ZA-K-BSY+

99.823.99 1.1/07/11

6/20

500

600

800

1000

1

100

1200

1300

1400

1500

1600

0

200

400

600

800

1000

1200

1400

max.

Load

(N)

Stroke (mm)

durable

temporary

Drive unit with 2.5 m silicone cable. Depending on
the type of window, different bracket sets are
available separately.

Scope of supply

Mounting information

Pressure load diagram

Safety notes

Operating voltage 230 VAC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230V!

Observe enclosed red safety note!

- Connection must be carried out by a certified

electrical technician

- Danger of crushing hands and fingers!
- Keep people away from the operating area of

the drive

- Keep children away from the control
- Observe pressure load diagram of the gear rack!
- Use only in dry rooms
- Suitable for indoor mounting only. Use rain

detector in the event that there is a risk of rain

- Use option "-W" if mounted outdoors!
- Use unmodified original D+H parts only
- Observe the bracket-set mounting instructions

* only with BI-BT1 (electronically isolated due to Bluetooth)

- Rack and pinion drive for electric opening and

closing of windows and flaps in the facade and
roof area

- Operating voltage 230 VAC
- Up to 4 drives possible
- Useable for smoke extraction, D+H Euro-SHEV in

accordance with DIN EN 12101-2 as well as daily
ventilation

- Suitable for indoor mounting only

Intended use

- Microprocessor-controlled synchronous

electronics BSY+ for safe and precise
synchronous running of up to 4 drives

- Individually programmable via software SW-BSY+*
- SHEV-high speed function (fast-running feature in

OPEN-direction)

- Closing edge protection for the main closing edge
- Especially quiet motor running in ventilation mode
- Optinal with "-AS2" = protection class 2 and

"-AS3" as well as "-LS" = protection class 3

Features

- Swivel radius of the drive must go free over entire

range of stroke. Otherwise, the toothed rack and
the suspension can be damaged.

- Drives with a stroke of

must not be moun-

ted „hung up at the bottom“ (e.g. bracket UK).

- Eyebolt has to be adjusted so, that the drive is

disconnected with closed flap through it’s inside
stop position damping. Brackets can be damaged
by to rigid adjustment!

800 mm

- The drive set will be full configured by factory.

The drives must be reconfigured in case of
alterations (e.g. removing of drives from existing
set or integrating a new drive) with SW-BSY+*.

- Use only drives with the same force.
- Ensure evenly load distribution on all the drives.

Maximum pressure load of the toothed rack is not
automatically identical with maximum pressure force
of the drive!
Loads from over 1000 N to 1500 N are only briefly
permissible (e.g. to throwing off snow or with wind
loads). These may arise up to a stroke of 800 mm.

Summary of Contents for ZA 105-K-BSY+

Page 1: ... bitte separat bestellen please order bracket sets separately Kiinnikesarjat tilattava erikseen Rogamos que pidan los juegos de fijación por separado Standard Ausführung Standard version Vakio malli Estándar modelo Ausführung ohne Tubus Version without tube versio ilman suojaputkea option OT Modelo sin tubo opcional OT Option OT option OT 99 823 99 1 1 07 11 ...

Page 2: ...hinweise Betriebsspannung 230 VAC Verletzungsgefahr durch Stromschlag L N nicht vertauschen PE anschließen 230V liegen auch am BSY Datenbus an Anschluss darf nur durch eine autorisierte Elektrofachkraft erfolgen Quetschgefahr im handzugänglichen Bereich Personen aus dem Fahrbereich desAntriebes fernhalten Kinder von der Steuerung fernhalten Nur in trockenen Räumen verwenden Nur für die Innenmontag...

Page 3: ...Kräfte SB III SB II SB I 300 N 300 N 300 N 300 N 800 N 800 N 800 N 800 N 1000 N 1000 N 1000 N 800 N 1500 N 1000 N 1000 N 800 N ZA 35 ZA 85 ZA 105 ZA 155 I III 77mm 23mm 7 1 mm s 5 mm s 5 mm s 7 1 mm s 9 mm s HS 17 mm s II Schließbereiche Technische Daten ZU Deutsch ZA K BSY 99 823 99 1 1 07 11 3 20 Schließkantenschutz In Laufrichtung ZU verfügt der Antrieb über einen aktiven Schutz für die Hauptsc...

Page 4: ...erteilung Kritische Lastverteilung Bei komplettenAnheben der Pyramide Lichtkuppel ist wegen der zu erwartenden seitlichen Windlast eine bauseitige Führung notwendig YE GN PE zweites Anschlusskabel WH n c GY n c YE SGI GN SGI zweites Anschlusskabel GN SZ GY SZ YE SA WH SA Option SZ SA GN Data B YE Data A BN L ZU BK L AUF BU N 230 VAC Option SGI GN Data B YE Data A BN L ZU BK L AUF BU N 230 VAC 230 ...

Page 5: ...er Umsetzung in nationales Recht müssen nicht mehr gebrauchsfähige Elektrogeräte getrennt gesammelt und einer umweltgerechten Wiederverwertung zugeführt werden Entsorgung Eine ZA K BSY HS Synchrongruppe kann aus bis zu 4 Antrieben bestehen welche über einen Bus kommunizieren Jeder Antrieb hat seine eigene Adresse Diese ist mittels Software SW BSY und BI BT1 konfigurierbar Der letzte Antrieb einer ...

Page 6: ...HEV in accordance with DIN EN 12101 2 as well as daily ventilation Suitable for indoor mounting only Intended use Microprocessor controlled synchronous electronics BSY for safe and precise synchronous running of up to 4 drives Individually programmable via software SW BSY SHEV high speed function fast running feature in OPEN direction Closing edge protection for the main closing edge Especially qu...

Page 7: ...ff reserve temporary OPEN Forces CR III CR II CR I 300 N 300 N 300 N 300 N 800 N 800 N 800 N 800 N 1000 N 1000 N 1000 N 800 N 1500 N 1000 N 1000 N 800 N ZA 35 ZA 85 ZA 105 ZA 155 I III 77mm 23mm 7 1 mm s 5 mm s 5 mm s II Closing ranges Technical data CLOSE Closing edge protection In the CLOSE direction the drive has an active protection for the main closing edge If there is an overload in the clos...

Page 8: ...GI Option SZ SA GN Data B YE Data A BN L CLOSE BK L OPEN BU N 230 VAC Option SGI GN Data B YE Data A BN L CLOSE BK L OPEN BU N 230 VAC 230 VAC Standard GN Data B YE Data A BN L CLOSE BK L OPEN BU N Mounting examples triangular pyramid domelight pyramid weighty wing Uncritical load distribution Critical load distribution Guiding device required by customer in case of complete lift off of pyramid do...

Page 9: ...laration of Conformity We declare under our sole responsibility that the product described under Technical Data is in conformity with the following directives 2004 108 EC 2006 95 EC Technical file at D H MechatronicAG D 22949Ammersbek Thomas Kern Maik Schmees Member of the Board Authorized signatory Technical Director 12 06 2010 Electrical devices accessories and packaging should be sorted for env...

Page 10: ...äin hiljainen moottori tuuletuskäytössä Saatavissa myös AS 2 suojausluokka 2 sekä AS3 kuten LS suojausluokka 3 Turvallisuusohjeita Käyttöjännite 230 VAC Sähköiskun vaara Älä vaihda L ja N paikko ja Kytke PE BSY väylä toimii myös 230V jännitteellä Noudata avaajaan liitettyä punaista turvaohjetta Kytkennän saa suorittaa vain asianmukaisen koulutuksen saanut sähkömies Puristumisvaara Ihmisten pysyttä...

Page 11: ...N 800 N 800 N 800 N 800 N 1000 N 1000 N 1000 N 800 N 1500 N 1000 N 1000 N 800 N ZA 35 ZA 85 ZA 105 ZA 155 I I I I 7 7 m m 2 3 m m 7 1 m m s 5 m m s 5 m m s I I sulkeutumisalueet Tekniset tiedot Sormisuojaus KIINNI suunnassa moottori on varustettu aktiivisella sulkeutuvan reunan suojauksella Mikäli suljettaessa tapahtuu ylikuormitus tilanne alueilla 3 ja 2 ajaa avaaja itseään AUKI 10s ja yrittää uu...

Page 12: ... KELTAINEN Data A RUSKEA L KIINNI MUSTA L AUKI SININEN N 230 VAC Optio SGI VIHREÄ Data B KELTAINEN Data A RUSKEA L KIINNI MUSTA L AUKI SININEN N 230 VAC 230 VAC Vakio VIHREÄ Data B KELTAINEN Data A RUSKEA L KIINNI MUSTA L AUKI SININEN N Asennus esimerkkejä Kolmio pyramidi Kattovalokupu Pyramidi Raskas ikkuna Vähemmän kriittinen painonjako Kriittinen painonjako Ohjainputki tulee asentaa mikäli pyra...

Page 13: ...Hävittäminen Tarkastukset ja huollot tulee suorittaa D H n huoltoohjeiden mukaisesti Korjauksissa saa käyttää vain alkuperäisiä D H varaosia Fyysiset korjaukset saa suorittaa vain D H tai valtuutettu maahantuoja Puhdista lika pyyhkimällä kuivalla ja pehmeällä liinalla Älä käytä pesuainetta tai liuotusainetta puhistukseen Huolto ja puhdistus Kaikille D H tuotteille myönnetään 2 den vuoden takuu vah...

Page 14: ...remallera para la apertura y el cierre motorizado de ventanas y compuertas en fachadas y techos Tensión de servicio 230 VAC Apropiado para un máximo de 4 motores Se puede utilizar en aperturas de extracción de humos D H Euro SVHC conforme a la norma DIN EN 12101 2 así como para la ventilación natural diaria Adecuado únicamente para el montaje interior Utilización reglamentaria Características Elec...

Page 15: ...N 300 N 300 N 800 N 800 N 800 N 800 N 1000 N 1000 N 1000 N 800 N 1500 N 1000 N 1000 N 800 N ZA 35 ZA 85 ZA 105 ZA 155 I III 77mm 23mm 7 1 mm s 5 mm s 5 mm s II Rango de cierre Datos técnicos CIERRE Protección en el borde al cerrar En la dirección CIERRE el motor dispone de una protección activa del canto principal de cierre En caso de darse una sobrecarga en el sector de cierre 3 y 2 el motor para...

Page 16: ...nal SZ SA GN Data B YE Data A BN L CIERRE BK L ABRIR BU N 230 VAC Opcional SGI GN Data B YE Data A BN L CIERRE BK L ABRIR BU N 230 VAC 230 VAC Estándar GN Data B YE Data A BN L CIERRE BK L ABRIR BU N Ejemplos de montaje Pirámide triangular Claraboya Pirámide Hoja de ventana pesada Distribución de carga no crítica Distribución de carga crítica En caso de elevación completa de la pirámide claraboya ...

Page 17: ... nuestra responsabilidad que el producto descrito bajo Datos técnicos está en conformidad con las regulaciones 2004 108 EG 2006 95 EG Expediente técnico en D H MechatronicAG D 22949Ammersbek Thomas Kern Maik Schmees Junta directiva Apoderado Director técnicor 12 06 2010 Declaracióndeconformidad Recomendamos que los aparatos eléctricos accesorios y embalajes sean sometidos a un proceso de recuperac...

Page 18: ...s Programmierbar über Software SW BSY und BI BT1 Programmable via SW BSY and BI BT1 software ProOhjelmoitavissa SW BSY et BI BT1 Programable con el software SW BSY y BI BT1 GN grün green vihreä verde YE gelb yellow keltainen amarillo BU blau blue sininen azul BN braun brown ruskea marrón BK schwarz black musta negro WH weiss white valkoinen blanco PK rosa pink pinkki rosa GY grau grey harmaa gris ...

Page 19: ...pimässä tilassa MUUTOIN ON MAHDOLLISTA SAADA SÄHKÖISKU Conecte el BI BT1 únicamente sin tensión eléctrica EN CASO CONTRARIO EXISTE RIESGO DE ELECTROCUCIÓN Abzweigdose Junction box Kytkentärasia Caja de conexión L N PE 230 VAC 50 Hz 1 2 BU YE GN BN YE GN N PE Data a Data b ZA K BSY Slave 1 BK BU YE GN BN YE GN N PE Data a Data b ZA K BSY Master 2 BK L L L L Co nn ec ted Po we r BI BT 1 Bus Interfac...

Page 20: ...eudet teknisiin muutoksiin pidetään Derecho re servado a modificaciones técnicas 99 823 99 1 1 07 11 Abmessungen Dimensions Mitat Dimensiones 216 9 13 30 55 15 35 225 12 160 46 104 9 13 Ø 6 30 30 9 7 Hub stroke liikemitta carrera 165 mm Hub stroke liikemitta carrera 82 mm 100 mm Nennhub nominal stroke Nimellis liikemitta Carrera nominal 162 Ausführung ohne Tubus Version without tube Versio ilman s...

Reviews: