GG-CO2

Maintenance

The GG-CO2 was designed for long life and minimal 

maintenance. For proper operation it is essential 

that the test and calibration schedule be adhered to. 

Calibration Technologies recommends the following 

maintenance schedule 

Maintenance Guidelines: 

•  The sensor is shipped with a factory calibration.  

Sensor should be calibrated 6 months from 

purchase date.

•  Calibrate the detector at least once every 6 months. 
• 

Calibration should be performed with certified 

calibration gas.  Calibration kits and replacement 

cylinders are available from Calibration 

Technologies.

•  All tests and calibrations must be logged. 
•  Always disconnect power at the controller before 

performing any wiring at the sensor.

Sensor Life:

  Typical sensor life of the GG-CO2 is five 

to seven years.  Failure of the infrared sensor happens 

normally when the infrared source opens or breaks, 

similar to an incandescent light bulb filament.  If this 

occurs, the sensor will produce a continuous fault 

indication signal of 0.5 mA and the fault LED will be 

lit.  Contact Calibration Technologies for a sensor 

replacement.  

Summary of Contents for GG-CO2

Page 1: ...Installation and Operation Manual GG CO2 CARBON DIOXIDE GAS SENSOR...

Page 2: ...ly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Page 3: ...920 N Tradewinds Pkwy Columbia MO 65201 866 394 5861 Sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6 Oper...

Page 4: ...cycles etc The circuit board is sealed in potting compound completely protecting sensitive electronic components and copper tracing from corrosion The specially vented chemical resistant polycarbonat...

Page 5: ...variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws should be screwed into the studs Mount sensor enclosur...

Page 6: ...elded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections should be soldered Ground...

Page 7: ...asure sensor output in mA Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 2 hours the unit can be zero calibrated by the...

Page 8: ...8 GG CO2 Figure 2 Sensor output and zero span adjustments Span and Zero adjustments 40 200 mV mVDC Black Red Calibration Gas Port...

Page 9: ...ld be performed with certified calibration gas Calibration kits and replacement cylinders are available from Calibration Technologies All tests and calibrations must be logged Always disconnect power...

Page 10: ...cale Repeatability 1 of full scale Wiring Connections 3 conductor shielded stranded 20 AWG cable General Cable C2525A or equivalent up to 1500 ft Terminal Block Plug Field Wiring 26 12 AWG torque 4 5...

Page 11: ...ct by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper storage ins...

Page 12: ...ctiengineering com 866 394 5861 GG CO2 DOC1 0 20190604...

Reviews: