CTI SD2-NH3 Installation And Operation Manual Download Page 4

4

SD2-NH3

Installation

General Description

The SD2-NH3 is a single-point sample-draw ammonia sensor.  This design 

helps the sensor survive in continuous-exposure applications where other 

diffusion-type electrochemical sensors simply fail and die.
This ammonia sensor utilizes proven electrochemical sensor technology for 

accuracy. It is designed with special pump/valve sequencing to refresh the 

cell with clean air to prevent ammonia saturation and extend the cell life.   

An automatic reverse purge routine also helps self-clean the micron filter.  

The SD2-NH3 has a 10-minute sampling rate, and the sample-draw cycle is 

as follows:

2-minute sample time from the room being monitored.  At the end of the 

two minutes, the sample data is stored and held for the next 10 minutes 

also while being transmitted via 4-20 mA output to the controller or PLC.

2-minute fresh air purge from outside fresh air source.
6-minute pump shut-off phase.

The standard detection range (0-50 ppm) of the SD2-NH3 sensor provides 

monitoring of ammonia concentrations accurately down to 5 ppm without 

false alarms. 

The SD2-NH3 sensor provides an industrial standard linear 4/20 mA output 

signal compatible with most gas detection systems and PLCs. The output 

signal is not affected by drastic temperature and moisture variations.

All circuit boards are sealed in potting compound, protecting sensitive 

electronic components and copper tracing from corrosion.
An external fresh-air sample tube and hardware are included with the SD2-

NH3.  Tube length provided is five feet.

Locating the SD2-NH3

An important consideration when installing the SD2-NH3 is that it must be 

easily accessible for occasional maintenance, and protected from physical 

damage. 

The sample air port should be mounted on the inside of the CA room and 

penetrate through the CA room wall.  The SD2-NH3 detector will connect to 

it on the other side of the wall (see 

Figure 1

 on next page).

The fresh air port is located on the bottom the SD2-NH3 enclosure. This will 

be the source of fresh air necessary for proper monitoring and longer cell 

life.
The SD2-NH3 sensor can adequately monitor 1,200 sq feet.

Installation Guidelines:

• 

Do not mount sample air port any farther then the supplied tubing and 

hardware allows.

• 

Mount sensor on a solid surface with minimal vibration.

• 

Mount sensor thru the holes in the mounting flanges of the enclosure. 

•  Mount sensor in a general-purpose location only. Do not install in a 

hazardous environment.

• 

Mount sensor away from electromagnetic interference.

•  Always mount sensor vertically with the sampling port at the bottom.
•  Take air movement and ventilation patterns into account.
• 

Keep sensor and wire runs away from mercury vapor lights, variable 

speed drives, and radio repeaters to prevent electrical interference.

• 

More than one sensor should be installed for highly critical locations.

Summary of Contents for SD2-NH3

Page 1: ...Installation and Operation Manual SD2 NH3 SAMPLE DRAW AMMONIA SENSOR FOR CONTROLLED ATMOSPHERE ROOMS...

Page 2: ...nly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Page 3: ...wy Columbia MO 65201 phone 866 394 5861 email sales ctiengineeing com website ctiengineering com General description 4 Installation 4 Locating the SD1 NH3 4 Installation guidelines 4 Fresh air port in...

Page 4: ...sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion An external fresh air sample tube and hardware are included with the SD2 NH3 Tube length provide...

Page 5: ...conduit to the conduit body A 5 Attach the conduit body A to the sample air inlet port B at the bottom of the sensor enclosure 6 Take the finished subassembly and line up the 1 2 conduit with the 1 2...

Page 6: ...ays use 3 conductor insulated stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all spl...

Page 7: ...out after 4 minutes Zero Calibration After the sensor is installed and has been powered up for a minimum of 8 hours the unit can be zero calibrated by the following Note Place bottom back board in ca...

Page 8: ...eady to Indicate Power Blinks once per second for 60 seconds during power up Blinks once per second continuously if supply voltage is too low Figure 3 Zero adjustment Bottom back board Status amber LE...

Page 9: ...CTI All calibrations should be logged During every calibration interval disassemble the inlet filters and clean with compressed air Always disconnect power at the controller before performing any wiri...

Page 10: ...ft Application dependent but generally less than 3 per month Linearity 0 5 of full scale Repeatability 1 of full scale Wiring Connections 3 conductor shielded stranded 18 AWG cable General Cable C2535...

Page 11: ...uct by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper storage in...

Page 12: ...ctiengineering com 866 394 5861 SD2 NH3 DOC1 2 20200923...