Daikin Altherma EHVH04SU18CB6W Installation Manual Download Page 23

7 Hand-over to the user

Installation manual

23

08SU EHVH08~16SU26CB6W
Daikin Altherma – Low temperature split
4P449980-1B – 2016.11

7

Hand-over to the user

Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:

▪ Fill in the installer setting table (in the operation manual) with the

actual settings.

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation on the url as earlier described in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do in relation to maintaining the unit.

▪ Explain  the  user  about  energy  saving  tips  as  described  in  the

operation manual.

8

Maintenance and service

NOTICE

Maintenance  must  be  done  by  an  authorised  installer  or
service agent.

We  recommend  to  do  maintenance  at  least  once  a  year.
However,  applicable  legislation  might  require  shorter
maintenance intervals.

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

8.1

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

NOTICE: Risk of electrostatic discharge

Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.

8.1.1

Opening the indoor unit

CAUTION

The  front  panel  is  heavy.  Be  careful  NOT  to  jam  your
fingers when opening or closing the unit.

You just need to remove the front panel of the unit to gain access to
most  parts  which  need  maintenance.  In  rare  cases,  you  may  also
need to remove the switch box.

8.2

Checklist for yearly maintenance
of the indoor unit

Check the following at least once a year:

▪ Water pressure

▪ Water filter

▪ Water pressure relief valve

▪ Discharge piping

▪ Pressure relief valve of the domestic hot water tank

▪ Booster heater of the domestic hot water tank

▪ Switch box

▪ Descaling

▪ Chemical disinfection

▪ Anode

▪ Pressure reducing valve of the domestic hot water tank kit

▪ Pressure relief valve of the domestic hot water tank kit

Water pressure

Check whether the water pressure is above 1 bar. If it is lower, add
water.

Water filter

Clean the water filter.

NOTICE

Handle  the  water  filter  with  care.  Do  NOT  use  excessive
force  when  you  reinsert  the  water  filter  so  as  NOT  to
damage the water filter mesh.

1

3

2

5

4

Water pressure relief valve

Open the valve and check if it operates correctly. 

The water may be

very hot!

Checkpoints are:

▪ The  water  flow  coming  from  the  relief  valve  is  high  enough,  no

blockage of the valve or in between piping is suspected.

▪ Dirty water coming out of the relief valve:

▪ open the valve until the discharged water does NOT contain dirt

anymore

▪ flush  the  system  and  install  an  additional  water  filter  (a

magnetic cyclone filter is preferable).

To make sure this water originates from the tank, check after a tank
heat up cycle.

It is recommended to do this maintenance more frequently.

Discharge piping

Check  whether  the  discharge  piping  is  positioned  appropriately  to
drain the water. See 

"4.4.2 To connect the water piping" on page 7

and 

"4.4.3  To  connect  the  pressure  relief  valve  to  the  drain"  on

page 9

.

Summary of Contents for EHVH04SU18CB6W

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EHVH04SU18CB6W EHVH08SU18CB6W EHVH08SU26CB6W EHVH11SU26CB6W EHVH16SU26CB6W...

Page 2: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 3: ...wizard Capacities energy metering 18 5 2 5 Space heating control 18 5 2 6 Domestic hot water control 19 5 2 7 Contact helpdesk number 19 5 3 Menu structure Overview installer settings 20 6 Commission...

Page 4: ...unit is designed for indoor installation only and for ambient temperatures ranging from 5 35 C 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tigh...

Page 5: ...r input signal b 23 Safety thermostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage...

Page 6: ...gularities The maximum allowed deviation is 1 1 NOTICE Do NOT tilt the unit backwards 0 1 1 4 3 Connecting the refrigerant piping See the outdoor unit installation manual for all guidelines specificat...

Page 7: ...mplies with the applicable legislation INFORMATION If you have to inspect the inside of the domestic hot water tank you can access it via the booster heater boss The connection of the water piping inv...

Page 8: ...discharge pipe and tundish are delivered with the tank kit 180 l 260 l WARNING Install the tundish away from any electrical device Possible consequence Electric shock or fire NOTICE To ensure a free...

Page 9: ...ate the system the domestic hot water tank needs to be filled completely Turning on the system when the tank is not full can damage the integrated booster heater and cause electrical errors 4 4 6 To i...

Page 10: ...4 5 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M 1 2 3 1 2 3 X2M X5M X6YB X6YA X6Y X1A X19A 3031 a Legend see illustration below In c...

Page 11: ...the distribution network operator if necessary that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax 1 Connect the backup heater power supply For 6W...

Page 12: ...eful NOT to damage it 3 Use the 2 screws in the accessory bag to fix the wallplate of the user interface to the sheet metal of the unit Be careful NOT to distort the shape of the backside of the user...

Page 13: ...e illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 5 10 To connect the space heating ON OFF...

Page 14: ...red by the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the booster heater power supply and the earth cable INFORMATION The non self resetting thermal cut...

Page 15: ...methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the menu structure Accessing settings via t...

Page 16: ...installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 2 Basic configuration 5 2 1 Quick wizard Lan...

Page 17: ...ermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the unit s user interface is turned ON Code Description A...

Page 18: ...5 Space heating control Leaving water temperature Main zone Code Description A 3 1 1 1 N A Set point mode 0 Fixed Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for...

Page 19: ...ion on the comfort setpoint for the room Leaving water temperature Emitter type Code Description A 3 1 1 7 9 0B Reaction time of the system 0 Quick Example Small water volume and fan coils 1 Slow Exam...

Page 20: ...heater steps Forced off contact Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW operation Contact type main Contact type add Digi...

Page 21: ...To check the water volume in 3 2 Preparing water piping on page 4 The domestic hot water tank is filled completely The following is properly installed see the installation manual of the domestic hot w...

Page 22: ...o to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished...

Page 23: ...he PCB 8 1 1 Opening the indoor unit CAUTION The front panel is heavy Be careful NOT to jam your fingers when opening or closing the unit You just need to remove the front panel of the unit to gain ac...

Page 24: ...be ensured that the water quality remains compliant with EU directive 98 83 EC Anode No maintenance or replacement required Pressure reducing valve of the domestic hot water tank kit Depending on loc...

Page 25: ...th drain fill valve delivered as accessory h Water filter i Space heating water IN 1 1 4 F BSP j Space heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water h...

Page 26: ...heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water hot water OUT 3 4 F BSP m Low voltage wiring intake 24 mm n High voltage wiring intake power supply cont...

Page 27: ...nt OUT d Plate heat exchanger e Shut off valve with drain fill valve f 3 way valve g Backup heater h Flow sensor i Pressure relief valve j Domestic hot water tank k Components in domestic hot water ta...

Page 28: ...rmostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermost...

Page 29: ...ctrical meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC det...

Page 30: ...KRTW wired room thermostat External sensor floor or ambient 2 core 4 core communication 2 core 4 core main X2M 1 4 add X2M 1a 4 main X2M 1 3 4 add X2M 1a 3 4 main X2M 1 4 add X2M 1a 4 Only for KRP1AH...

Page 31: ...ssels pre charge pressure in domestic hot water tank kit 2 5 bar Expansion valve setting 8 bar Temperature and pressure relief valve Set opening temperature 90 95 C Set opening pressure 10 bar Replace...

Page 32: ...4P449980 1 B 00000005 4P449980 1B 2016 11 Copyright 2016 Daikin...

Reviews: