ENGLISH
GB
35
Set-point reduction percentage
50 %
Type of external analogue signal
0-10V
Twin operating mode
= Alternate every 24h
Pump start control
EXT (from remote signal on input IN1).
7<3(62)$/$50
Alarm Code
Alarm Symbol
Alarm Description
e0 - e16; e21
Internal Error
e17 - e19
Short Circuit
e20
Voltage Error
e22 - e31
Internal Error
e32 - e35
Electronic system excess temperature
e37
Low voltage
e38
High voltage
e39 - e40
Pump blocked
e43; e44; e45; e54
Pressure Sensor
e46
Pump Disconnected
e42
Dry operation
e56
Motor excess temperature (motor
protector trips)
e57
Frequency of PWM external signal less
than 100 Hz
e58
Frequency of PWM external signal
greater than 5 kHz
Table 7: Factory settings
Tabella 8: Elenco allarmi
15. DISPOSAL
This product or any part of it must be disposed of correctly:
- Use public or private local systems for waste collection.
- If that is not possible, contact Dab Pumps or the nearest authorised
service workshop.
INFORMATION
Frequently asked questions (faq) on the ecodesign directive 2009/125/
ec establishing a framework for the setting of ecodesign requirements
for energy-related products and its implementing regulations:
http://
ec.europa.eu/enterprise/policies/sustainable-business/documents/
HFRGHVLJQJXLGDQFH¿OHVBIDTBHQSGI
Guidelines accompanying commission regulations implementing the
ecodesign directive:
KWWSHFHXURSDHXHQHUJ\HI¿FLHQF\HFRGHVLJQ
OHJLVODWLRQBHQKWPVHH³FLUFXODWRUV´
16. ERROR CONDITION AND RESET
Display
indica-
tion
Description
Reset
e0 – e16
Internal
error
- Switch off system power.
- Wait for the warning lights on the control panel
to go off, then power the system again.
- If the error persists, change the circulator.
e37
Low mains
voltage
(LP)
- Switch off system power.
- Wait for the warning lights on the control panel
to go off, then power the system again.
- Check that the mains voltage is correct, if ne-
cessary reset it at the plate values
e38
High mains
voltage
(HP)
- Switch off system power.
- Wait for the warning lights on the control panel
to go off, then power the system again.
- Check that the mains voltage is correct, if ne-
cessary reset it at the plate values.