D+H RZN 4304 Instructions For Use Manual Download Page 9

9/12

RZN 430x-M

Rev.:1.6

Maintenance

Once a year by a specialist company, who is
authorized by the appliance manufacturer.

Renew test badge, keep control book.

Respective current D+H maintenance
instruction is decisive.
D+H authorized expert companies are
specially trained by D+H for carrying out this
maintenance compentently, and therefore
they are automatically provided with relevant
maintenance instructions.
Following tests must be carried out with
maintenance:
- Outside examination/ inspection of system

components

- Measuring of insulation resistances
- Checking of all relevant power supply units
- Functional testing of connected system

components

- Record of competent carrying-out of

maintenance, and designation
according to directions

Every 6 months and after specialist or other
qualified personnel has taken the system
into operation.
Eliminate faults without fail. Keep a log book.

Inspection:

Check all devices and cable connections for
visible damage and dirt. Fire detectors, smo-
ke-vent buttons, smoke vents, etc. must not
be impeded in operation by storage goods
or reconstruction measures.

Function:

Continually activate a different smoke-vent
button (smoke detector) per line during each
new test.
Open the smoke-vent button. First all open
the system, then close it again.
Activate fire detectors with D+H smoke-
detector test unit or cigarette smoke. Re-
sponse time-lag approx. 20 sec. The red
LED must light up, and the smoke vent must
open.

Closing after automatic activation by smo-
ke detector:

Wait until the detector no longer contains any
smoke.
Use the  button  in  the  control  panel  to
switch  the  line on / off.
Press the concealed button marked 

 in

the smoke vent unit. The smoke vent closes,

and the red LEDs 

 in the button and in

the control panel extinguish.
When dip switch 3 is switched on OFF, the
flap can be closed directly by smoke vent
button as well. For this press masked key

 in button.

Smoke vent closes, detectors will be reset.

If used, activate external control.
The smoke vent must open.

Closing after automatic activation by
external control:

Opening the contact in the external system,
e.g. by resetting the fire detection system.
Press the concealed button marked 

 in

the smoke vent unit.
The smoke vent closes, and the red LEDs

 in the button and in the control panel

extinguish.
Check alarm display and all drives for
smooth operation up to final opening/closing
position.

Emergency power supply:

Cut out the main fuse in the distribution
system. Repeat the function test. The green

pilot light

in the smoke-vent buttons must

not light up.

The green LED 

Power

in the control

panel must not light up.
Ventilation is disabled.

Check-Up

Summary of Contents for RZN 4304

Page 1: ...uable property Annual function check by manufacturer or duly authorized specialist Wiring installation and functional testing only by qualified electrician The green pilot lights on the vent buttons m...

Page 2: ...2 LED DRIVES GROUP 2 fuse DIP switchblock S2 DIP switchblock S1 ALARM LINIE 2 LED FAULT LINIE 2 LED FAULT LINIE 1 LED ALARM LINIE 1 LED ALARM RESET Line ON OFF Reset detectors ALARM RESET Line ON OFF...

Page 3: ...em 400m Min clearance from walls beams etc 50cm Do not mount in airflow from ventilation systems or domelights Fire extinguishing systems must not adversely affect the detectors In case of sprinkler s...

Page 4: ...4 12 RZN 430x M Rev 1 6 Standard Connection with RT 42 11...

Page 5: ...nt button RT 42 On smoke vent buttons with a lower PCB serial no than DH4642 see rear of PCB Line connection to next smoke vent button from terminal 2 Terminal 7 is without significance Fire detectors...

Page 6: ...imate LT 43 thermal detector THE4 ye bk bk closed open signal optional open monitored Mot a Mot b L L P P bl bu br bn control alarm closed general malfunction Smoke vent button RT 43 H RT 43 N 10kW al...

Page 7: ...button each first to penultimate smoke vent button each Shunt connection by customer S general malfunction E1 Parallel Connection of Smoke Vent Buttons RT 43 H N Terminal resistors for line monitoring...

Page 8: ...ctor using the smoke heat vent button DIP switches 3 must be OFF DIP switch 4 ON The vent closes completely after the vent button has been pressed once If DIP switch 4 is OFF the vents will only close...

Page 9: ...nt button First all open the system then close it again Activate fire detectors with D H smoke detector test unit or cigarette smoke Re sponse time lag approx 20 sec The red LED must light up and the...

Page 10: ...fuse and connections Check fuse connections cables terminal resistors on drives Check terminal resistor or module between terminals 5 and 7 Check terminal resistor or module between terminals 5 and 6...

Page 11: ...which operate by thermal ascending force and by automatic fire recognition devices thermal detector smoke detector and they release either self acting or manual by smoke detectors at an early stage of...

Page 12: ...up end Example 1 1 Lane Simple wiring however unfavourable for voltage drop All drives on one line Example 2 2 lanes Control panel in the centre one side wired as branch the other one as terminal line...

Reviews: