Cumberland Alert Alarm III Owner'S Manual Download Page 6

 

Part No. 4801-1201 Rev. 1-20 

Alert Alarm III 

4

 

5.2  Power Out 

The Power Out alarm can occur in two cases.  One is when the power has been out for more that one 
minute.  The other situation could be caused by the 120VAC 2 amp fuse located at the bottom, back 
of the box, being blown.  If the power out alarm condition is active, and you find that there is power 
present at the outlet where the alarm is plugged in, then you should check the fuses.  Note that both 
fuses are 2 amp. 

5.3  No Siren at Test 

If the siren fails to sound when the test button is pressed, several scenarios could be present.  First, 
the battery fuse could be blown.  Note that both fuses at the bottom of the box are 2 amp.  Secondly, 
the battery could be disconnected or depleted.  Third, the siren itself could be bad.  Check for 
12VDC at the siren leads themselves.  And, of course, there could be a bad connection somewhere 
in the siren circuit. 

5.4  Temperature Sensors Out of Calibration 

If the operator feels that the temperature sensors are not correct, he should follow these steps: 
Remove the Upper and/or Lower limit setpoint knobs by loosening their set screws.  Next, turn the 
Lower limit shaft counter clockwise until it stops.  Now, turn the Upper limit shaft clockwise until it 
stops--there should be no sensor lights lit.  Next, turn the Upper limit shaft until the sensor indicators 
are lighted--at this point, you should replace the Upper limit knob with the white indicator arrow 
pointing to the correct temperature and tighten it down.  Follow the same steps to set the Lower limit 
setpoint. 

5.5  Trouble-Shooting the Auxiliaries 

The auxiliary inputs must always form a closed loop.  If the loop is ever open, the alarm will sound.  
If an auxiliary input is sounding, the trouble can be isolated between the alarm and the circuit by 
disconnecting the circuit from the terminal block in the alarm box and replacing it with a jumper.  If 
the corresponding auxiliary input still causes an alarm condition, the problem is the alarm, otherwise 
the circuit is the culprit. 

6.  Installation 

6.1  Mount the Box 

The box should be mounted in a location where it will be protected from damage.  The enclosure is 
waterproof and should be mounted using the mounting kit supplied with the controller.  Holes drilled 
through the box allow a path for moisture, dust, and ammonia and will void your warranty. 

6.2  Installing Sensors 

After determining the location of the sensors, they should be attached to the walls, and/or ceiling of 
the confinement building.  Next, run the two wires into the enclosure via the watertight connector at 
the bottom of the box.  The wires should be cut off and a spade terminal crimped to their ends.  They 
next should be attached to the terminal block in the positions marked Sen 1 and Sen 2. Note that the 
sensors are not polarity sensitive, and it therefore makes no difference as to which wire goes to 
which sensor terminal. 

6.3  Attaching the Siren 

After the siren is mounted, it should be wired into the control box.  This is done at the terminal 
block locations labeled 

siren red

 and 

siren white

.  Note that polarity is important here and that the 

red siren wire must be connected into the 

siren red

 terminal block position and the same for the 

white wire. Note also, any 12VDC device which uses less that 1 amp of current could be connected 
in the siren’s place. 

Summary of Contents for Alert Alarm III

Page 1: ...4801 1201 Rev 1 20 Owners Manual Alert Alarm III CUMBERLAND Assumption IL 62510 Phone 217 226 4421 Fax 217 226 4420 CUMBERLAND Alert Alarm III Owners Manual Cumberland 1004 E Illinois St Assumption I...

Page 2: ...Sensors 2 4 8 Power Out 3 4 9 Battery Low 3 4 10 Auxiliary Inputs 3 4 11 Recommendations 3 5 Trouble Shooting Your Alarm 3 5 1 Battery Low 3 5 2 Power Out 4 5 3 No Siren at Test 4 5 4 Temperature Sen...

Page 3: ...setting the high and low alarm temperatures while a front panel display contains status indicators and test functions 2 Ratings and Specifications Power Supply 120VAC or 240VAC 50 60 HZ Temperature R...

Page 4: ...ill not charge when the Power switch is OFF 4 6 Test The test button provides a means of verifying the operational status of the siren It is recommended that the operator press the test button for abo...

Page 5: ...se inputs For instance water pressure switches light meters and thermostats could all be used In the future Cumberland will offer several options for these inputs Section 8 shows how the Farm Hand fam...

Page 6: ...le Shooting the Auxiliaries The auxiliary inputs must always form a closed loop If the loop is ever open the alarm will sound If an auxiliary input is sounding the trouble can be isolated between the...

Page 7: ...to monitor areas that utilize separate power systems relays should be used to inform the controller of a power outage This could be accomplished via an auxiliary system and relays or by serializing r...

Page 8: ...Part No 4801 1201 Rev 1 20 Alert Alarm III 6 7 Schematic Diagram...

Page 9: ...ackup ventilation or accept the risk of such loss or injury WARNING ADVERTENCIA Cuando este controlse utilize en sistemas de ventilacion y calefaccion para seres vivientes donde una falla pueda causar...

Page 10: ...5 8 12 493 68 20 6 836 93 33 9 24 055 43 6 1 12 325 68 5 20 3 6 779 93 4 34 1 23 82 43 3 6 3 12 215 68 9 20 5 6 695 93 9 34 4 23 472 43 9 6 6 12 051 69 4 20 8 6 612 94 5 34 7 23 13 44 4 6 9 11 943 69...

Page 11: ...warranted parts and equipment and does not cover labor charges for removing or installing defective parts shipping charges with respect to such parts any applicable sales or other taxes or any other c...

Reviews: