ENGLISH 

 

34 

 

 

2.1

 

Safety 

The device contains an electronic device with inverter. 
Use is allowed only if the electric system is in possession of safety precautions in accordance with the regulations in force in the 

country where the product is installed (for Italy CEI 64/2). The appliance is not intended to be used by persons (including children) 
with reduced physical, sensory or mental capacities, or who lack experience or knowledge, unless, through the mediation of a 
person responsible for their safety, they have had the benefit of supervision or of instructions on the use of the appliance. Children 

must be supervised to ensure that they do not play with the appliance.                        

 

2.2

 

Responsibility 

The Manufacturer does not vouch for correct operation of the machine or for any damage that it may cause if it has been tampered 
with, modified and/or run outside the recommended work range or in contrast with other indications given in this manual. 

 

2.3

 

Particular warnings 

 

Always switch off the mains power supply before working on the electrical or mechanical part of the system. Before 
opening the equipment, wait at least 15 minutes after disconnecting it from the power supply. The capacitor of the 

direct current intermediate circuit remains charged with dangerously high voltage even after the mains power has 
been turned off.

 Only firmly cabled mains connections are admissible. The appliance must be earthed (IEC 

536 class 1, NEC and other applicable standards).

 

 

Mains terminals and motor terminals may still have dangerous voltage when the motor is stopped. 

 

3.

 

APPLICATIONS 

The inverter of the 

MCE/C

 series is a device conceived for the management of 

circulation pumps

 allowing integrated regulation of 

the differential pressure (head); it is thus possible to adapt the performance of the circulation pump to the actual demands  of the 
system. This determines considerable energy saving, a greater possibility of control of the system, and reduced noise. 

The MCE-150/C inverter is designed so that it can be housed directly on the pump motor body. 

 

4.

 

TECHNICAL DATA 

 

MCE-150/C 

MCE-110/C 

Inverter power supply 

Voltage [VAC]  (Tol +10/-20%)   

380-480 

380-480 

Phases  

Frequency [Hz] 

50/60 

50/60 

Max. current [A] 

42,0-33,5 

32,5-26,0 

Leakage current to earth [mA] 

< 10 

Inverter output 

Voltage [VAC]  (Tol +10/-20%)  

0 - V supply 

0 - V supply 

Phases  

Frequency [Hz] 

0-200 

0-200 

Max. current [A rms] 

32,0 

24,0 

Mechanical power P2 

20 HP / 15 kW 

15 HP / 11 kW 

Mechanical 

characteristics 

Weight of unit [kg]   
(control unit only, excluding package) 

12 

Max. dimensions [mm] 

(LxHxD) 

340x430x250 

Installation 

Work position 

housed on the pump motor body 

Grade of protection IP 

55 

Max. ambient temperature [°C] 

40 

Hydraulic 

characteristics of 

regulation and 

operation 

Differential pressure regulating range 

1 - 95% full scale pressure sensor 

Sensors 

Type of pressure sensors 

Ratiometric 

Differential  pressure  sensors  full  scale 
value [bar] 

4/10 

Functionality and 

protections 

Connectivity 

 

Multi inverter connection 

Protections 

 

Self protected against overload 

 

Excess temperature of internal electronics 

 

Abnormal supply voltages 

 

Direct short circuit between output phases 

Temperatures

 

Storage temperature [ºC] 

-10 ÷ 40 

Table 1: Technical data 

 

Summary of Contents for MCE-110/C

Page 1: ...INSTALLATIE EN ONDERHOUD INSTRUCCIONES DE INSTALACIÓN Y MANTENIMIENTO INSTALLATIONS OCH UNDERHÅLLSANVISNING РУКОВОДСТВО ПО МОНТАЖУ И ТЕХНИЧЕСКОМУ ОБСЛУЖИВАНИЮ KURMA VE BAKIM BİLGİLERİ ΟΔΗΓΙΕΣ ΓΙΑ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΚΑΙ ΤΗ ΣΥΝΤΗΡΗΣΗ INSTRUCTIUNI PENTRU INSTALARE SI INTRETINERE NAVODILA ZA VGRADNJO IN UPORABO ИНСТРУКЦИЯ ЗА МОНТАЖ И ПОДДРЪЖКА INSTALLÁCIÓS ÉS KARBANTARTÁSI UTASÍTÁS MCE 150 C MCE 110 C V7...

Page 2: ...1 FRANÇAIS page 17 ENGLISH page 33 DEUTSCH seite 49 NEDERLANDS pag 65 ESPAÑOL pág 81 SVENSKA sid 97 РУССКИЙ стр 113 TÜRKÇE sf 129 ΕΛΛΗΝΙΚΑ σελ 145 ROMANA pag 161 SLOVENŠČINA stran 177 БЪЛГАРСКИ Стр 193 MAGYAR Old 209 ...

Page 3: ...ing Lights 44 9 MENU 44 10 FACTORY SETTINGS 48 11 TYPES OF ALARM 48 12 MODBUS MCE C 48 13 BACNET 48 1 KEY The frontispiece shows the version of this document in the form Vn x This version indicates that the document is valid for all software versions of the device n y For example V3 0 is valid for all Sw 3 y In this document the following symbols will be used to avoid situations of danger Situatio...

Page 4: ...otor terminals may still have dangerous voltage when the motor is stopped 3 APPLICATIONS The inverter of the MCE C series is a device conceived for the management of circulation pumps allowing integrated regulation of the differential pressure head it is thus possible to adapt the performance of the circulation pump to the actual demands of the system This determines considerable energy saving a g...

Page 5: ...ls is 16 mm The section type and laying of the cables for supplying power to the inverter and connecting to the electropump must be chosen according to the regulations in force Table 2 supplies an indication on the section of the cable to be used The table refers to 4 core PVC cables 3 phases earth and gives the recommended minimum section with relation to the current and the length of the cable T...

Page 6: ...6 10 10 10 10 16 16 16 16 16 16 16 32 A 6 6 6 6 10 10 10 16 16 16 16 16 16 16 16 36 A 10 10 10 10 10 10 16 16 16 16 16 16 16 16 16 40 A 10 10 10 10 10 16 16 16 16 16 16 16 16 16 16 44 A 10 10 10 10 10 16 16 16 16 16 16 16 16 16 16 48 A 10 10 10 10 16 16 16 16 16 16 16 16 16 16 16 52 A 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 56 A 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 60 A 16 16 16 16 16...

Page 7: ...electrical characteristics of the inputs see Table 3 Electrical characteristics of the inputs DC inputs V AC inputs Vrms Minimum switch on voltage V 8 6 Maximum switch off voltage V 2 1 5 Maximum admissible voltage V 36 36 Current absorbed at 12V mA 3 3 3 3 Max accepted cable section mm 2 13 N B The inputs can be controlled with any polarity positive or negative with respect to their earth connect...

Page 8: ...set point reduction function in remote mode I3 Quick Start If input 3 is activated from the control panel the pump is started at the quick start frequency Fq see advanced menu I4 Not enabled Figure 5 Example of Connection of Quick Start Digital Input With reference to the example in Figure 4 and if the EXT and Economy functions have been activated from the control panel the system behaviour will b...

Page 9: ...ltage 0 10V itself see par 7 1 3 and par 9 The input A2V is not enabled See Figure 6 for an example of connection Figure 6 Example of Connection of Analogue Input N B The 0 10V analogue input is mutually exclusive with the NTC type temperature sensor T connected to the same poles of the 18 pole terminal block 5 5 3 NTC wiring diagram for measuring the fluid temperature T and T1 For installation of...

Page 10: ... listed below refer to the two 3 pole terminal boards J3 and J4 indicated with the screen printing OUT1 and OUT2 below which is also indicated the type of contact for the terminal NC Normally Closed C Common NO Normally Open Characteristics of the output contacts Type of contact NO NC COM Max bearable voltage V 250 Max bearable current A 5 If resistive load 2 5 If inductive load Max accepted cable...

Page 11: ... as follows 1 hold down the central menu key for 5 seconds 2 scroll through the parameters until you see ET 3 increase the value of the ET parameter in the advanced menu until the noise disappears For the possible operating modes of twin systems see par 9 6 START All the starting operations must be performed with the MCE 150 C cover closed Start the system only when all the electrical and hydrauli...

Page 12: ...ent mode the differential pressure is reduced or increased as the water request falls or rises This mode may be set by means of the control panel on the cover of the MCE 150 C see par 9 7 1 5 T constant function This function causes the circulator to increase or decrease the flow rate to keep constant the temperature measured by the NTC sensor connected as described in paragraph 5 5 3 Four operati...

Page 13: ...the circulator works to keep the absolute difference between T and T1 constant at a dTs inversely proportional to the temperature recorded by T1 For example when T1 50 C the circulator keeps the absolute difference between T and T1 constant at 13 75 C 5 If T1 70 C dTs T T1 10 Finally when the temperature T1 is higher than 70 C the circulator works to keep the absolute difference between T and T1 c...

Page 14: ...the yellow light is lit Red light Warning of an alarm malfunction present in the system If the light is blinking it is a non blocking alarm and the pump can still be controlled If the light is fixed it is a blocking alarm and the pump cannot be controlled Green light Pump ON OFF signal If On the pump is running If Off the pump is stopped 9 MENU MCE C provides 2 menus user menu and advanced menu Th...

Page 15: ...ures T and T1 1 10000 K Td Running time of the hydraulic circuit it acts in an inversely proportional way on the regulating speed in the T and DT regulations 0 1800 s Bs Parameter for setting up Booster mode 0 80 Ad Modbus address of the device 1 247 Br Serial communication baud rate 1 2 2 4 4 8 9 6 19 2 38 4 Kb s Pa Type of parity control None Odd Even Sb Number of stop bits 1 2 Rd Minimum respon...

Page 16: ...t point is set from Page 3 0 Depending on the type of regulation chosen on the previous page the set point to be set will be a head Hs a frequency Fs a temperature Ts or a difference in temperature dTs Page 5 0 Page 5 0 is displayed in all pressure regulating modes and allows the setting of auto or economy operating mode Auto mode disables the reading of the status of digital input I2 and in fact ...

Page 17: ...urs Liquid temperature measured on the input A1V 18 pole terminal block Liquid temperature measured on the input A2V 18 pole terminal block T Temperature difference of the liquid T T1 in absolute value Page 9 0 On page 9 0 you can choose the language in which to display the messages Page 10 0 On page 10 0 you can display the alarms log by pressing the right button Alarms Log If the system finds an...

Page 18: ...e Error e22 e30 Voltage Error e31 Protocol Error e32 e35 Excess temperature e37 Low voltage e38 High voltage e39 e40 Excess current e42 Dry operation e43 e44 e45 e54 Pressure Sensor e46 Pump Disconnected Booster mode activated in an operation mode not allowed e55 Temperature sensor T error e56 Temperature sensor T1 error Table 6 List of Alarms 12 MODBUS MCE C The use of the Modbus protocol is allo...