SFLC-212-173
26
5.2 Setting table
A setting item changes by the specification of a product, or the existence of an option.
(1) Important setting
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Sets the phase wire
of input circuit.
(311)
Press SET and DISPLAY together for longer than 3 seconds
(311)
Select an phase wire by + and -
Press SET for longer than 3 seconds
Selected phase wire is entered
Press DISPLAY
Returns to display mode.
50
Sets the input
voltage
(phase-voltage
full scale).
(312)
Press SET and DISPLAY together for longer than 3 seconds
Press RESET/SHIFT
(311) (312)
Select an input voltage (In case of 1φ3W, it is phase-voltage full scale) by + and -
Press SET
Selected input voltage is entered
Press DISPLAY
Returns to display mode.
50
Sets the
measurement range
of voltmeter
(211)
Press SET and RESET/SHIFT together for longer than 3 seconds
(211)
Select a measurement range by + and -
Press SET
Selected measurement range is entered
Press DISPLAY
Returns to display mode.
42-45
Sets the
measurement range
of ammeter
(213)
Press SET and RESET/SHIFT together for longer than 3 seconds
(211)
Press RESET/SHIFT
Press RESET/SHIFT
Select a measuring range by + and -
(212) (213)
Press SET
Selected measuring range is entered
Press DISPLAY
Returns to display mode.
42-45
Sets the display
combination
(111)
Press SET for longer than 3 seconds
Select the display combination by + and -
(111)
Press SET
Selected display combination is entered
Press DISPLAY
Returns to display mode.
34-38
Sets the output
factor of analog
output 1 (AO1).
(221A)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press MODE
(211) (221A)
Select an output factor by + and -
Press SET
Selected output factor is entered
Press DISPLAY
Returns to display mode.
46
Sets the output
factor of analog
output 2 (AO2).
(222A)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press MODE
(211) (221A)
Press RESET/SHIFT
Select an output factor by + and -
Press SET
(222A)
Selected output factor is entered
Press DISPLAY
Returns to display mode.
46
Sets the output
factor of analog
output 3 (AO3).
(223A)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press MODE
(211) (221A)
Press RESET/SHIFT
Press RESET/SHIFT
Select an output factor by + and -
(222A) (223A)
Press SET
Selected output factor is entered
Press DISPLAY
Returns to display mode.
46