Shift of drive cable

The drive will be full configured by factory.
The drives must be reconfigured in case of
alterations (e.g. removing of drives
from existing set or integrating
a new drive) with SCS.

If  after  mounting  the  measure  x  is  as  bigger  as 
23 mm, null balance with software SCS is neccesary.
Closure  Ranges  will  shift  in  relation  to  new  zero 
point.

Mount the drives mechanical stress-free.   
With that, a better load distribution
is ensured on all the drives.

At  vertical  active  pulling  application  (e.g.  for  a    
skylight) the forces must be rearranged by software 
SCS

Slave 1

Mounting informations

≥ 23 mm ? 

X

Main closing edge

Beside closing edge

Beside
closing edge

Closing edge protection

In  the  "CLOSE"  direction  the  drive  has  an  active 
protection for the main closing edge. If there is an 
overload in the closing range 3 and 2, the drive runs 
"OPEN" for 10 seconds, then "CLOSE" again. If after 
three  attempts  closing  is  not  possible,  the  drive 
remains in this position.
In  addition,  the  drive  is  equipped  with  passive 
protection. The closing speed in closing range 2 and 
1 is reduced to 5 mm/s.

 

 

Significantly greater forces can be

 

 

exerted at the secondary closing

 

 

edges. Danger of crushing hands and

 

 

fingers!

7/12

English

99.828.64 1.3/05/20

99.828.64 1.3/05/20

Electrical devices, accessories, batteries and packa-
ging  should  be  sorted  for  environmental-friendly 
recycling.  Do  not  dispose  electrical  devices  and 
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for 
waste  electrical  and  electronic  equipment  and  its 
implementation into national right, electrcal devices 
that are no longer usable must be collected separa-
tely  and  disposed  of  in  an  environmentally  correct 
manner.

Disposal

Declaration of Conformity

We  declare  under  our  sole  responsibility  that  the 
product  described  under  “Technical  Data”  is  in 
conformity with the following directives:

2014/30/EU, 2014/35/EU

Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek

Dirk Dingfelder 

Maik Schmees

Member of the Board 

Authorized signatory, Technical Director

18.05.2020

Maintenance and cleaning

Maintenance work is only allowed when the device is in 
a de-energized condition! Inspection and maintenance 
has to be carried out according to D+H maintenance 
notes.  Only  original  D+H  spare  parts  may  be  used. 
Repair is to be carried out exclusively by D+H.
Wipe  away  debris  or  contamination  with  a  dry,  soft 
cloth.
Do not use cleaning agents or solvents.

Guarantee

You will get 2 years guarantee for all D+H products 
from date of verified handing over of the system up to 
maximal  3  years  after  date  of  delivery,  when 
mounting  and  starting  has  been  carried  out  by  an 
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H 
components with external systems or with mixing of 
D+H products with parts of other manufacturers.

Visual inspection: 

Only one master drive is allowed.
The master always has the last address of all the 
drives; this can be found on a sticker attached to 
the drive. Slaves are numbered downwards from 
the master, so that in a group of three drives, for 
example, the master is no. 3, with a slave 2 and 
slave 1 drive. Please note that this only applies in 
the ex-factory configuration. As soon as the drives 
are reconfigured with SCS, the ex-factory 
addressing no longer applies.

Wiring:

Is the drive or drive group wired properly?
See connection plans.

Diagnostics with SCS software:

The SCS software and a BSY+ interface is 
required for further troubleshooting or 
configuration.

Troubleshooting

KA 34-ACB / KA 54-ACB

KA 34-ACB / KA 54-ACB

Summary of Contents for KA 34-ACB

Page 1: ...KA 34 ACB KA 54 ACB 99 828 64 1 3 05 20 Standard version Mirrored version Option L en Original instructions Page 2 Connection Page 8 Please order bracket sets separately ...

Page 2: ...rection Protection system for the main closing edge Locking relief after closing Drive unit with 2 5 m silicone cable Dependent on the type of window different bracket sets are available separately Extent of supply Intended use Chain drive for electric opening and closing of windows and flaps in the facade and roof area Operating voltage 24 V DC stabilized Useable for smoke ventilation as well as ...

Page 3: ...ycle time 10 minutes Aluminium powdercoated RAL 9006 IP 32 th bracket sets With covering stoppers delivered wi 5 75 C 30 min 300 C 90 not condensing LpA 70 dB A Closing edge protection activated 3 repetitions of stroke Locking relief activated retraction lift max 0 2 mm C3 Nominal stroke 100 mm 300 N 7 mm s 16 1 mm s O1 C1 C2 O2 O3 23 mm 150 N 5 mm s 5 mm s 77 mm 150 N 5 mm s 5 mm s 23 mm 500 N 7 ...

Page 4: ... 30 me 10 minutes With cycle ti Aluminium powdercoated RAL 9006 IP 32 With covering stoppers delivered with bracket sets 5 75 C 30 min 300 C 90 not condensing LpA 70 dB A Closing edge protection activated 3 repetitions of stroke Locking relief activated retraction lift max 0 2 mm C3 Nominal stroke 100 mm 500 N 7 mm s 17 2 mm s O1 C1 C2 O2 O3 23 mm 150 N 5 mm s 5 mm s 77 mm 150 N 5 mm s 5 mm s 23 m...

Page 5: ... 30 With cycle time 10 minutes Aluminium powdercoated RAL 9006 IP 32 With covering stoppers delivered with bracket sets 5 75 C 30 min 300 C 90 not condensing LpA 70 dB A Closing edge protection activated 3 repetitions of stroke Locking relief activated retraction lift max 0 2 mm C3 Nominal stroke 100 mm 800 N 7 mm s 17 2 mm s O1 C1 C2 O2 O3 23 mm 150 N 5 mm s 5 mm s 77 mm 150 N 5 mm s 5 mm s 23 mm...

Page 6: ...he forces must be rearranged by software SCS Slave 1 Mounting informations 23 mm X Main closing edge Beside closing edge Beside closing edge Closing edge protection In the CLOSE direction the drive has an active protection for the main closing edge If there is an overload in the closing range 3 and 2 the drive runs OPEN for 10 seconds then CLOSE again If after three attempts closing is not possibl...

Page 7: ... Only original D H spare parts may be used RepairistobecarriedoutexclusivelybyD H Wipe away debris or contamination with a dry soft cloth Donotusecleaningagentsorsolvents Guarantee You will get 2 years guarantee for all D H products from date of verified handing over of the system up to maximal 3 years after date of delivery when mounting and starting has been carried out by an authorized D H dist...

Page 8: ...Master 2 1 110 Ω 3 Group Mot a ACB a Mot b ACB b CPS M AM 1 2 110 Ω PinAssignment Connection BN Mot b OG ACB a GY ACB b GN BSY b YE BSY a WH Mot a WH weiss white blanc blanco BN braun brown brun marrón OG orange orange orange naranja YE gelb yellow jaune amarillo GN grün green vert verde PK rosa pink rose rosa GY grau grey gris gris 2 up to max 3 drives looped through KA 34 ACB KA 54 ACB 99 828 64...

Page 9: ... WH Mot a KA ACB GN BSY b YE BSY a GY ACB b OG ACB a BN Mot b WH Mot a KA ACB Connection Notes 1 Termination The ACB segment must be terminated with 2 resistors 110 Ω The resistors must in each case be connected at the end of the cable 2 Integrated resistor 3 Protect wire against short circuit 4 Cable according to D H table for layout of cables See instructions for use of control panel KA 34 ACB K...

Page 10: ...10 12 English KA 34 ACB KA 54 ACB 99 828 64 1 3 05 20 Connection M a s t e r Master Slave 5 cm 1 5 cm M a s t e r S l a v e 2 3 4 1 8 ...

Page 11: ...KA 34 ACB KA 54 ACB 99 828 64 1 3 05 20 350 500 600 700 800 1000 1100 1200 1300 247 5 322 5 372 5 422 5 472 5 576 5 628 5 678 5 728 5 A B 421 496 546 596 646 750 802 852 902 H Dimensions B 173 5 mm A 40 mm 5 1 m m H ...

Page 12: ...tr 28 32 22949Ammersbek Germany Tel 4940 605 65 239 Fax 4940 605 65 254 E Mail info dh partner com www dh partner com 2020 D H Mechatronic AG Ammersbek Rights to technical modifications reserved 100 Recycled paper 99 828 64 1 3 05 20 ...

Reviews: