Wired Controller
CDV-46
30
Parameter
code
Parameter name
Parameter
range
Default
value
Note
P50
Air outlet
temperature setting
for Fresh Air Indoor
Unit in cooling*
16°C~30°C(61°F ~
86°F )
18°C
(64°F)
Only applicable to Fresh Air
Indoor Unit
P51
Air outlet
temperature setting
for Fresh Air Indoor
Unit in heating*
16°C~30°C(61°F ~
86°F )
22°C
(71°F)
Only applicable to Fresh Air
Indoor Unit
P54
Union setting of
Fresh Air Indoor
Unit*
00: without union
control
01: with union control
00
After union function is set,
Fresh Air Indoor Unit will be
turned on/off following the
on/off status of common
indoor unit. Besides, Fresh
Air Indoor Unit can also be
turned on/off manually.
Note: only applicable to
Fresh Air Indoor Unit.
Note:
ķ
Under parameter setting status, FAN, TIMER, SLEEP and SWING button are
invalid. Press ON/OFF button to go back to home page, but not turning on/off
the unit.
ĸ
Under parameter setting status, the signal from remote controller is invalid.
Summary of Contents for CDV-46
Page 2: ......
Page 43: ...Wired Controller CDV 46 37 Fig 6 5 Timer Off setting in unit On status in Celsius g g ...
Page 46: ...Wired Controller CDV 46 40 ...
Page 47: ...Wired Controller CDV 46 41 Fig 6 7 Unit On Off time setting in unit On status in Celsius ...
Page 48: ...Wired Controller CDV 46 42 Fig 6 8 Unit On Off time setting in unit On status in Fahrenheit ...
Page 51: ...Wired Controller CDV 46 45 Fig 6 9 Setting of Quiet function in Celsius ...
Page 54: ...Wired Controller CDV 46 48 Fig 6 11 Turn on Air Function in Celsius ...
Page 55: ...Wired Controller CDV 46 49 Fig 6 12 Turn on Air Function in Fahrenheit ...
Page 58: ...Wired Controller CDV 46 52 Fig 6 13 Save Setting for Cooling in Celsius ...
Page 59: ...Wired Controller CDV 46 53 Fig 6 14 Save Setting for Cooling in Fahrenheit ...
Page 62: ...Wired Controller CDV 46 56 Fig 6 15 Turn on Filter Clean Reminder Function in Celsius ...
Page 74: ......