12

English

Wiring

WARNING

• Do not use tapped wires, stranded wires (

CAUTION 

1), extension cords, or starburst connections, as they may cause over-

heating, electrical shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the ter-

minal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that an earth leakage breaker capable of handling harmonics must be used, in order 
to prevent malfunctioning of the earth leakage breaker itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Do not turn on the safety breaker until all work is completed. 

1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wires between the indoor and out-

door units 

so that the terminal numbers match

Tighten the terminal screws securely. We recommend a 
flathead screwdriver be used to tighten the screws. The 
screws are packed with the terminal block. 

 CAUTION

•When connecting the inter-unit wire to the ter-
minal block using a single core wire, be sure to 
perform curling. 
Problems with the work may cause heat and 
fires. 
•Make sure that the earth wire between the pull 
relief and terminal is longer than the other wires.

•If the stranded wires must 

be used, make sure to use the round crimp-
style terminal for connection to the power 
supply terminal block. Place the round 
crimp-style terminals on the wires up to the 
covered part and secure in place.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire retainer. 

Room A

Room A

Room B

Outdoor unit

Indoor unit

Be sure to use the dedicated circuits.

Safety breaker

Earth leakage 
circuit breaker

50Hz 
220-240V

To room B

Inter-unit wire
4-core 1.5mm² or more 
H05RN

Power supply wire
3-core 2.5mm² or more
H05RN

1

2

3

L

N

1

2

3

1-3

A

B

A<B

Stranded wire

Round crimp-style
terminal

Good

Wrong

Good

Wrong

1

2

3

L

N

1

2

3

Make sure the connecting 
piping and wiring fit 
into             .

(Incorrect handling will 
make it hard to attach the 
stop valve cover, causing 
deformation.)

ROOM-A

ROOM-B

A

B

A

B

Piping

Piping

Wiring
Wiring

Outdoor 
unit

ROOM-A

ROOM-B

Piping

Piping

Wiring
Wiring

Outdoor 
unit

Make absolutely sure all wiring is correct.

Make sure the wiring and piping from the indoor unit to the outdoor unit match.

4

4

P

Good

Wrong

Shape wires so that the stop 
valve cover fits securely.

Firmly secure wire retainer 
so wire terminations will not 
receive external stress.

 

Also use the two screws 
located at the bottom of 
the packing case to tighten 
the four locations.

Power supply

ROOM-A

ROOM-B

Use the 
specified wire 
type and 
connect it 
securely.

Be sure to clamp the wire for 
power source on this location.

ROOM-A

ROOM-B

Liquid piping

Gas piping

Liquid piping

Gas piping

Wire retainer

Refer to the figure.

Make sure the electrical 
wiring does not come into 
contact with the gas piping.

Summary of Contents for 2MXM50M2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models 2MXM40M2V1B 2MXM50M2V1B 2AMXM40M2V1B 2AMXM50M2V1B Deutsch Fran ais Nederlands Espa ol Italiano Portugues T rk e...

Page 2: ...blece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A...

Page 3: ...ionsfilen D som positivt intygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifi...

Page 4: ...survele PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22...

Page 5: ...es may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be secure...

Page 6: ...malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wire away from copper pip...

Page 7: ...y be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air condi...

Page 8: ...prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is installed above Cut thermal insulation pipe to an appropriate length and wrap it...

Page 9: ...ion bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation...

Page 10: ...ormance Connect so that the piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor...

Page 11: ...joints which have been used once already Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislation In Europe the EN378 is the ap...

Page 12: ...high pressure valve Hi 3 Apply vacuum pumping for 20 minutes or longer Check that the compound pressure gauge reads 0 1MPa 76cmHg 4 After checking the vacuum close the low pressure and high pressure v...

Page 13: ...ill break the compressor 3 5 6 2 1 4 R32 Please fill in with indelible ink 1 the factory refrigerant charge of the product 2 the additional refrigerant amount charged in the field and 1 2 the total re...

Page 14: ...pe 4 Flare the pipe 5 Check that the flaring is properly made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the un...

Page 15: ...inuously The units in both rooms will start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the...

Page 16: ...the stranded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered p...

Page 17: ...RMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS S NPL P...

Page 18: ...1 Remove the two screws on the side and remove the top plate of the outdoor unit 2 Remove the electric box cover by sliding it being careful not to bend the electric box hook 3 Cut the jumper J23 of...

Page 19: ...unction turns off power supply to the outdoor unit and sets the indoor unit into standby electricity saving mode thus reducing the power consumption of the air conditioner The standby electricity savi...

Page 20: ...the manual included with the indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the...

Page 21: ...eller fan ON heating Muffler 9 5CuT 9 5CuT 9 5CuT Branch pipe Muffler Gas stop valve Muffler Gas stop valve 9 5CuT 9 5CuT Thermistor gas Thermistor liquid Thermistor gas 6 4CuT 6 4CuT EV A EV B Motor...

Page 22: ......

Page 23: ......

Page 24: ...3P423316 1C 2015 12 Copyright 2015 Daikin...

Reviews: