2. Precautions During Heavy Repair
COOLING CYCLE HEAVY REPAIR
1) Remove retained refrigerant more than 5 minutes after turning off
a refrigerator. (If not, oil will leak inside.)
2) Remove retained refrigerant by cutting first high pressure side
(drier part) with a nipper and then cut low pressure side.
(If the order is not observed, oil leak will happen.)
Removal of retained
refrigerant.
- Use special parts and tools for R-134a or R-600a.
Use of tools.
Precautions
Items
Process
Compresso
Evaporato
Drye
High Pressure
Low
pressure
Suction
Discharge tube
Condense
Hot
1) Nitrogen only should be used when cleaning inside of cycle pipes
inside and sealing.
2) Check leakage with an electronic leakage tester.
3) Be sure to use a pipe cutter when cutting pipes.
4) Be careful not the water let intrude into the inside of the cycle.
Others.
- Weld under nitrogen atmosphere in order to prevent oxidation
inside a pipe. (Nitrogen pressure : 0.1~0.2 kg/cm2.)
Nitrogen blowing
welding.
- Be sure to replace drier when repairing pipes
and injecting refrigerant.
Replacement of drier.
49
Summary of Contents for FPN-X22D3 Series
Page 1: ...Jun 2012 ...
Page 4: ...2 Outside Diemension SPECIFICATIONS The real features are model dependent 3 ...
Page 24: ...WIRING DIAGRAM Basic Model 23 ...
Page 25: ...WIRING DIAGRAM Full Models 24 ...
Page 26: ...WIRING DIAGRAM Full Models_Inverter Comp 25 ...
Page 32: ...Evaporator in detail How to Disassemble Assemble for each part 31 ...
Page 34: ...7 Refrigerator Damper changing method How to Disassemble Assemble for each part 33 ...
Page 38: ...2 Freezing or cooling failure Weak cooling TROUBLE SHOOTING 37 ...
Page 41: ...6 Dews on Refrigerator Compartment TROUBLE SHOOTING 40 ...
Page 42: ...5 Refrigeration failure Foods does not get cool or cold soon TROUBLE SHOOTING 41 ...
Page 54: ...COOLING CYCLE HEAVY REPAIR Brzing Reference Drawings 53 ...