6.6
Fusing
ELECTRIC SHOCK
: Can cause severe injury, death, or damage to equipment. Use a hotstick to service a
Bay-O-Netfuse.Donotinstallafusetocompleteanelectricalcircuitifafaultconditionissuspected.
Donotre-energizesuspectedfailedequipment.Afterinstallingfuses,energizetransformerfroma
remote upstream source.
WARNING:
Never attempt to remove fuses with pressure on the tank. Severe burns and personal
injury may result from hot dielectric fluid.
Bay-O-Net Fuses
The Bay-O-Net fuse (Fig. 20 A) is used in series with an isolation link or current-limiting fuse “ELSP Back-up
Fuse” to achieve over current protection and high current interrupting current rating. The bay-o-net fuses are
field replaceable without needing to open the transformer tank.
Fig. 20 A