background image

 

CAUTION! 

A battery can present a high risk of short circuit current and electrical shock. Take 

the following precautions before replacing the battery: 
1. Remove all watches, rings or other metal objects. 
2. Only use tools with insulated handles. 
3. 

DO NOT 

lay tools or other metal parts on top of battery or any battery terminals. 

4.

 

Disconnect the charging source prior to connecting or disconnecting battery terminals. 

5. Wear rubber gloves and boots. 
6. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source 
of ground. 

CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL 

SHOCK! 

The likelihood of such shock will be reduced if such grounds are removed during 

installation and maintenance (applicable to a UPS and a remote battery supply not having a 
grounded circuit) 

 

CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF 
USED BATTERIES ACCORDING TO THE INSTRUCTIONS.

 

 

BATTERY REPLACEMENT PROCEDURE: 

Turn off and unplug all connected equipment. 
2. 

Turn the UPS off and unplug it from the AC power source. 

3. 

Remove the front panel of the UPS. 

4. 

Remove two screws from the battery compartment cover and slide the cover completely off of     

            the unit. 
5. 

Remove the batteries from the compartment. 

6. 

Disconnect the battery wires from the batteries. 

7. 

Install the replace batteries by connecting the red wire (+) and black wire (-) to the same color   

            connectors from the battery pack. 
8. 

Put the batteries back into the compartment. 

9. 

Re-install the battery compartment cover and tighten the retaining screws. 

10. 

Put the front panel back on the UPS. 

11. 

Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge. 

 
 

REMINDER: 

Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Almost any 

retailer that sells lead-acid batteries collects used batteries for recycling.

   

 

DEFINITIONS FOR ILLUMINATED LCD INDICATORS

 

 
1. 

ONLINE: The UPS is supplying utility power to 

connected equipment.   
2. 

BATTERY: During a severe brownout or blackout, 

this icon appears and an alarm sounds (two short beeps 
followed by a pause) to indicate the UPS is operating 
from its internal batteries. During a prolonged brownout 
or blackout, the alarm will beep rapidly every 1/2 second 
(and the BATT.CAPACITY meter shows one 20% 
capacity segment shaded. The capacity depends on how 
much load added and the runtime left.) to indicate the 
UPS’s batteries are nearly out of power. You should save 
files and turn off your equipment immediately or allow the 
software to shut the system down. 
3. 

Energy-Saving: The UPS in energy-saving bypass mode. When the utility power is normal and the 

battery is fully charged, the UPS will go into energy-saving bypass mode automatically. See “CyberPower 
GreenPower UPSTM Technology” section for more information. 
4. 

LOAD capacity / Sensitivity setup: This meter displays the approximate output load level (in 20% 

increments) of the UPS battery outlets. It can also be sensitivity setup meter if you are in Setup mode. It is to 
control the sensitivity of the UPS to switch to Battery Mode by selecting UPS shutdown voltage range. When 
the sensitivity is increased, the UPS will switch to Battery Mode with less input power variation. 
5. 

BATTERY capacity: This meter displays the approximate charge level (in 20% increments) of the 

UPS’s internal battery. During a blackout or severe brownout, the UPS switches to battery power, the 
BATTERY icon appears, and the charge level decreases. 
6. 

FAULT: This icon appears if there is a problem with the UPS. Press the POWER button to turn off the 

UPS. 
F01: Battery Mode or AC/Utility Power Mode Overload fault (Turn on the UPS again.) 
F02: Battery Output Short fault (Turn on the UPS again.) 
F03: Charger Fault (Contact CyberPower Systems for support.) 
F04: Internal Fault (Contact CyberPower Systems for support.) 
F05: Fan Abnormal (Contact CyberPower Systems for support.) 
7. 

OVER LOAD: This icon appears and an alarm sounds to indicate the battery-supplied outlets are 

overloaded. To clear the overload, unplug some of your equipment from the battery-supplied outlets until the 
icon turns off and the alarm stops. 
8. 

SCHEDULE: Users can setup the schedule to turn on and shut down the computer and UPS through 

PowerPanel® Personal Edition software. The LCD display will show how much time is left before the UPS 
will turn back on or shut down. 
9. 

ESTIMATED RUNTIME: This displays the run time estimate of the UPS with current battery capacity 

and load. 
10. 

OUTPUT meter: This meter measure, in real time, the AC voltage that the UPS system is providing to 

the computer, such as normal AC line mode, AVR mode, and battery backup mode. (Note: The OUTPUT 
meter shows the status of the battery backup outlets in terms of load, frequency, and voltage.) 
11. 

INPUT meter: This meter measures the AC voltage that the UPS system is receiving from the utility 

wall outlet. The UPS is designed, through the use of automatic voltage regulation, to continuously correct 
output voltage to connected equipment to a safe voltage output range. In the event of a complete power loss, 
severe brownout, or over-voltage, the UPS relies on its internal battery to supply consistent output voltage. 
The INPUT voltage meter can be used as a diagnostic tool to identify poor-quality input power. 
12. 

EVENT: This meter records the number of power outages. 

13. 

MUTE: This icon appears whenever the UPS is in silent mode. The alarm does not beep during silent 

mode until the battery reaches low capacity. 
14. 

AVR (Automatic Voltage Regulation): This icon appears whenever your UPS is automatically 

correcting low AC line voltage without using battery power. This is a normal, automatic operation of your 
UPS, and no action is required on your part. 
 

 
For more information about functions setup, please refer to the 

Function Setup Guide

 
 
 
 

      TECHNICAL SPECIFICATIONS 

 
 

Model 

 

PR2200ELCDSL

 

PR3000ELCDSL 

Capacity    (VA) 

2200VA/1980W 

3000VA/2700W 

Input 

 

Frequency Range 

50/60Hz +/-3 Hz (Auto Sensing) 

AVR Function 

Yes 

Output 

 

On Battery Output Voltage 

/-10% 

On Battery Output 
Frequency 

50/60Hz +/-1% 

Overload Protection 

On Utility: Circuit Breaker & Internal Current Protection 

On Battery: Internal Current Limiting 

Surge Protection 

 

Lightning / Surge 
Protection 

Yes 

Operating Temperature 

+32

°

F to 104

°

F ( 0

°

C to 40

°

C ) 

Physical 

 

Total # of UPS outlets 

IEC x 8 

IEC x 9 

Maximum 
Dimensions(LxWxH) 

221 x 170 x 432 mm 

Weight (kg) 

23.3 

24.5 

Battery 

 

Battery 

Sealed Maintenance Free Lead Acid Battery 

Typical Recharge Time 

8 hours 

Charging Current(Max.) 

1A 

User Replaceable 

Yes 

Status Indicators 

Indicators 

Power On, LCD Display, Online, On Battery, Fault, Replace Battery 

Audible Alarms 

On Battery, Low Battery, Overload 

Communication 

 

PowerPanel

®

 Business 

Edition Software 

Windows 8/7/Vista/XP/2000/Server 2003, Linux 

Management 

 

Self -Test 

Yes 

Auto-Charger 

Yes 

Auto-Restart 

Yes 

USB interface 

Yes 

Expansion Port 

Yes 

EPO Port 

Yes 

Certifications

 

Certifications 

CE, RCM 

 
 

      TROUBLESHOOTING 

 
 

Problem

 

Possible Cause 

Solution

 

Circuit breaker button is 
projecting from the back of the 
unit.

 

Circuit breaker has 
tripped due to an 
overload. 

Turn the UPS off and unplug at least one 
piece of equipment. Wait 10 seconds, reset 
the circuit breaker by depressing the button, 
and then turn the UPS on.

 

The UPS does not perform 
expected runtime. 

Battery not fully 
charged. 

Recharge the battery by leaving the UPS 
plugged in. 

Battery is slightly worn 
out. 

Contact CyberPower Systems about 
replacement batteries at 

[email protected]

 

The UPS will not turn on. 

The on/off switch is 
designed to prevent 
damage by rapidly 
turning it off and on. 

Turn the UPS off.    Wait 10 seconds and 
then turn the UPS on. 

The battery is worn 
out. 

Contact CyberPower Systems about 
replacement batteries at 

[email protected]

 

Mechanical problem. 

Contact CyberPower Systems at 

[email protected]

 

PowerPanel® Business Edition 
is inactive. 

The USB cable is not 
connected. 

Connect the USB cable to the UPS unit and 
an open serial port on the back of the 
computer. You must use the cable that 
came with the unit.

 

The unit is not 
providing 
battery power. 

Shutdown your computer and turn the 
UPS off. Wait 10 seconds and turn the 
UPS back on. This should reset the unit. 

The fault LED is illuminated. 

Overload 

Remove excessive load and restart the 
UPS. 

Output Short 

Contact CyberPower Systems at 

[email protected]

 

Battery Overcharge 

Contact CyberPower Systems at 

[email protected]

 

Over Temperature 

Contact CyberPower Systems at 

[email protected]

 

Additional troubleshooting information can be found at 

www.cpsww.com.au

 

 

For more information, visit 

www.cyberpower.com

 or contact 

Cyber Power Systems, Inc. 

 

All rights reserved. Reproduction without permission is prohibited. 

 

 

 

 

Reviews: