GG-VL2-NH3

Span Calibration: 

Do not adjust the span pot 

without certified calibration gas! If span adjustment is 

required, use the following procedure (see Figure 3):
•  Unscrew calibration port cover and connect cal gas 

hose to hose barb fitting

•  Press the CAL switch once to enter cal mode. 
•  Apply 1% NH3 span gas at 0.5 to 0.8 L/min (span 

gas must be in air, not nitrogen or other carrier).

•  Sensor should react to gas within 15 seconds.
•  Once the output signal has peaked (or 2 minutes 

maximum) adjust the span pot until the correct 

output is achieved (200 mVdc).

• 

Shut-off gas, remove hose and replace cover.

•  Press the CAL switch to exit cal mode.
•  Calibration is now complete.

Note: Allow up to an hour for the signal to return back 

to 4 mA after exposure to high concentrations. 
Note: If correct output during span adjustment is 

unachievable, replace the sensor element. See sensor 

replacement procedure on page 10 if a replacement 

sensor element is needed.
Note: Gas exposures well above the 0-1% NH3 range 

of the sensor can shorten the life of the sensor 

element, and typically results in a "zero signal shift", 

where the signal is stuck at full-scale levels. Make sure 

no ammonia gas is present and simply re-zero the 

sensor following the 

Zero Calibration

 procedure on 

the previous page.

4mA adjustment: 

Sometimes a fine adjustment of the 

4mA signal may be desired to compensate for a slight 

positive or negative zero-signal reading on the control 

panel.
•  Make sure the sensor is NOT in calibration mode.
•  Adjust the 4mA pot until the control panel reads 

zero.

Summary of Contents for GG-VL2-NH3

Page 1: ...Installation and Operation Manual GG VL2 NH3 AMMONIA VENT LINE SENSOR...

Page 2: ...only in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment shoul...

Page 3: ...nstallation guidelines 5 Wiring 6 Operation 7 Start up 7 Calibration 7 Maintenance 10 Troubleshooting 11 Specifications 11 Warranty 12 For technical support contact Calibration Technologies 920 N Trad...

Page 4: ...r Note The nipple of the supplied mounting kit should be welded to the relief header to allow airflow to the sensor Note Removing the plug from the mounting kit usually allows more fresh air to the se...

Page 5: ...discharge path and have escape route planned Make sure ammonia does not discharge onto sensor assembly or personnel working on sensor i e mount sensor opposite side of discharge Install sensor enclosu...

Page 6: ...ring Guidelines Use only the existing conduit hole for connections to the sensor Always use three conductor insulated stranded shielded copper cable Do not pull sensor wiring with AC power cables This...

Page 7: ...down below approx 4 000 ppm NH3 This prevents the possibility of a low reading when the gas concentration exceeds the Upper Explosion Limit Calibration The GG VL2 NH3 sensor comes factory calibrated...

Page 8: ...low up to an hour for the signal to return back to 4 mA after exposure to high concentrations Note If correct output during span adjustment is unachievable replace the sensor element See sensor replac...

Page 9: ...NH3 Figure 3 Transmitter and sensor assembly Calibration port Unscrew cap to apply calibration gas Sensor element assembly Sensor cable plug Calibration switch Push to enter cal mode 40 200 mV mVDC B...

Page 10: ...me exposure to liquid ammonia poisoning due to silicon based oils or lubricants sulfur compounds or high concentrations of chlorine gas Maintenance Sensor Replacement part GG VL2 NH3 RS When the senso...

Page 11: ...1 Certified to CSA C22 2 No 61010 1 Troubleshooting Sensor Fault 0 5 mA signal output Indications any or all Red LED on transmitter lit and voltage signal at testpoints is 5 mVdc 5 mA output PLC disp...

Page 12: ...e or defects attributable to repair of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this...

Page 13: ...13 GG VL2 NH3...

Page 14: ...14 GG VL2 NH3...

Page 15: ...15 GG VL2 NH3...

Page 16: ...ctiengineering com 866 394 5861 GG VL2 DOC1 4 20180808...

Reviews: