D+H RZN 4304 Instructions For Use Manual Download Page 3

3/12

RZN 430x-M

Rev.:1.6

230V power supply:

Separate, nondisconnectible circuit.
Mark fuses for ID.
Power cable NYM-I 3x1.5.
Connected load for
RZN 4304-M =120 VA,
for RZN 4308-M = 240 VA.

24V emergency power supply:

Use only VdS - approved batteries.
RZN 4304-M:

2 x 12 V / 1,9 Ah

RZN 4308-M:

2 x 12 V / 6,5 Ah

For connection with alarm - objects:
RZN 4304-M:

2 x 12 V / 6,5 Ah

RZN 4308-M:

2 x 12 V / 6,5 Ah

Attention! For RZN 4304-M in conjunction
with 7,0 Ah  Batteries, always use the
housing of RZN 4308-M.

Low-voltage wiring:

Install and insert low-voltage wiring separa-
te from power-supply lines.
Mark wiring and terminal boxes red for
identification.

Control panel:

Mount in sheltered position suitable for
maintenance access in vicinity of drives.

Smoke-vent buttons:

Installations should be 150 cm above floor
level.

Fire detectors:

Max. area of surveillance for smoke- and
heat-vent system 400m².
Min. clearance from walls, beams, etc. 50cm.
Do not mount in airflow from ventilation
systems or domelights. Fire extinguishing
systems must not adversely affect the
detectors. In case of sprinkler systems,
please ask for information on special
interactive control! Area of surveillance in
conjunction with acoustic alarm as per BMA
regulations.

Drives:

All connected drives must not have more
than 

4 ampere

 altogether, when using control

panel 

type RZN 4304-M

, and they must not

have more than 

8 ampere

 altogether, when

using control panel 

type RZN 4308-M

.

Direction of drive rotation:

Reverse poles if running in wrong direction.

Regulations:

The relevant regulations are VDE 0833
covering danger warning equipment, VDE
0100 for electrical systems, DIN 18232 for
smoke- and heat-extraction systems, local
fire-brigade regulations and the EVU for
connection to mains supply.

 

Pictograph explanation

Smoke / heat alarm

Fault

Control panel O.K.

Fuse

Power supply

Vent button "OPEN"

Vent or smoke/heat vent button "CLOSE"

Battery charging voltage control

Installation Information

Summary of Contents for RZN 4304

Page 1: ...uable property Annual function check by manufacturer or duly authorized specialist Wiring installation and functional testing only by qualified electrician The green pilot lights on the vent buttons m...

Page 2: ...2 LED DRIVES GROUP 2 fuse DIP switchblock S2 DIP switchblock S1 ALARM LINIE 2 LED FAULT LINIE 2 LED FAULT LINIE 1 LED ALARM LINIE 1 LED ALARM RESET Line ON OFF Reset detectors ALARM RESET Line ON OFF...

Page 3: ...em 400m Min clearance from walls beams etc 50cm Do not mount in airflow from ventilation systems or domelights Fire extinguishing systems must not adversely affect the detectors In case of sprinkler s...

Page 4: ...4 12 RZN 430x M Rev 1 6 Standard Connection with RT 42 11...

Page 5: ...nt button RT 42 On smoke vent buttons with a lower PCB serial no than DH4642 see rear of PCB Line connection to next smoke vent button from terminal 2 Terminal 7 is without significance Fire detectors...

Page 6: ...imate LT 43 thermal detector THE4 ye bk bk closed open signal optional open monitored Mot a Mot b L L P P bl bu br bn control alarm closed general malfunction Smoke vent button RT 43 H RT 43 N 10kW al...

Page 7: ...button each first to penultimate smoke vent button each Shunt connection by customer S general malfunction E1 Parallel Connection of Smoke Vent Buttons RT 43 H N Terminal resistors for line monitoring...

Page 8: ...ctor using the smoke heat vent button DIP switches 3 must be OFF DIP switch 4 ON The vent closes completely after the vent button has been pressed once If DIP switch 4 is OFF the vents will only close...

Page 9: ...nt button First all open the system then close it again Activate fire detectors with D H smoke detector test unit or cigarette smoke Re sponse time lag approx 20 sec The red LED must light up and the...

Page 10: ...fuse and connections Check fuse connections cables terminal resistors on drives Check terminal resistor or module between terminals 5 and 7 Check terminal resistor or module between terminals 5 and 6...

Page 11: ...which operate by thermal ascending force and by automatic fire recognition devices thermal detector smoke detector and they release either self acting or manual by smoke detectors at an early stage of...

Page 12: ...up end Example 1 1 Lane Simple wiring however unfavourable for voltage drop All drives on one line Example 2 2 lanes Control panel in the centre one side wired as branch the other one as terminal line...

Reviews: