CDP-TW-K-BSY+
Main closing edge
Beside closing edge
Beside closing edge
In the "CLOSE" direction the drive has an active protection
for the main closing edge. If there is an overload in the closing
range 3 and 2, the drive runs "OPEN" for 10 seconds, then
"CLOSE" again. If after three attempts closing is not possible,
the drive remains in this position.
In addition, the drive is equipped with passive protection. The
closing speed in closing range 2 and 1 is reduced to 5 mm/s.
There are still substantial forces that
pose a risk to life and limb.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
Closing edge protection
Performance features
- Micro processor controlled synchro electronics
BSY + for a precise synchronous run of up to
2 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
- Locking relief after closing
- Especially quiet motor running in ventilation mode
- Symmetrical chain outlet
- Connection via pin-and-socket connector
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
Intended use
- Chain drive for electric opening and closing of heavy
windows and flaps in the facade and roof area
- Operating voltage 230 V AC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as
daily natural ventilation
- Only for inside mounting
Technical data
Observe maximum pressure load of the chain!
Maximum pressure load
per chain
is not
automatically identical with maximum pressure force
of the drive!
Pressure load diagram
250
500
750
1000
1250
1500
1750
2000
1500
1000
500
0
max.
Load
(N)
Stroke (mm)
3000
2500
per chain
total
Operating voltage 230 V AC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230V!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the chain!
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed r
ed safety slip!
Safety notes
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
Extent of supply
OPEN
Forces
CR
III
CR
II
CR
I
2 x 800 N
2 x 800 N
2 x 800 N
2 x 500 N
CDP-TW 1600
C
L
O
S
E
2 x 1500 N
2 x 1000 N
2 x 1000 N
2 x 500 N
CDP-TW 3000
2 x 1000 N
2 x 1000 N
2 x 1000 N
2 x 500 N
CDP-TW 2000
Running speed and forces
Normal operation
=
SHEV- fast running =
All forces
+ approx. 20 % switch-off reserve (temporary)
Closure Ranges
Type
CDP-TW 1600-K-BSY+ CDP-TW 2000-K-BSY+ CDP-TW 3000-K-BSY+
Power supply
230 V AC, +10 % / -15 %, 50 Hz
Power consumption
100 W / 142 VA
120 W / 160 VA
160 W / 214 VA
Nominal force
2 x 800 N
2 x 1000 N
2 x 1500 N
Nominal locking force
2 x 1500 N
Lifetime ***
>10 000 double strokes
Reliability
Re = 400
Duty cycle
30 % S2 (EN 60034-1), no continuous voltage
Housing
Aluminium, PC/ABS (end covers)
Ingress protection
IP 32
Temperature range
-5 ... +75 °C
Fire stability
30 min / 300 °C
Nominal stroke length *;** See type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings),
locking relief activated (0,3 mm)
* Programmable with software SCS
** 1000 mm max. according to VdS 2580
*** (500 mm) according to VdS 2580
WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.