5 Configuration

Installation manual

19

08SU EHVH08~16SU26CB6W
Daikin Altherma – Low temperature split
4P449980-1B – 2016.11

Leaving water temperature: Modulation

#

Code

Description

[A.3.1.1.5]

[8-05]

Leaving water temperature modulation:

▪ 0 (No): Disabled

▪ 1  (Yes):  Enabled.  The  leaving  water

temperature  is  calculated  according
to  the  difference  between  desired
and actual room temperature.
This  allows  better  matching  of  the
heat 

pump 

capacity 

to 

actual

required  capacity  and  results  in  less
start/stop  cycles  of  the  heat  pump
and more economic operation.

N/A

[8-06]

Leaving water temperature maximum
modulation:

0°C~10°C (default: 3°C)

Requires modulation to be enabled.

This is the value by which the desired
leaving water temperature is increased
or lowered.

INFORMATION

When  leaving  water  temperature  modulation  is  enabled,
the  weather‑dependent  curve  needs  to  be  set  to  a  higher
position  than  [8-06]  plus  the  minimum  leaving  water
temperature  setpoint  required  to  reach  a  stable  condition
on  the  comfort  setpoint  for  the  room.  To  increase
efficiency, modulation can lower the leaving water setpoint.
By  setting  the  weather‑dependent  curve  to  a  higher
position, it cannot drop below the minimum setpoint. Refer
to the illustration below.

a

+[8-06]

−[8-06]

b

Ta

Tt

a

Weather-dependent curve

b

Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.

Leaving water temperature: Emitter type

#

Code

Description

[A.3.1.1.7]

[9-0B]

Reaction time of the system:

▪ 0:  Quick. 

Example: 

Small  water

volume and fan coils.

▪ 1:  Slow. 

Example: 

Large  water

volume, floor heating loops.

Depending on the system water volume
and the heat emitters type, the heat up
of a space can take longer. This setting
can compensate for a slow or a quick
heating system by adjusting the unit
capacity during the heat up cycle.

5.2.6

Domestic hot water control

CAUTION

Only for EHVH_SU_CB6W models.

When  using  the  domestic  hot  water  tank  to  produce  hot
water,  do  NOT  turn  OFF  the  heat  pump. 

Reason:

  the

electrical  backup  heater  from  the  space  heating  circuit  is
used during disinfection of the domestic hot water tank.

#

Code

Description

[A.4.1]

[6-0D]

Domestic hot water Type:

▪ 0 (Reheat only): Only reheat operation

is allowed.

▪ 1  (Reheat  +  sched.):  Same  as  2,  but

between the scheduled heatup cycles,
reheat operation is allowed.

▪ 2  (Scheduled  only):  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

[A.4.5]

[6-0E]

The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.

INFORMATION

There is a risk of space heating capacity shortage/comfort
problem (in case of frequent domestic hot water operation,
frequent  and  long  space  heating  interruption  will  happen)
when  selecting  [6‑0D]=0  ([A.4.1]  Domestic  hot  water
Type=Reheat only).

5.2.7

Contact/helpdesk number

#

Code

Description

[6.3.2]

N/A

Number that users can call in case of
problems.

Summary of Contents for EHVH04SU18CB6W

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EHVH04SU18CB6W EHVH08SU18CB6W EHVH08SU26CB6W EHVH11SU26CB6W EHVH16SU26CB6W...

Page 2: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 3: ...wizard Capacities energy metering 18 5 2 5 Space heating control 18 5 2 6 Domestic hot water control 19 5 2 7 Contact helpdesk number 19 5 3 Menu structure Overview installer settings 20 6 Commission...

Page 4: ...unit is designed for indoor installation only and for ambient temperatures ranging from 5 35 C 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tigh...

Page 5: ...r input signal b 23 Safety thermostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage...

Page 6: ...gularities The maximum allowed deviation is 1 1 NOTICE Do NOT tilt the unit backwards 0 1 1 4 3 Connecting the refrigerant piping See the outdoor unit installation manual for all guidelines specificat...

Page 7: ...mplies with the applicable legislation INFORMATION If you have to inspect the inside of the domestic hot water tank you can access it via the booster heater boss The connection of the water piping inv...

Page 8: ...discharge pipe and tundish are delivered with the tank kit 180 l 260 l WARNING Install the tundish away from any electrical device Possible consequence Electric shock or fire NOTICE To ensure a free...

Page 9: ...ate the system the domestic hot water tank needs to be filled completely Turning on the system when the tank is not full can damage the integrated booster heater and cause electrical errors 4 4 6 To i...

Page 10: ...4 5 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M 1 2 3 1 2 3 X2M X5M X6YB X6YA X6Y X1A X19A 3031 a Legend see illustration below In c...

Page 11: ...the distribution network operator if necessary that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax 1 Connect the backup heater power supply For 6W...

Page 12: ...eful NOT to damage it 3 Use the 2 screws in the accessory bag to fix the wallplate of the user interface to the sheet metal of the unit Be careful NOT to distort the shape of the backside of the user...

Page 13: ...e illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 5 10 To connect the space heating ON OFF...

Page 14: ...red by the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the booster heater power supply and the earth cable INFORMATION The non self resetting thermal cut...

Page 15: ...methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the menu structure Accessing settings via t...

Page 16: ...installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 2 Basic configuration 5 2 1 Quick wizard Lan...

Page 17: ...ermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the unit s user interface is turned ON Code Description A...

Page 18: ...5 Space heating control Leaving water temperature Main zone Code Description A 3 1 1 1 N A Set point mode 0 Fixed Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for...

Page 19: ...ion on the comfort setpoint for the room Leaving water temperature Emitter type Code Description A 3 1 1 7 9 0B Reaction time of the system 0 Quick Example Small water volume and fan coils 1 Slow Exam...

Page 20: ...heater steps Forced off contact Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW operation Contact type main Contact type add Digi...

Page 21: ...To check the water volume in 3 2 Preparing water piping on page 4 The domestic hot water tank is filled completely The following is properly installed see the installation manual of the domestic hot w...

Page 22: ...o to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished...

Page 23: ...he PCB 8 1 1 Opening the indoor unit CAUTION The front panel is heavy Be careful NOT to jam your fingers when opening or closing the unit You just need to remove the front panel of the unit to gain ac...

Page 24: ...be ensured that the water quality remains compliant with EU directive 98 83 EC Anode No maintenance or replacement required Pressure reducing valve of the domestic hot water tank kit Depending on loc...

Page 25: ...th drain fill valve delivered as accessory h Water filter i Space heating water IN 1 1 4 F BSP j Space heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water h...

Page 26: ...heating water OUT 1 1 4 F BSP k Domestic hot water cold water IN 3 4 M BSP l Domestic hot water hot water OUT 3 4 F BSP m Low voltage wiring intake 24 mm n High voltage wiring intake power supply cont...

Page 27: ...nt OUT d Plate heat exchanger e Shut off valve with drain fill valve f 3 way valve g Backup heater h Flow sensor i Pressure relief valve j Domestic hot water tank k Components in domestic hot water ta...

Page 28: ...rmostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermost...

Page 29: ...ctrical meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC det...

Page 30: ...KRTW wired room thermostat External sensor floor or ambient 2 core 4 core communication 2 core 4 core main X2M 1 4 add X2M 1a 4 main X2M 1 3 4 add X2M 1a 3 4 main X2M 1 4 add X2M 1a 4 Only for KRP1AH...

Page 31: ...ssels pre charge pressure in domestic hot water tank kit 2 5 bar Expansion valve setting 8 bar Temperature and pressure relief valve Set opening temperature 90 95 C Set opening pressure 10 bar Replace...

Page 32: ...4P449980 1 B 00000005 4P449980 1B 2016 11 Copyright 2016 Daikin...

Reviews: