CONFIGURATIONS (cont´d)
Note: You will find more configurations on the web page.
8
EDIT
L1
L2
L3
I
o
FI40 30mA 4pol.
FI-Schalter
6 x MCB 16A “C” 1pol.
1 x RCD 40A 30mA 4pol.
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
2
3
1
PUSH
2
3
1
PUSH
2
3
1
PUSH
2
3
1
PUSH
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
2
3
1
PUSH
eCP_20
eCP_20
eCP_20
eCP_20
IN
OUT1
OUT2
OUT3
IN
OUT1
OUT2
OUT3
IN
OUT1
OUT2
OUT3
3 x LX-218CA-NET
(3 x 3,1A = 9,3A RMS)
(3 x 20A peak = 60A)
3 x LX-218CA-NET
(3 x 3,1A = 9,3A RMS)
(3 x 20A peak = 60A)
3 x LX-218CA-NET
(3 x 3,1A = 9,3A RMS)
(3 x 20A peak = 60A)
4 x AERO-40A
(4 x 3A RMS = 12A)
(4 x 16A peak = 64A)
4 x AERO-40A
(4 x 3A RMS = 12A)
(4 x 16A peak = 64A)
4 x AERO-40A
(4 x 3A RMS = 12A)
(4 x 16A peak = 64A)
With these values, in one phase we will have:
RMS current: 4 x
AERO-40A
and 3 x
LX-218CA-NET
--> 12A + 9,3A RMS = 21,3A RMS, phase
max RMS current is 32A.
Peak current: 4 x
AERO-40A
and 3 x
LX-218CA-NET
--> 64A + 60A peak = 124A Peak, each
circuit breaker can stand 5In < I < 10In, that is to say between 80A< I < 160A.
230V DASNET-RACK: maximum number of cabinets - 12 AERO-40A + 9 LX-218CA-NET
Manual del Usuario
/ DASnet Splitter /
User’s Manual