background image

9

M898-3_GB_letter

NEB 6500 and NEB 6500 R

4.3  Electrical connections

Installation provides for the utilization of an ON/OFF 

humidistat that controls starting and switching off the 

humidifier: it is, however, possible to use a simple ON/OFF 

contact; the only difference is that the machine must be 

started and stopped manually. This choice however does not 

in any way influence the installation procedure described 

below.

Installation must provide a separator switch for the ap-

pliance on the electric power supply, as shown in Pic. 12. 

Installation of a 2.5 amp slow blow fuse is necessary for 

the start-up of the motor.

4.3.1  Wiring diagram

Pic. 12 - Wiring diagram

1. External humidistat (not supplied).

2. Floating device.

3. Electric motor.

4. Solenoid valve.

5. Heating resistance (only on 6500 R)

6. Temperature probe

7. Electronic board

8. Line protection (not supplied)

4.3.2  Cabling

The flexible lead that is used for the electric connections, 

must be at least protected by an ordinary PVC sheath 

and respect 227 IEC 53 standards (CENELEC H05VV-F or 

H05VVH2-F or better)

With reference to Pic. 13:

 

»

Remove the cover of the external junction box by un-

screwing the four screws. In the box there are two cable 

clamps that will be used to pass the power cable 

P

 and 

the humidistat cable 

H

.

 

»

Pass the power cable through the cable clamp 

P

.

 

»

Fasten the neutral and phase (live) wires to the terminals 

L

 and 

W

 and the ground wire to the ground terminal.

Pic. 13 - External junction box opened.

 

»

Pass the cable of the humidistat through the cable gland 

H

 and connect the two wires to the 

H-H

 terminals. The 

cable holder is fitted with a special plug that is suggested 

to keep safe for an eventual future use.

 

»

Close the junction box.

Do NOT apply any voltage to the H-H contacts. The elec-

tronic board checks the status OPENED or CLOSED of the 

H-H contacts to start and stop the humidifier.

4.4  Hydraulic connections

The installation of the humidifier also needs the water 

supply and drainage pipes connected. The pipes supplied 

must be connected to the machine as explained in par. “3.2 

Preliminary operations”.

Pic. 14 - Hydraulic connections

The supply pipe 

A

 supplied has a threaded bushing G3/4 at 

both ends: connect the free end (the straight one) directly 

Summary of Contents for F3025

Page 1: ...F3025 NEB 6500 F3026 NEB 6500 R READ AND SAVE THESE INSTRUCTIONS Adiabatic humidifier ...

Page 2: ...F3025 NEB 6500 ...

Page 3: ...F3026 NEB 6500 R ...

Page 4: ...g diagram 9 4 3 2 Cabling 9 4 4 Hydraulic connections 9 4 5 Final operations 10 5 Operation Control 10 5 1 Preliminary checking 10 5 2 Starting 10 5 3 Stopping 10 6 Electronic control 10 6 1 The electronic board 10 6 1 1 Dip switches 11 6 2 Adjusting the humidification capacity 11 6 3 The washing reset cycle 11 7 Maintenance 12 7 1 Cleaning the air filter 12 7 2 Drain siphon 12 7 3 Feeding solenoi...

Page 5: ...nce only 6500 R 8 Internal junction box Tab 3 Main components 2 Introduction The NEB 6500 is an air humidifier and operates on the principle of water atomizing by centrifugation The ma chine must be fed with tap or demineralized water The NEB 6500 operation is controlled by a circuit board that runs the normal machine operations and also the reg ular automatic washing cycles of the supply tank to ...

Page 6: ...e machine Check that all the materials listed below are in the pack before starting work N 1 humidifier mod NEB 6500 or NEB 6500 R N 1 installation manual N 4 expansion plug with screws N 1 brackets for wall mounting N 3 brackets for hanging installation N 1 screw M6 20 EX6 with washer N 1 Water supply pipe 59 long with connectors G3 4 N 1 water drain pipe 59 long and 0 39 i d N 2 cable ties 3 2 P...

Page 7: ... screws with screw anchors supplied with it The bracket can be used as a template to mark the holes on the wall Respect the distances as indicated in par 4 Position ing and make sure that the bracket is level before drilling the holes Pic 6 Wall mounting bracket Make sure that the wall can support the machine under operating conditions and that the screws are the right ones for that type of wall D...

Page 8: ...etal chains preferably steel chains chain material should not be affected by humidity Respect the minimum distances indicated in Pic 5 Disassemble the rear bracket A for wall installation as shown in Pic 10 by unscrewing the four screws V Then remove the screw S that fixes the external junction box Pic 10 Wall mounting bracket removal Now five 5 screws should be available 4 screws removed from the...

Page 9: ...standards CENELEC H05VV F or H05VVH2 F or better With reference to Pic 13 Remove the cover of the external junction box by un screwing the four screws In the box there are two cable clamps that will be used to pass the power cable P and the humidistat cable H Pass the power cable through the cable clamp P Fasten the neutral and phase live wires to the terminals L and W and the ground wire to the g...

Page 10: ... The distribution inlets are correctly positioned WARNING prolonged use of the machine without water supply can seriously damage the solenoid valve 5 2 Starting To start the humidifier turn on the main switch The machine will perform a washing cycle lasting about one minute as described in detail in par 6 3 The washing reset cycle At the end of the cycle if the humidistat contact is closed the hum...

Page 11: ...le each time The machine is started with the main switch The humidistat closes the H H contacts because the necessary R H conditions have been reached The scope of this cycle is to prevent water depositing in the machine when it is not in operation in this way preventing the proliferation of bacteria The cycle has a fixed duration and consists in Exclusion of the motor and a 40 second waiting peri...

Page 12: ...ing the three screws hold ing it Separate the two plastic grids A from the filter material B Clean the filter B with a vacuum cleaner or immerse it in slightly soapy water and rinse dry without wringing Filter MUST BE COMPLETELY DRY before reinstalla tion ATTENTION never enable the humidifier without the air filter fitted The air filter is composed of three pieces that must be assembled in such a ...

Page 13: ...hine in an environment with a tempera ture range between 14 F and 140 F When the machine is still packed keep it upright Do not put any other heavy things on the box 8 1 Points to check before and after a long period of inactivity 8 1 1 Before Disconnect the electric connections and close the supply water ON OFF taps Cover the machine to protect it from the dust 8 1 2 After Check the state of the ...

Page 14: ...14 M898 3_GB_letter NEB 6500 and NEB 6500 R Notes ...

Page 15: ...15 M898 3_GB_letter NEB 6500 and NEB 6500 R Notes ...

Page 16: ...CUOGHI LLC 135 Brandywine blvd suite A Fayetteville GA 30214 info cuoghillc com www cuoghillc com ...

Reviews: