Controlling Instructions

1 Working Mode

Manual Mode: The user can adjusts the fan speed switch manually (high, middle and low);

Intelligent Mode: According to the setting value of PM2.5 or CO2, it can switch the fan speed automatically.

Mute Mode: Operation at low speed;

Periods Mode: The user can set different fan speed in four periods within 24 hours (00: 00 ~ 06: 00, 06: 00 ~
12: 00, 12: 00 ~ 18: 00, 18: 00 ~ 24: 00)

2 Key’s Function

Power-on Key(long press for 2s);

Fan speed key, switch the fan speed(high, medium, low), the default is low speed when power on;

Confirmation key (use in confirm operating or standby mode setting);

Function key (adjust the fresh air and exhaust air). There are three status: “exhaust air”, “fresh air”, and

“fresh air + exhaust air”; Default is “fresh air + exhaust air”

Mode key (WIFI key also). There are four modes: manual, intelligent, mute, and periods. Default is

manual mode. Long press till the buzzer off then is WIFI status.

3 Operation Instructions

1 Switch on and off: press and hold the

for 2s to turn on or off. When it’s the switch off status, all readings

and output will off.

2 Switch the operating mode: Press the

to change the operating mode. The working mode is cyclically

switched in the four states of "periods-intelligent-manual-mute". After the mode setting is completed, press the

the screen returns to the data detection interface.

3 Time period mode: Press the operating mode key and the confirmation key, the user can set the fan speed by

for 4 time periods per day (00: 00 ~ 06: 00, 06: 00 ~ 12: 00, 12: 00 ~ 18: 00, 18: 00 ~ 24:00).

Note

This time period used for setting fan speed

For example

Setting

Monday

00:00

Low

06:00

Medium

12:00

High

18:00

Low

By this logic, the fan speed be set to low speed from 00:00 to 06:00; and it be set to medium speed from 06:00

to 12:00, high speed from 12:00 to 18:00.

Summary of Contents for AM6108B

Page 1: ...Writer Audit Approved Mei Yang Product Name Indoor Air Quality Controller Item No AM6108B Version V0 3 Date 2019 10 12 SPECIFICATION ...

Page 2: ...sion Content Reviser Date 1 V0 1 First edition Mei Yang 2019 5 10 2 V0 2 Add product communication protocol Mei Yang 2019 8 13 2 V0 3 1 Standby current change to 90mA 2 Add the WIFI connection mode 3 Update the UI key icon Mei Yang 2019 10 12 ...

Page 3: ...mpatible with push button and touch screen operation Using standard 86 box size thickness 24mm PM2 5 CO2 RH T etc multiple sensors can be optionally selected With fresh air control function three level speed of wind can be adjusted four working modes intelligent manual mute and periods Customizable filter alert function The built in dust sensor uses the principle of laser scattering technology to ...

Page 4: ...ment TSI 8530 25 2 50 10 RH CO2 Measurement accuracy 50ppm 5 of reading 0 50 Temperature Measurement accuracy 1 Humidity Measurement accuracy 8 RH PM Response time T90 8s CO2 Response time T90 120s Working condition 10 50 0 95 RH Non condensing Storage condition 20 60 0 95 RH Non condensing Working voltage DC 12V Working current 140mA Standby current 90mA Signal Output RS485 Installation hole dist...

Page 5: ... 11 Dimensions and Interface Definition 1 Dimensions Unit mm tolerance 0 2 mm 2 Pin definition No Pin Description 1 TA Communication port RS485_TA 2 TB Communication port RS485_TB 3 12V Power input 12V 4 GND Power input GND ...

Page 6: ...assensor com cn 5 11 UI Interface Description Parameter Range corresponding to color LIST Gas Level Range Color PM2 5 μg m Good 0 75 Just so so 75 115 Bad 115 CO2 ppm Good 0 600 Just so so 600 1000 Bad 1000 ...

Page 7: ...lso There are four modes manual intelligent mute and periods Default is manual mode Long press till the buzzer off then is WIFI status 3 Operation Instructions 1 Switch on and off press and hold the for 2s to turn on or off When it s the switch off status all readings and output will off 2 Switch the operating mode Press the to change the operating mode The working mode is cyclically switched in t...

Page 8: ...5 Manual mode The fan speed switched by the user Despite the time period and air quality The fan speed can be adjusted by the The adjustment range is low medium high 6 Mute mode The fan runs at low speed and cannot switch the fan speed manually under this mode and it s not affected by air quality 7 Function setting Press the to cycle the HVAC system through the three states of exhaust air fresh ai...

Page 9: ... as shown below Step 2 Connecting Cable connect the corresponding cable to the controller s RS485 interface according to the interface definition as shown below Step 3 Match the two holes in the controller with the hooks in the wall mount bracket and slide the controller down to ensure that the controller is tightly locked with the bracket ...

Page 10: ...not drop the controller or rub it against hard objects during use otherwise it may cause damage to the controller s external light and damage Do not place the controller in a dusty environment to avoid dust accumulation in the controller and affect the measurement accuracy When using the controller do not cover or block the vent hole with any object to avoid affecting the air quality monitoring Do...

Page 11: ...rmat Description Start Symbol Sending by controller is fixed as 11H Length Length of frame bytes data length 2 including CMD IP DATA Command Command is fixed as 55H Address Controller address is 1 254 default is 01H Data Data of writing or reading length is not fixed Check Sum Cumulative sum of data 256 HEAD LEN CMD IP DATA The system s default slave device address is 01H the controller command is...

Page 12: ... Temperature DF8 DF9 0 600 Corresponding value 100 10 C 10 0 50 0 one decimal place is reserved Indoor Humidity DF10 0 95 0 95 Indoor HCHO Concentration DF11 DF12 Reserved Indoor VOC lever DF13 DF14 DF4 0x01 VOC L1 DF4 0x02 VOC L2 DF4 0x03 VOC L3 1 3 Error code DF15 DF16 Reserved Reserved DF17 DF18 Reserved DF19 DF20 CheckSum CS After Sales Services and Consultancy Cubic Sensor and Instrument Co L...

Reviews: