ENGLISH
47
8.2.5
Enabling water flow rate estimation
Tank shape
You can set the shape of the tank from those listed:
-
Parallelepiped
-
Cylinder
Once the shape has been chosen, indicate the volume by setting the
largest side/diameter and the smallest side of the section.
Once configuration is complete, the system will be ready but in standby.
You can choose whether to access the "Main Menu" or set the "Optional Configurations".
Refer to the respective chapters 8.5 Main menu and 8.4 Optional configurations.
8.3
Filling Configuration
Absorbed current
Enter the rated current shown on the motor label.
The choice of values starts from a minimum of 0.5 A (default value) to a
maximum of 12.0 A, 20.0 A or 29.0 A, depending on the selected panel
and on the supply voltage.
When first installed, the key is inhibited, as entering a
value is mandatory.
Type of control used
The following controls are available:
Depth sensor
Floats
Level probes
When first installed, the key is inhibited, as entering a
value is mandatory.
Tank with float against dry run
Indicate whether the tank will be equipped with a float that stops pump operation in the event of a
lack of liquid.
8.3.1
Depth sensor
Tank with security float
Indicate whether you want to use safety floats.
Once you have made your choice, then indicate the polarity of your floats.
No float
(no protection
is set)
High float
(protection
against
overflow)
Low float
(protection
against empty
tank emergency)
Both floats
(both
protections are
set)