background image

 

 

1.

 

SAFETY 

This manual contains important instructions. Please read and follow all instructions 

carefully during installation and operation of the unit. Read this manual thoroughly 

before attempting to unpack, install, or operate the Battery module. 

 

CAUTION!   

The UPS unit must be connected to a grounded AC power outlet 

with  fuse  or  circuit  breaker  protection.  The  Battery  modules  grounded  are 

through the UPS.

 

 

CAUTION!   

The  battery  can  power  hazardous  components  inside  the  unit, 

even when the AC input power is disconnected.

 

 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a 

temperature  and  humidity  controlled  indoor  area,  free  of  conductive 

contaminants.  (Please  see  specifications  for  acceptable  temperature  and 

humidity range).

 

 

CAUTION!    (No  User  Serviceable  Parts):

  Risk  of  electric  shock,  do  not 

remove  cover.  No  user  serviceable  parts  inside.  Refer  servicing  to  qualified 

service personnel. 

 

CAUTION!    (Non-Isolated  Battery  Supply): 

Risk  of  electric  shock,  battery 

circuit  is  not  isolated  from  AC  power  source;  hazardous  voltage  may  exist 

between battery terminals and ground. Test before touching.

 

 

CAUTION!   

Wiring must be done by qualified personnel.

 

 

CAUTION!    DO  NOT  USE  WITH  OR  NEAR  AQUARIUMS! 

To  reduce  the 

risk  of  fire,  do  not  use  with  or  near  aquariums.    Condensation  from  the 

aquarium  can  come  in  contact  with  metal  electrical  contacts  and  cause  the 

machine to short out. 

 

CAUTION!   

Do not dispose of batteries in fire as the battery may explode. 

 

CAUTION!   

Do  not  open  or  mutilate  the  battery,  released  electrolyte  is 

harmful to the skin and eyes. 

 

CAUTION!   

A  battery  can  present  a  risk  of  electric  shock  and  high  short 

circuit current. The following precaution should be observed when working on 

batteries 

1.  Remove watches, rings or other metal objects. 

2.  Use tools with insulated handles. 

 

CAUTION!   

Make sure everything is turned off and disconnected completely 

Summary of Contents for BPSE240V75ART3U

Page 1: ...Userˊs Manual BPSE240V75ART3U BPSE240V75ART3UOA CyberPower Systems Inc www cyberpower com K01 C000117 02 ...

Page 2: ...4 2 VERTICAL TOWER INSTALLATION 8 5 ELECTRICAL INSTALLATION 10 5 1 One Battery module with 240Vdc input of the Power module 10 5 2 Multiple Battery modules with 240Vdc input of the Power module 11 5 3 Two Battery modules with 240Vdc input of the Power module 13 5 4 Multiple Battery modules with 240Vdc input of the Power module 13 6 TECHNICAL SPECIFICATION 14 ...

Page 3: ...r serviceable parts inside Refer servicing to qualified service personnel CAUTION Non Isolated Battery Supply Risk of electric shock battery circuit is not isolated from AC power source hazardous voltage may exist between battery terminals and ground Test before touching CAUTION Wiring must be done by qualified personnel CAUTION DO NOT USE WITH OR NEAR AQUARIUMS To reduce the risk of fire do not u...

Page 4: ...ctor before any other cables are connected DO NOT INSTALL THE UNIT WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES ...

Page 5: ...3 2 UNPACKING Battery module User s manual Rackmount left rail Rackmount right rail Rackmount ears Stands 2PCS Flat head screws M4X8L Pan head screws M5X12L Screw hole dust Plastic washers Battery Cable ...

Page 6: ...R PANEL DESCRIPTION Front View Rear View Fuse Replaceable fuse is accessible from the rear panel It must be done by qualified personnel Output Connector Use this output connector to connect the Battery module and the Power module Battery input Terminal Block Use this input Terminal Block to daisy chain the next Battery module ...

Page 7: ...ty is especially important to growing organizations with changing needs that value having the option to position a UPS on a floor or in a rackmount system Please follow the instructions below for the respective mounting methods 4 1 RACKMOUNT INSTALLATION Step1 Rackmount ears installation a Attach the two rackmount ears to the UPS using the provided screws M4X8L 8pcs b Insert dust cover into the ra...

Page 8: ...ion 9 b Attach the rackmount rail to your rack with two M5X12L screws and two plastic washers at the front of the rack Located in position 1 position 6 Do not tighten the screws Adjust the rail size on the rail assembly of your rack Secure the rail to the rear of the rack with two M5X12L screws and two plastic washers Tighten all screws at the front and rear of the rail Once completed perform the ...

Page 9: ...ace with the front of the unit facing toward you Secure the UPS to your rack with four M5X12L screws at the front of the rack Located in position 2 position 8 b Once completed perform the same steps for Power module CAUTION The Battery module must be installed below the UPS ...

Page 10: ...ION Attach the base stands 1 Without Power module a Tighten the screws M5X12 4pcs of the base stands rackmount ears onto the bottom of the Battery module b Insert dust cover into the rackmount ear screw holes that are not being used ...

Page 11: ... stands 2 With Power module a Tighten the screws M5X12 4pcs of the base stands rackmount ears onto the bottom of the UPS and Battery module b Insert dust cover into the rackmount ear screw holes that are not being used ...

Page 12: ...afety regulations 5 1 One Battery module with 240Vdc input of the Power module a Loosen the screws to remove the Terminal Block Cover located on the rear panel of Power module b Connect the Battery Cable to the Power module and ensure the polarity is right c Loosen the screws to remove the Output Connector Cover of Battery module ...

Page 13: ...le Battery modules with 240Vdc input of the Power module a Loosen the screws to remove the Battery input Terminal Block Cover and Output Connector Cover of the 1 Battery module b Connect Battery Cable to Battery input Terminal Block of the 1 Battery module and ensure the polarity is right 1 Battery module ...

Page 14: ...tput Connector Cover of the 2 Battery module d Connect the 1 Battery module to the 2 Battery module e Connect the 1 Battery module to Power module Refer to above steps of chapter 5 1 Once completed retighten the Block Cover 2 Battery module ...

Page 15: ...le Battery modules with 240Vdc input of the Power module Please refer to the following diagram and the steps of Connection 2 Power module Battery Input 240Vdc 4 Battery module Input Terminal Block N N 1 Battery module Output Connector 1 Battery module Input Terminal Block 3 Battery module Output Connector 3 Battery module Input Terminal Block 2 Battery module Output Connector 2 Battery module Inpu...

Page 16: ...680 Weight kg 55 66 Environment Operating Temperature 0 C to 40 C Relative Humidity 0 to 90 Non condensing CyberPower Systems Inc www cyberpower com 6F No 32 Sec 1 Chenggong Rd Nangang District Taipei 115 Taiwan Entire contents copyright 2013 CyberPower Systems Inc All rights reserved Reproduction in whole or in part without permission is prohibited PowerPanel Business Edition and PowerPanel Perso...