background image

Q-222-039 

 

Input current 
terminal 
1S, 1L 
 
Input voltage 
terminal 
P1, P2 
 
 
Ground 
terminal 

Input current 
terminal 
1S, 1L, 3S, 3L 
 
Input voltage 
terminal 
P1, P2 
 
 
Ground 
terminal 

Input current 
terminal 
1S, 1L, 3S, 3L 
2S, 2L 
 
Input voltage 
terminal 
P1, 0 
 
Ground  
terminal 

 

5. Connection 

 

Refer to the terminal name on the front name plate of the main unit, and connect according to the wiring  
diagram below or the wiring diagram name plate on the lower side of the main unit. 
Use the included M4 screws to connect the auxiliary power supply, input voltage, input current, output,  
and ground terminals. 

〔Applicable solderless terminal〕  

Solderless terminal for M4 screw 
Outer diameter of terminal, 8.5mm or less 
Tightening torque:1.0 to 1.3 N・m 

 

PTT2-92A-12                       PTT2-92A-33                       PTT2-92A-34 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 
 
 

■ Connection diagram 

PTT2-92A-12                         PTT2-92A-33                          PTT2-92A-34 

AUX.SUPPLY

L

( )

( )

P1

K

U

2

1

V

1S

E

A

( )

B

( )

OUTPUT

P2

AUX.SUPPLY

( )

P1

A

( )

B

( )

( )

OUTPUT

P2

AUX.SUPPLY

P1

E

OUTPUT

( )

A

( )

B

( )

( )

2S

0

E

2L

1L

LOAD

2
3

1

K

L

V

U

1S

1L

3S

K

K

0

3L

LOAD

L

2
3

1

U

V

L

3S

K

1L

1S

K

L

3L

LOAD

L

 

 

・Grounding is class D grounding (grounding resistance 100Ω or less). 
・If there is a power line that causes noise or a sharp voltage fluctuation, separate the output  

wiring as much as possible.  In addition, use twisted cable or shielded twisted cable. 

・This product will not be damaged even if the output terminal is left open in the current output 

specifications. 

・After completing the wiring work, attach the terminal cover. 

 

Output terminal 
A(+), B(-) 

Auxiliary  
supply terminal 
S1(  ), S2(  ) 

+ 

~ 

- 

~ 

Output terminal 
A(+), B(-) 

Auxiliary  
supply terminal 
S1(  ), S2(  ) 

+ 

~ 

- 

~ 

Output terminal 
A(+), B(-) 

Auxiliary  
supply terminal 
S1(  ), S2(  ) 

+ 

~ 

- 

~ 

Summary of Contents for PTT2-92A-12

Page 1: ...Q 222 039 INSTRUCTION MANUAL V I PHASE ANGLE TRANSDUCER PTT2 92A 12 PTT2 92A 33 PTT2 92A 34 MODEL B...

Page 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Page 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Page 4: ...thod 4 5 Connection 6 6 Handling explanation 7 7 Specification 7 1 Rating 7 7 2 Performance 8 7 3 Electrical strength Mechanical strength 9 7 4 Noise immunity 9 7 5 EMC 10 7 6 Structure and environmen...

Page 5: ...92A 12 M4 screw 4 piece set 1 M4 screw 5 piece set 1 PTT2 92A 33 M4 screw 4 piece set 1 M4 screw 7 piece set 1 PTT2 92A 34 M4 screw 4 piece set 2 M4 screw 5 piece set 1 4 Mounting method Please insta...

Page 6: ...e this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from th...

Page 7: ...ightening torque 1 0 to 1 3 N m PTT2 92A 12 PTT2 92A 33 PTT2 92A 34 Connection diagram PTT2 92A 12 PTT2 92A 33 PTT2 92A 34 AUX SUPPLY L P1 K U 2 1 V 1S E A B OUTPUT P2 AUX SUPPLY P1 A B OUTPUT P2 AUX...

Page 8: ...uxiliary power supply and voltage input are applied is the output equivalent to the input 0 7 Specification 7 1 Rating Item Specification Input Phase angle LEAD 60 to LAG 60 Please specify LEAD 90 to...

Page 9: ...g inverter output Cycle control PWM inverter SCR phase angle control Adjustment range The output adjustment range is BIAS 5 of the output span MAX 5 of the output span Use only when adjustment is requ...

Page 10: ...es 1 second of rated voltage 10 times 10 second intervals 40 times 1 second and 20 times 4 seconds and 10 times 16 seconds of rated current 2 times 1 minute intervals 10 times 1 second of rated curren...

Page 11: ...61000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Page 12: ...its 10 to 55 5 to 90 RH Non condensing Storage temperature limits 40 to 70 Product warranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012...

Page 13: ...rm use please adjust in the next way Remove the terminal cover and VR cap before adjustment and attach the VR cap and terminal cover after adjustment 1 For the output load connect an actual load withi...

Page 14: ...r less Z Other V I Phase Angle Transducer Three phase four wire Type Specification code PTT2 92A 34 Model Input Rated voltage Rated current Output Output load range Auxiliary supply B Model B 1 LEAD 6...

Reviews: