3/12
RZN 430x-M
Rev.:1.6
230V power supply:
Separate, nondisconnectible circuit.
Mark fuses for ID.
Power cable NYM-I 3x1.5.
Connected load for
RZN 4304-M =120 VA,
for RZN 4308-M = 240 VA.
24V emergency power supply:
Use only VdS - approved batteries.
RZN 4304-M:
2 x 12 V / 1,9 Ah
RZN 4308-M:
2 x 12 V / 6,5 Ah
For connection with alarm - objects:
RZN 4304-M:
2 x 12 V / 6,5 Ah
RZN 4308-M:
2 x 12 V / 6,5 Ah
Attention! For RZN 4304-M in conjunction
with 7,0 Ah Batteries, always use the
housing of RZN 4308-M.
Low-voltage wiring:
Install and insert low-voltage wiring separa-
te from power-supply lines.
Mark wiring and terminal boxes red for
identification.
Control panel:
Mount in sheltered position suitable for
maintenance access in vicinity of drives.
Smoke-vent buttons:
Installations should be 150 cm above floor
level.
Fire detectors:
Max. area of surveillance for smoke- and
heat-vent system 400m².
Min. clearance from walls, beams, etc. 50cm.
Do not mount in airflow from ventilation
systems or domelights. Fire extinguishing
systems must not adversely affect the
detectors. In case of sprinkler systems,
please ask for information on special
interactive control! Area of surveillance in
conjunction with acoustic alarm as per BMA
regulations.
Drives:
All connected drives must not have more
than
4 ampere
altogether, when using control
panel
type RZN 4304-M
, and they must not
have more than
8 ampere
altogether, when
using control panel
type RZN 4308-M
.
Direction of drive rotation:
Reverse poles if running in wrong direction.
Regulations:
The relevant regulations are VDE 0833
covering danger warning equipment, VDE
0100 for electrical systems, DIN 18232 for
smoke- and heat-extraction systems, local
fire-brigade regulations and the EVU for
connection to mains supply.
Pictograph explanation
Smoke / heat alarm
Fault
Control panel O.K.
Fuse
Power supply
Vent button "OPEN"
Vent or smoke/heat vent button "CLOSE"
Battery charging voltage control
Installation Information