4 7
Pcb Control Functions
6.
Defrost Mode
• For ced Defrost
1) START: Temp Control SW is pushed for 5 sec continuosly
2)
FLOW
1- Buzzer for 1 sec.
2. Same of the general Defrost Flow
7.
Initial Defrost
1)
When Power is on, Check the D-SENSOR Temp.
2)
Start Condition: Less than 3.5 deg for D-SENSOR
8.
COMP Restart prevent
1)
The COMP. cannot be on within 6min. after COMP off.
2) During Pre-cool step in defrost mode. 6 min. dellay is unavailable
9.
Alarm function
1) DOOR OPEN: 3 sec. in times every minute
2)
TEMP SW: When it is clicked
3)
POWER ON
4)
FORCED DEFROST
5)
FAST TIME SW
10.
Control in R1 Error
* In R SENSOR Open/Short error, Compress/Fan are controled by time as
following
Comp/Fan ON TIME: 20 min.
Comp/Fan OFF TIME: 30 min.
11.
Error Code
1)
D1 Error
* Display: FREEZER RED LED on/off one times.
* Condition: It is occured when D sensor is open or short.
2)
D2 Error
* Display: FREEZER RED LED on/off two times.
* Condition: D2 Error is occured that heater off by timer for 80 min.
3)
R1 Error
* Display: REFRIGERATOR RED LED on/off one times.
* Condition: It is occured when R sensor is open or short
12.
OPTION
Protection of OVER-COOL in CRISP
NO CONTROL FUNCTION
CONTENTS
Display contents
LED on/off Output
D1 ERROR
D2 ERROR
R1 ERROR
Summary of Contents for ERF-310
Page 2: ......
Page 4: ...2 EXTERNAL DRAWINGS 4 1 ERF 310M 340M 370M 2 ERF 310A 340A 370A...
Page 5: ...5 3 WIRING DIAGRAMS 1 ERF 310M 340M 370M 2 ERF 310A 340A 370A...
Page 8: ...6 REFRIGERANT CYCLE DIA 8...
Page 36: ...10 EXPLODE DRA 36 1 ERF 310M ERF 340M ERF 370M...
Page 37: ...Explode drawings 37...
Page 38: ...38 2 ERF 310A ERF 340A ERF 370A Explode drawings...
Page 39: ...39 Explode drawings...
Page 40: ...11 PART LIST 40 1 Parts list M TYPE...
Page 41: ...Part List 41...
Page 42: ...42 Part List 2 Parts list A TYPE...
Page 43: ...Part List 43...
Page 48: ...13 MAIN PCB DIA 48...