Daikin McQuay IOM 1177 Installation Operation & Maintenance Data Download Page 5

IOM 1177 / Page 5 of 8

Installation

Field Wiring

Wiring between the sensor and the water source heat pump 
unit for typical heating and cooling operation is shown in 

Figure 3

.

Figure 3: Field wiring

SmartSource

 

Board

MicroTech

®

 III Board

I/O Expansion 

Module

Base Board

Terminal Block Label

TB2-1

TB1-1

TB1-2

TB1-3

TB1-4

TB1-5

TB3-1

TB3-2

TB1-1

Description

24V
AC

Unit Status Output

Fan & Unit Mode

Setpoint Adjust

Room 

Temp Sensor & 

Tenant Override

DC Signal Common

Emergency Shutdown 

Input

Unoccupied Input

Dehumidification Input

Terminal Label

R

1

2

3

4

5

E

U

1

 

Typical Wiring

Terminal Label

1

2

3

4

5

E

U

Description

Unit Status LED Input

Fan & Unit Mode

Setpoint Adjustment

Room 

Temperature 

 

Sensor & 

Tenant Override

DC Signal Common

Emergency Shutdown

Unoccupied

Adjustable Cool/Warm Room Temperature Sensor with Occupancy Switch (Part No. 910121753)

Maintenance

Wipe the display as needed with a damp water only cotton 
cloth. Do not use any type of cleaner as it may damage the 
buttons or scratch the display. Do not paint.

Terminal Descriptions

1 – Unit Status Indicator Input from the MicoTech III 

SmartSource Unit Controller. (5VDC)

2 - Output Signal, Fan and Unit Mode (0 to 5VDC)
3 - Output Signal, Setpoint Adjustment
4 - Output Signal, Room Temp Thermistor Sensor. (10K ATP 

Z curve, 10K-2)

5 - Ground or Neutral. Common Reference for All Signal 

Terminals

E – Emergency Shutdown. (Terminal grounded when in 

System “Off” mode, VDC only) 

U - Unoccupied Contact. (Terminal grounded when in 

Unoccupied, VDC only)

Summary of Contents for IOM 1177

Page 1: ...cquay com Room Temperature Sensor Adjustable Cool Warm With Occupancy Switch Sensor Part No 910121753 Used With Water Source Heat Pumps SmartSource Units with MicroTech III Controls Models GS GT Enfinity Units with MicroTech III Controls Models CCH CCW VFC VFW LVC LVW MHC MHW VHC VHF IMPORTANT Operator save these instructions for future use ...

Page 2: ...nd should be handled carefully Rough handling or distorting components could cause the control to malfunction The remote sensors cannot be used with systems where power interruptions are part of normal system operation NOTICE MERCURY NOTICE This product does not contain mercury However this product may replace a product that contains mercury Mercury and products containing mercury must not be disc...

Page 3: ...Supple mental Primary 3 Way Valve Control Water Source Heat Pumps Hori zontal Enfinity W CCH CCW 1 1 No No No No No No No No No Vertical W VFC VFW 1 1 No Yes No No No Yes1 Yes No No Vertical Stacked W VHC 1 1 No No No No No No No No No Console W MHC MHW 1 1 No No No No No Yes1 Yes No No Hori zontal Vertical Smart Source 1 Stage W GSH GSV 3 4 Yes Yes Yes Yes Yes Yes Yes Yes Yes Hori zontal Vertical...

Page 4: ...apping the bottom into position Figure 1 Junction box mounting Junction box Field provided thermostat wiring 6 32 1 2 mountings screws Drywall Mounting 1 Place the base plate against the wall where you want to mount the sensor 2 Mark out the two mounting holes where the unit will be attached to the wall Drill a 3 16 hole in the center of each mounting hole and insert a drywall anchor into the hole...

Page 5: ...t Fan Unit Mode Setpoint Adjustment Room Temperature Sensor Tenant Override DC Signal Common Emergency Shutdown Unoccupied Adjustable Cool Warm Room Temperature Sensor with Occupancy Switch Part No 910121753 Maintenance Wipe the display as needed with a damp water only cotton cloth Do not use any type of cleaner as it may damage the buttons or scratch the display Do not paint Terminal Descriptions...

Page 6: ...ycle on a call for heat or cool in the unoccupied mode Status LED This green LED will light to indicate the system status See Table 8 for unit status LED definitions Override Button When the Override button is pressed the thermistor sensor across terminal 4 is shorted If held for more than 5 seconds but less than 11 seconds it puts the water source heat pump controller into a timed Occupied Overri...

Page 7: ...IOM 1177 Page 7 of 8 This page left blank intentionally ...

Page 8: ... 2012 McQuay International 800 432 1342 www mcquay com IOM 1177 Page 8 of 8 ...

Reviews: