 1MPa 76cmHg 4 After checking the vacuum close the low pressure and high pressure v...

Page 13: ...ill break the compressor 3 5 6 2 1 4 R32 Please fill in with indelible ink 1 the factory refrigerant charge of the product 2 the additional refrigerant amount charged in the field and 1 2 the total re...

Page 14: ...pe 4 Flare the pipe 5 Check that the flaring is properly made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the un...

Page 15: ...inuously The units in both rooms will start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the...

Page 16: ...the stranded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered p...

Page 17: ...RMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS S NPL P...

Page 18: ...1 Remove the two screws on the side and remove the top plate of the outdoor unit 2 Remove the electric box cover by sliding it being careful not to bend the electric box hook 3 Cut the jumper J23 of...

Page 19: ...unction turns off power supply to the outdoor unit and sets the indoor unit into standby electricity saving mode thus reducing the power consumption of the air conditioner The standby electricity savi...

Page 20: ...the manual included with the indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the...

Page 21: ...eller fan ON heating Muffler 9 5CuT 9 5CuT 9 5CuT Branch pipe Muffler Gas stop valve Muffler Gas stop valve 9 5CuT 9 5CuT Thermistor gas Thermistor liquid Thermistor gas 6 4CuT 6 4CuT EV A EV B Motor...

Page 22: ......

Page 23: ......

Page 24: ...3P423316 1C 2015 12 Copyright 2015 Daikin...

Reviews: