background image

Powering Device 

Power Input: 

110 - 240 V AC 50/60Hz *

Fuse Protection - Internal: 

1A load, T/SLO-BLO, VDE/UL rated

Electrical Safety Class: 

EU Safety Class II if installed in  

 

an appropriate mounting box

Terminals: 

Screw terminals

 

Wire size: 30-12 AWG (0.05-3 mm

2

)

 

(solid or stranded wire with sleeve)

Terminal Assignment: 

See wiring diagrams and  

 

information printed on unit. If  

 

incorrectly connected there is a risk  

 

of failure, malfunction or destruction. 

* In case of 277V usage step down transformer needed. Please find the compatible 

type in table below. Usage of other step down transformer is possible. Please contact 

your local support for more information.

Technical Data

System Components

Key Functions 

Type: 

Lightsweep™ Digital Controller

Product Code: 

LL-DC

SKU: 

93037756

Dimensions: 

W x L x H: 213 x 90 x 58 mm

Weight: 

400 grams

Housing: 

DIN (EN50022) rail mounted, M12

Warranty: 

5 years

Operating Conditions 

Operating Temperature: 

0°C - 45°C

Relative Humidity: 

90%, non-condensing

IP Rating: 

20

Compatible Step Down Transformer 

 

     Hatch Lighting 

LS120-75EN-277

MANUFACTURER

TyPE

Product Availability 

 

93037756  LightSweep™ Digital Controller 

LL-DC

SKU

DESCRIPTION

ARTICLE

NO.

Product  

Certifications 

E486320

Interfaces 

Digital Interface: 

Two independent digital  

   

communication and power supply  

   

interface. The power supply is  

   

feeding 18,5V/175mA DC, +/-10%,  

   

it has electrical current limitation  

   

and protection against overheating  

   

and overvoltage. DALI 2.0 devices  

   

can be connected, please contact  

   

your local support for compatible  

   

device’s list.

Relay Outputs: 

4 outputs as Solid state dry contacts,  

   

24-240V AC or DC nominal load,  

   

400V/50mA peak, galvanically  

   

separated contacts 

   

(VISO= max. 4.5 kV between contacts)

Input Interface: 

4-channel Max. 25VDC

Data Interface: 

1 Ethernet connector: RJ45, 10Mbit/s  

   

full duplex

Data Cable Routes: 

CAT5 and higher grade, max. 100  

   

meter cable length

Controller Network: 

Up to 10 Lightsweep Digital Controller  

   

can form a network

Lightsweep

TM

Digital

local network

Lightsweep

TM

 Digital

network

Lightsweep

TM

 Digital

network

Lightsweep

TM

Digital

Multisensor

Lightsweep

TM

Digital
Switch

Interface

Lightsweep

TM

Digital
Switch

Interface

Lightsweep

TM

Digital

Multisensor

Luminaires

Luminaires

Mobile

device

LAN

LAN

Lightsweep

 Digital system components: 

SKU 

DESCRIPTION 

ARTICLE NO.

93037756 Lightsweep

 Digital Controller 

LL-DC

93045357 Lightsweep

 Digital Multisensor Recessed 

LL-DMS2-CR

93037758 Lightsweep

 Digital Multisensor Surface Mounted 

LL-DMS2-CS

93037759 Lightsweep

 Digital Switch Interface for up to 3 buttons  LL-DSW-PB3

93037760 Lightsweep

 Digital Switch Interface for up to 9 buttons  LL-DSW-PB9

Summary of Contents for Lightsweep

Page 1: ...s en veiligheidsinformatie kan op de volgende locatie worden gevonden ET Eestikeelse paigaldusjuhendi ja ohutusn uded leiate aadressilt EN The English version of the installation instruction and safet...

Page 2: ...tal Interface Two independent digital communication and power supply interface The power supply is feeding 18 5V 175mA DC 10 it has electrical current limitation and protection against overheating and...

Page 3: ...pendently Mounted Control for panel mounting Type of action and additional features Type 1 Control Pollution Degree 2 Software Class and Structure Class A Rated Impulse Voltage 2500 Marking Definition...

Page 4: ...amps start dimming up and down on the bus until another short press is performed or 5 minute timer is expired Meanwhile DIGITAL A B LED is blinking purple Strip wires as shown on illustration Mains 11...

Page 5: ...eparation of circuits Warning the wiring shall be installed in accordance with National Electric Code and local codes rules the power wiring must be separated accordingly from the class 2 signal wirin...

Page 6: ...software configuration impact PB1 long press min 10 seconds reset all Digital devices control gears other devices to reset value on Bus A PB2 long press min 10 seconds reset all Digital devices contro...

Page 7: ...gn or typical values when measured under laboratory conditions Current powered by GE is a business of the General Electric Company 2018 GE www currentbyge com CTRL020 Rev 09 05 18 Legal Disclaimer For...

Reviews: