3P130768-6L   English

10

COMPLETE SYSTEM EXAMPLE

[4] Use round crimp-style terminals for connecting wires to the 

power supply terminal block.
If unavailable, observe the following points when wiring.

Do not connect wires of different gauge to the same 
power supply terminal.
(Looseness in the connection may cause overheating.)

Use the specified electric wire. Connect the wire securely 
to the terminal. Lock the wire down without applying 
excessive force to the terminal. (Tightening torque: 
131N·cm ±10%)

[5] Tightening torque for the terminal screws.

Use the correct screwdriver for tightening the terminal 
screws. If the blade of screwdriver is too small, the head 
of the screw might be damaged, and the screw will not be 
properly tightened.

If the terminal screws are tightened too hard, screws 
might be damaged.

Refer to the table below for the tightening torque of the 
terminal screws.

<Precautions when connecting the ground>

When pulling the ground wire out, wire it so that it comes 
through the cut out section of the cup washer.
(An improper ground connection may prevent a good ground 
from being achieved.)

10. 3 REMOTE POWER SUPPLY WIRING, 

TRANSMISSION WIRING, COMPUTERISED 
CONTROL WIRE

Pass the remote control wiring, the transmission wiring, 
and the computerised control wire into the control box 
through the through-hole and connect to the terminals 
on the X3M terminal block. After connection, secure 
with the included clamping material. 

(Refer to Fig. 18)

[PRECAUTIONS]

Refer to the “Remote Controller Installation Manual” on how 
to install and lay the wiring for the remote controller.

Do not, under any circumstances, connect the power wiring 
to the remote controller or transmission wiring terminal block.
Doing so can destroy the entire system.

Connect the remote controller and transmission wiring their 
respective terminal blocks.

10. 4 WIRING FOR THE HUMIDITY REGULATOR 

(LOCALLY PROCURED)

<VKM-GBMV1 SERIES ONLY>

Pass into the control box together with the power wire 
through the power wiring through-hole.

Remove the short-circuit wires (1 and 2) on the X1M 
terminal block and connect the wiring for the humidity 
regulator.

Secure with clamping material together with the power 
wire.

 (Refer to Fig. 17)

<VKM-GBMV1 series only>

If using humidistat, install one per Heat Reclaim Ventilator unit.
Controlling more than one Heat Reclaim Ventilator unit with a 
single humidity controller may prevent normal humidity oper-
ation and cause water leakage, etc.

10. 5 WIRING EXAMPLE

This unit can be used as part of the combined operation sys-
tem used together with indoor units (VRV system air condition-
ers), or as a independent system for processing outside air. 

When connecting with a cooling free building multi type and 
bringing the RA of this unit directly in from the ceiling, con-
nect to a BS unit identical to the building multi indoor unit 
(master unit), and use group-linked operation. (See the Engi-
neering Data for details.)

Tightening torque (N·m)

Terminal block for remote controller/
Transmission wiring (X3M)

0.88 ± 0.09

Power supply terminal block (X1M)

1.31 ± 0.13

Ground terminal

1.69 ± 0.25

Power 

su

pply wiring

S

he

a

thed c

ab

le 

(H05VV-0

3

G)

Tr

a

n

s

mi

ss

ion wiring

S

he

a

thed c

ab

le

S

witch

F

us

e

Power 

su

pply

Remote controller

VRV
Indoor 

u

nit

VRV
Indoor 

u

nit

VRV
O

u

tdoor 

u

nit

He

a

t Recl

a

im 

Ventil

a

tor (VKM)

He

a

t Recl

a

im 

Ventil

a

tor (VKM)

Electric wire

Round crimp-style terminal

Attach insulation sleeve

Round crimp-style terminal

Cup washer

Cut out section

Spring washer, flat washer

Ground screw

Wiring specifications

Sheathed wire (2 wire)

Size

0.75 - 1.25 mm

2

Length

MAX. 100 m

External contact spec-
ifications

Normally closed contact
(Current tolerance 10 mA – 0.5 A)

Fi

g

. 1

8

Clamp
(Accessory)

Remote controller wiring
Transmission wiring

Resin Clamp parts

Detail of terminal block (X3M)

01_EN_3P130768-6L.fm  10 ページ  2013年3月21日 木曜日 午前11時48分

Summary of Contents for VKM100GBMV1

Page 1: ...puchons de formes arrondies des grilles d aspiration vacuation d air avant l installation de cette unit Ventilaci n con recuperaci n de calor Por favor lea cuidadosamente el manual de instalacion e in...

Page 2: ...icable for a certain product or domain Be sure to use only the specified parts and accessories for installation work Failure to use the specified parts may result in the Heat Reclaim Ventilator unit f...

Page 3: ...ntil installation work is done 1 Decide upon a line of transport 2 Leave the unit inside its packaging while moving until reach ing the installation site Where unpacking is unavoidable use a sling of...

Page 4: ...be sufficient enough to eliminate the electric noise The bellows may not be able to be used in some districts so exercise caution Contact your local government office or fire department for details Wh...

Page 5: ...aring the weight of the unit Refer to Fig 3 5 THE METHOD OF INSTALLATION CAUTION Hold underside of the unit or hanger bracket without putting force on other parts when unpacking or moving the unit As...

Page 6: ...greater than or equal to the diameter of the connecting pipe pipe size PT3 4B When piping passes indoors always insulate it all the way to the base of the drain socket In areas where freezing may occu...

Page 7: ...ing that passes indoors After checking that the water supply piping connections do no leak insulate them using the included insulation as shown in Fig 10 Tighten both edges with clamping material Refe...

Page 8: ...e connections Refer to Fig 14 CAUTION When brazing a pipe while feeding nitrogen inside the pipe make sure to set the nitrogen pressure to 0 02 MPa 0 2 kg cm 2 or less using the pressure reducing valv...

Page 9: ...g and insects tends to swarm around the light minute insects may intrude indoors through the air supply opening and air filter In such cases the use of a high performance filter sold sep arately is re...

Page 10: ...wiring through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the uni...

Page 11: ...iring their respective terminal blocks 10 4 WIRING FOR THE HUMIDITY REGULATOR LOCALLY PROCURED VKM GBMV1 SERIES ONLY Pass into the control box together with the power wire through the power wiring thr...

Page 12: ...Fuse Switch Power supply 220 240V 50 Hz F1 F2 F1 F2 R S P1 P2 F1 F2 T1 T2 Transmission wiring Outdoor unit IN D OUT D Control box Standard indoor unit A Standard indoor unit B Earth Earth Earth Remote...

Page 13: ...ONTROL FORCED OFF AND ON OFF OPERATION Wire specifications and how to perform wiring Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller The equipment in...

Page 14: ...AL button for more than four seconds with the unit in the normal mode to enter the local setting mode 2 Use the TEMPERATURE ADJUSTMENT button to select the desired MODE NO The code display will blink...

Page 15: ...n 17 27 0 Approx 2500 hours Approx 1250 hours No counting Nighttime free cooling operation ON OFF and starting time 1 OFF ON 2hours later ON 4hours later ON 6hours later ON 8hours later Initial settin...

Page 16: ...ting Heating humidification 21 C Cooling suction temperature at refrigerant heat exchanger 26 C Configurable range of set temperature Heating humidification 14 to 26 C Cooling 18 to 33 C The correlati...

Page 17: ...listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal CAUTION If carpentry work is not completed when a test run is fin ished tell the cu...

Page 18: ...white page fm 1...

Page 19: ...white page fm 2...

Page 20: ...EM12A038 1303 3P130768 6L DE 00_CV_3P130768 6L fm 2...

Reviews: