18/36
CPS-M1
(L
T 84U-SD)
LT 84-U (-SD)
L
P
X6.4
X6.1
X4.1
X5.1
X4.5
X5.4
System
Battery-Mode
NSV 401
Battery low
A.V.R active
Battery-Mode
Power
I
O
2
NSV 401
1
6 4
X3
X4
5
4
3
2
1
X4
ACB.A
ACB +
ACB.B
SGI
–
2
2
1
1
4
3
2
1
AM-1-1-08-230-D4-D2
4
4
3
3
2
2
1
1
X1
X2
X6
X5
–
DI 2.1
DO 2.1
–
DI 1.1
–
DI 1.2
DO 1.1
L ▲
L ▼
L
N
E
N
N
L
NSV
X1
X6
X2
X5
X4
English
99.827.31 1.4/06/18
Connection – AM 230
Ventilation button
Connection – NSV 401 control and vent button to AM 230
No.
Name
Description
X1.1 L
Phase 230 V input
X1.2
N
Neutral conductor input
X2.1
N
Neutral conductor output
X2.2
L-OPEN Phase 230 V OPEN direction output
X2.3
L-CLOSE Phase 230 V CLOSE direction output
X2.4
E
Monitoring wire
X4.5
-
Reference potential (do not connect to P-)
X4.4
ACB +
Supply of the ACB interface
(not yet implemented)
X4.3
ACB.A
ACB interface of drive group
(not yet implemented)
X4.2
ACB.B
X4.1
SGI
Position transmitter for drive group
(not yet implemented)
X5.4 DO 1.1
Freely configurable digital output 1.1, max. 50 mA /
NOT CLOSED signal LT
X5.3 -
Reference potential (do not connect to P-)
X5.2 DI 1.1
Freely configurable digital input 1.1,
0 to 28 V, active minus or plus / OPEN LT
X5.1 DI 1.2
Freely configurable digital input 1.2,
0 to 28 V, active minus or plus / CLOSE LT
X6.4 -
Reference potential (do not connect to P-)
X6.3
FES
Fault NSV
X6.2 -
Reference potential (do not connect to P-)
X6.1
SES
Start NSV
, max. 50 mA
Please Note:
If the AM 230 is used as a pure ventilation group, the line monitoring
can be switched off. In this case, no EM 230 end module is required.