GVL 8408-M-UL
GVL 8408-M-UL
99.828.04 1.0/06/19
99.828.04 1.0/06/19
4/12
5/12
English
English
View motherboard
For continued protection against fire, replace only with the same type
and rating of fuse or equivalent, adjacent to the fuse holders.
WARNING
Class 2 supply, 24 V shall be used.
Wiring plan (Paragon)
Output voltage 24 V DC!
Do not run cables together with power lines!
In case of a cable with
ground wire
(e.g. green / yellow) this must
not be used
!
total current
0.5
787
1312
2100
1
394
656
1050
1.5
262
427
699
2
197
328
525
2.5
157
262
420
3
131
213
351
3.5
112
180
299
4
98
164
262
ft
ft
ft
type
2x AWG 16
2x AWG 14
2x AWG 12
total current
0.5
240
400
640
1
120
200
320
1.5
80
130
213
2
60
100
160
2.5
48
80
128
3
40
65
107
3.5
34
55
91
4
30
50
80
m
m
m
type
2x 1,5 mm²
2x 2,5 mm²
2x 4 mm²
115 V AC, 60 Hz
to further ones
see line lenghts and cross sections
window drive
control panel
vent button
ca. 4 ft above
upper edge
firm flooring
external
control
4x AWG 20
4x AWG 20
2x AWG 20
4x AWG 20
rain sensor
3x AWG 14
room temperature
control
Line lenghts and cross sections
fuse mains
LED Power ON
28 - 14 AWG
max. 4.5 lb-in
22 - 12 AWG
max. 6 lb-in
mains connector
S1
F3.15A
T2.5A
S2
F3.15A
S3
F3.15A
S4
F3.15A
S5
F3.15A
Power
115 VAC
www.dh-partner.com
Ventilation control panel
GVL 8408-M-UL
Group 1
Group 2
Group 3
Group 4
Group 5
WARNING
For continued protection against fire,
replace only with the
same type and rating of fuse.
fuse drive
group 1
DIP-switch S1
fuse drive
group 2
DIP-switch S2
fuse drive
group 3
DIP-switch S3
fuse drive
group 4
DIP-switch S4
fuse drive
group 5
DIP-switch S5
group 1-5: 22 - 12 AWG / max. 4.5 lb-in
Encoding of group – DIP switches S1 - S5
Following functions can be adjusted for each group separately with
DIP switches S1 - S5
on
motherboard of control panel and on group plug-in unit, if available.
The delivery state of all DIP-switches is OFF.
1 = ON
Drives
CLOSE
up to final position by
single pressing
on respective vent button.
1 = OFF
Drives are closing
only so long as
the vent button is
pressed
.
2 = ON
Drives
OPEN
up to final position by
single pressing
on vent button.
2 = OFF
Drives are opening
only so long as
the vent button is
pressed
.
3 = ON
Drives are
automatically closed
by trigger of function „
Central CLOSE
",
e.g. by rain detector or room temperature control.
3 = OFF
Drives can be closed
only by pressing
the respective
vent button
.
4 = ON
Drives are
automatically opened
by trigger of function „
Central OPEN
",
e.g. by room temperature control.
4 = OFF
Drives can be opened
only by pressing
the respective
vent button
.