Maximum pressure load of the toothed rack is not
automatically identical with the maximum pressure
force of the drive!
Pressure load diagram
500
600
800
1000
1
100
1200
1300
1400
1500
1600
0
200
400
600
800
1000
1200
1400
max.
Load
(N)
Stroke (mm)
- Swivel radius of the drive must have clearance
across the entire range of the stroke, otherwise
the rack and pinion drive and the suspension can
be damaged
- Drives with a stroke of ≥800 mm must not be
mounted „hung up at the bottom“ (e.g. bracket UK)
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it’s inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
- Technical clarification is required with D+H in case
of only tensile force applications of more than 500 N
Mounting information
Safety notes
Operating voltage 230 VAC!
Risk of injury from electric shock
Do not reverse L+N! Connect PE!
Observe enclosed red safety note!
- Connection must be carried out by a certified
electrical technician
- Danger of crushing hands and fingers!
- Keep people away from the operating area of the drive
- Keep children away from the control
- Use only in dry rooms
- Suitable for indoor mounting only.
Use rain detector in locations if there is a risk of rain
- Use unmodified original D+H parts only
- Observe the bracket-set mounting instructions
- Observe pressure load diagram of the rack and
pinion drive rack
- Use option "-W" if mounted outdoors!
Intended use
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 230 VAC
- Usable for smoke extraction, D+H Euro-SHEV in
accordance with DIN EN 12101-2 as well as daily
ventilation
- Suitable for indoor mounting only
Drive unit with 2.5 m silicone cable. Depending on
the type of window, different bracket sets are
available separately.
Scope of supply
99.823.58 2.2/06/12
ZA 105-K
4/12
Type
ZA 105-K
Rated voltage
230 VAC, ±10%, 50 Hz
Performance
27 W / 30 VA
Nominal force
1000 N*
Runtime /100 mm
10 sec.
Nominal locking force
1100 N
Service life
>10 000 double strokes
Duty cycle
30 %, with cycle time
10 minutes
Housing
Aluminium anodized,
PC
Protective system
IP 65
Temp.range
-5 ... +75 °C
Nominal stroke length
See type plate
* + approx. 20 % cut-off reserve (temporary)
Technical data