IWR-5 Wireless Pressure & Temperature Receiver - Operating Manual
Page 4 IWR-5 Iss2.1
Dipswitch Configuration
The 8 way Dipswitch 1 is used to configure the basic functionality of the IWR-5
The RF network code must be the same as the IWPT units to be used with the receiver
unit.
Switches 1, 2, 3 & 4 select the network code as below
RF NETWORK
1 2 3 4
1
0 0 0 0
2
0 0 0 1
3
0 0 1 0
4
0 0 1 1
5
0 1 0 0
6
0 1 0 1
7
0 1 1 0
8
0 1 1 1
9
1 0 0 0
10
1 0 0 1
11
1 0 1 0
12
1 0 1 1
13
1 1 0 0
14
1 1 0 1
15
1 1 1 0
16
1 1 1 1
Switch 5 and 6 select the number of transmissions which are missed before the Alarm
relay output switches to the alarm condition.
Missed Transmissions 5 6
4
0 0
2
0 1
6
1 0
No Alarm 1 1
Switch 7 and 8 Configure the action of the Alarm Relay output. This can also be
configured to exact alarm values using the USB port and the IWR-Set software.
Relay Action
7 8
Relay 1 switches OFF any I/P above 50%
0 0
Relay 1 switches OFF any I/P above 75%
0 1
Relay 1 switches OFF any I/P above 25%
1 0
Relay 1 Configured via USB & IWR-Set software 1 1