Back
Used for system programming. Refer to programming section.
Up, Down, Left, Right (cursor movement)
Used for system programming. Refer to programming section.
4 Soft arrow keys use display for various functions
Perform functions shown on the LCD above the buttons TBD.
4 programmable site specific buttons
These buttons can be programmed to perform various functions such as tandem smoke reset,
elevator reset, HVAC reset etc. Custom labels can be provided. Refer to the programming section or
consult the factory for information.
figure 1
4.2 Modes of Operation
4.2.1 Normal
Normal mode exists when no off normal conditions are occurring in the installation. The LCD screen
shown in figure 8 will be present during normal mode. When in normal mode the CP-3000 is
monitoring system voltages, keypad inputs, etc. as well as monitoring for any off normal alarms,
supervisory or trouble signals. Transmitter polling signals are also logged during normal operation.
4.2.2 Alarm
Alarms can be generated by any of the compatible initiating devices listed in this manual. Upon
reception of an alarm signal from an initiating device the following will occur:
1. Any lower priority conditions currently displayed on the LCD will be replaced by the higher
level alarm. The lower priority condition will be redisplayed when the higher one is reset.
2. The sounder will emit a steady tone.
3. The Fire Alarm LED will flash once a second.
4. The corresponding alarm relay (1,2,3 or 4) will activate.