Informations for starting
Carry out following sight and performance checks for switching-on the smoke and heat vent
control panel.
All cables
connected?
Factory set?
(DIP switch)
10k
Ω resistor in
smoke vent
button
?
End module
2x47k
Ω
in junction box?
Connect mains.
LED mains lightens?
Connect battery
lines. Control l
ightens?
Smoke vent flap opens
and closes?
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
yes
yes
yes
yes
yes
yes
yes
Performance check alarm/reset and ventilation
yes
Partial or incomplete connection of
components can cause malfunction.
Check following connections: mains 230 V,
drives, smoke vent buttons, when necessary
fire detectors and vent buttons.
See wiring an connection plans pages 27-29.
Delivery condition of DIP switch see
pages 24-25.
Resistor must be cramped in electric last
button on terminal 3/8 (RT 45).
See connection plan pages 28.
10k
Ω resistor in fire
detector?
yes
End module on last or only drive in junction
box on wire 5 orange, 6 black, 7 black.
See connection plan page 27.
Check line safety fuse in distribution box and
fuse mains in control panel.
Mains still not available or line switch on "0"
or one of fuses faulty.
Possibly change poles in drive.
no
no
no
no
no
no
no
no
Operation - Release in case of alarm
clic
k
External control
Manual opening by smoke vent button:
Automatic opening by fire detector:
Automatic opening by external control (e.g. fire alarm system):
OK
SMOKE VENT
OK
OK
RT
Reset
OFF
ON
Line
RZN
OK
RT
OK
RT
Reset
OFF
ON
Line
RZN
Reset
OFF
ON
Line
RZN
English
English
Resistor must be cramped in last or only fire
detector on terminal 3 and 5 (SD-O/FD-T).
Resistor remains in control panel between
terminal RM "R" and "–", when no fire
detector is connected.
See connection plan page29.